1
IM 77C01U01-01E
1st Edition : Dec. 26, 2000-00
■
How to Install
NOTE
(1) To install the product, select a location where:
• no one may accidentally touch the terminals,
• mechanical vibrations are minimal,
• corrosive gas is minimal,
• Ambient temperature: 0 to 50
°
C; Ambient humidity: 50 to 90%RH
And the fluctuation is minimal,
• no direct radiant heat is present,
• no magnetic disturbances are caused,
• no wind blows against the terminal board (reference junction compensation ele-
ment),
• no water is splashed,
• no flammable materials are around,
(2)
Make sure to connect the grounding.
(3)
Turn off the product before installation and wiring.
(4)
Use the power supply within specifications.
(5)
Observe the following instructions for correct installation:
Recommended panel thickness is 1 to 10mm.
Install the product horizontally.
Install the product using attached fixture from the backside of the product.
Turn the screw only up to 180
°
after the screw touches the mounting panel to prevent
the case deformation by tightening the screw excessively.
(6)
Observe the following instructions for correct wiring:
Terminal connection screw is M3.5. Use the crimp-on terminals applicable to M3.5
screw for wiring.
Applicable wire size for input signal and power supply is 1.25mm
2
or more of cross
sectional area.