3. MODBUS Protocol
IM 249x-COMM
14
To change the baud rate press Inc. To move to the mode setting press Next.
The symbols are:
Baud
rate:
96 – 9600 bps
Trans
mode:
r – RTU
Parity:
n – no parity
48 – 4800
A – ASCII
E – even
24 – 2400
o – odd
12 – 1200
When you are finished changing the settings press Set. All the values will blink.
Press Set again to save the values and return to the first setting in the cycle.
•
Out of range floating-point values are shown as +/-3.40282347 X 10
38
.
•
The PSP uses a Motorola microcontroller. This means that Intel-based software,
such as Windows, might interpret the floating-point data transmitted from the
Power Series Plus as “swapped”.
•
A Watt/VAR/PF meter cannot access the Volt, Amp or Hertz registers and other
meters cannot access the Watt, VAR or PF registers.
•
VARs and PF are negative values if leading and positive if lagging.
•
Min and Max for VARs and PF disregard lead and lag. The smallest absolute
value is always the Min and the largest absolute value is always the Max.