PH450G/SC450G/ISC450G

pH/ORP/Conductivity Converters

HART Communication

TI 12A01A01-60EN

TI 12A01A01-60EN

©Copyright Sep. 2017

1st Edition Oct. 2017

CONTENTS

n

 

What is HART Communication? ...........................................................2

n

  Downloading and installing DD files

 ....................................................2

l

 

Before using FieldMate

 .....................................................................................2

l

 

Installing the DD File

 .........................................................................................3

l

 

Connecting Setup Tool

 .....................................................................................3

n

  Functions Available via HART Communication

 ..................................3

n

  Operational Precaution

 ..........................................................................4

l

 

Setting on the PH450G/SC450G/ISC450G and a setup tool 

(communication tool): ......................................................................................4

l

 

Operation with handling all the parameters of the PH450G/SC450G/

ISC450G:

 .............................................................................................................4

n

 

DD Online Parameters for PH450G (Device revision 2, DD file revision 

2) ..4

n

 

DD Online Parameters for SC450G (Device revision 2, DD file revision 2)

  .. 21

n

 

DD Online Parameters for ISC450G (Device revision 2, DD file 

revision 2)

 ................................................................................................36

Revision Information

 .....................................................................................

51

Summary of Contents for PH450G

Page 1: ...3 l Connecting Setup Tool 3 n Functions Available via HART Communication 3 n Operational Precaution 4 l Setting on the PH450G SC450G ISC450G and a setup tool communication tool 4 l Operation with hand...

Page 2: ...ons specific to the PH450G SC450G ISC450G FieldMate contains the versions of DD files at the time when sold To download the latest version of DD files visit our library by clicking the following link...

Page 3: ...th a four digit number such as 0102 xxxdd The first two digits 01 in the example above indicate the device revision The following two digits 02 in the example above indicate the DD revision Use the la...

Page 4: ...handling all the parameters of the PH450G SC450G ISC450G PH450G SC450G ISC450G has a lot of parameters Accessing many parameters may take several minutes n DD Online Parameters for PH450G Device revi...

Page 5: ...Meas type pH pH rH pH ORP R Sensor mV Sensor type pH pH ORP R mV ORP zero Sensor type ORP or Sensor type pH ORP Meas type ORP pH ORP R mV ORP slope Sensor type ORP or Sensor type pH ORP Meas type ORP...

Page 6: ...temp R W Numeric value 0 000000 to 100 000000 Temp unit C 3 2 0 0 0 0 0 0 t o 212 000000 Temp unit F C F Note Comp method Sensor type pH or Sensor type pH ORP Meas type pH pH rH pH ORP rH R W None TC...

Page 7: ...P Zero hi lim Sensor type ORP or Sensor type pH ORP Meas type ORP pH ORP R W Numeric value 0 000000 to 1500 000000 mV ORP Zero lo lim Sensor type ORP or Sensor type pH ORP Meas type ORP pH ORP R W Num...

Page 8: ...20001 Impedance setting Input 1 impedance R W Low High Imp 1 low limit Input 1 impedance Low R W Numeric value 1000 000000 to 1000000 000000 kOhm The use of Built in DTM causes an error and disables a...

Page 9: ...00 to 3600 000000 s PID D time Type Control Func PID R W Numeric value 0 000000 to 60 000000 s Burn Type Control R W Off Low High Expire time Type Control R W Numeric value 0 000000 to 1800 000000 s F...

Page 10: ...l R W direct reverse PID MR Type Control Func P R W Numeric value 0 000000 to 100 000000 PID I time Type Control Func PI PID R W Numeric value 1 000000 to 3600 000000 s PID D time Type Control Func PI...

Page 11: ...type pH ORP Meas type rH pH rH PID SP Type Control R W Numeric value no limit pH Param PH C F Param TEMPERATURE mV Param ORP rH Param RH Note PID Rng Type Control R W Numeric value g r e a t e r t h...

Page 12: ...larm R W Numeric value 1 000000 to 1800 000000 s Func Type Fail R W Hard Soft Fail Hard Fail Only The use of Built i n D T M d i s a b l e s Hard Soft Fail to be selected Use a device DTM or set at th...

Page 13: ...Param TEMPERATURE mV Param ORP rH Param RH Note PID Rng Type Control R W Numeric value greater than 0 001000 PID Dir Type Control R W direct reverse PID MR Type Control Func P R W Numeric value 0 0000...

Page 14: ...000 s Expire time Type Alarm R W Numeric value 1 000000 to 1800 000000 s Func Type Fail R W Hard Soft Fail Hard Fail Only The use of Built in DTM disables Hard S o f t F a i l t o b e selected Func Ty...

Page 15: ...Param TEMPERATURE mV Param ORP rH Param RH Note PID Rng Type Control R W Numeric value greater than 0 001000 PID Dir Type Control R W direct reverse PID MR Type Control Func P R W Numeric value 0 0000...

Page 16: ...R W Numeric value 1 000000 to 1800 000000 s Func Type Fail R W Hard Soft Fail Hard Fail Only The use of Built i n D T M d i s a b l e s Hard Soft Fail to be selected Use a device DTM or set at the fro...

Page 17: ...m TEMPERATURE mV Param ORP rH Param RH Note PID Rng Type Control R W Numeric value g r e a t e r t h a n 0 001000 PID Dir Type Control R W direct reverse PID MR Type Control Func P R W Numeric value 0...

Page 18: ...s Expire time Type Alarm R W Numeric value 1 000000 to 1800 000000 s Func Type Fail R W Hard Soft Fail Hard Fail Only The use of Built i n D T M d i s a b l e s disabled Hard Soft Fail to be selected...

Page 19: ...R W Off Warn Fail Temp too high R W Off Warn Fail Temp too low R W Off Warn Fail Matrix config Sensor type pH or Sensor type pH ORP Meas type pH pH rH pH ORP R W Warn Fail ORP too high Sensor type OR...

Page 20: ...point PID range Manual reset PID I time PID D time Control type DC period time Max pulse freq Alarm setpoint Alarm direction Alarm hysteresis Alarm delay time Expire time Wash setup Erase logbook R W...

Page 21: ...e use of Built in DTM may make characters displayed as unintended ones C is replaced with C F is replaced with F Use a device DTM or check at the front panel display n DD Online Parameters for SC450G...

Page 22: ...m Adj CC R cm m Method SC1 R Method SC2 R Polarization R Ohms R ohm USP R Zoom output mA1 value R mA mA2 value R mA S1 perc R S2 perc R S3 perc R S4 perc R Zoom device Serial number R Software Revisi...

Page 23: ...R W None TC Nacl Matrix Matrix SC1 Method SC1 Matrix R W Ammonia 0 50ppb Morpholine 0 500 ppb Ammonia 15 30 H2SO4 0 27 H2SO4 39 85 H2SO4 93 100 NaOH 0 15 NaOH 25 50 HCl 0 200 ppb HCl 0 18 Hcl24 44 HNO...

Page 24: ...250 d Concentration Additional table Measure Conc only R W Disable Enable Conc table unit Measure Conc only R W ppt ppm ppb Output setup mA1 setup Type R W Off Control Output Simulate Func Type Off R...

Page 25: ...trol R W Numeric value 0 000000 to 1800 000000 s Func Type Output R W Linear Table Param Type Output R W NONE CONDUCT Measure Cond only Cond Conc RESIST1 Measure res only CONCENT1 Measure Conc only TE...

Page 26: ...SP Type Control R W Numeric value no limit S cm S m Param CONDUCT1 2 p p b P a r a m CONCENT1 O cm O m Param RESIST1 2 C F Param TEMPERATURE P a r a m CONCENT2 Note PID Rng Type Control R W Numeric va...

Page 27: ...t S cm S m Param CONDUCT1 2 ppb Param CONCENT1 O cm O m Param RESIST1 2 C F Param TEMPERATURE Param CONCENT2 Note Lin 100 Type Output Func Linear R W Numeric value no limit S cm S m Param CONDUCT1 2 p...

Page 28: ...alue greater than 0 000000 S cm S m Param CONDUCT1 2 p p b P a r a m CONCENT1 O cm O m Param RESIST1 2 C F Param TEMPERATURE P a r a m CONCENT2 Note PID Dir Type Control R W direct reverse PID MR Type...

Page 29: ...lue greater than 0 000000 S cm S m Param CONDUCT1 2 p p b P a r a m CONCENT1 O cm O m Param RESIST1 2 C F Param TEMPERATURE P a r a m CONCENT2 Note Alarm delay Type Alarm R W Numeric value 1 000000 to...

Page 30: ...ol R W Numeric value greater than 0 000000 S cm S m Param CONDUCT1 2 p p b P a r a m CONCENT1 O cm O m Param RESIST1 2 C F Param TEMPERATURE P a r a m CONCENT2 PID Dir Type Control R W direct reverse...

Page 31: ...rm R W Numeric value greater than 0 000000 S cm S m Param CONDUCT1 2 p p b P a r a m CONCENT1 O cm O m Param RESIST1 2 C F Param TEMPERATURE P a r a m CONCENT2 Note Alarm delay Type Alarm R W Numeric...

Page 32: ...e 1 000000 to 3600 000000 s PID D time Type Control Func PID R W Numeric value 0 000000 to 60 000000 s Analog output Type Control R W PF DC Max freq Type Control Analog output PF R W Numeric value 1 0...

Page 33: ...am Type Control R W NONE CONDUCT Measure Cond only Cond Conc RESIST1 Measure res only CONCENT1 Measure Conc only TEMPERATURE CONDUCT2 Measure Cond only RESIST2 Measure res only CONCENT2 Measure Conc o...

Page 34: ...Low High Alarm hyst Type Alarm R W Numeric value greater than 0 000000 Alarm delay Type Alarm R W Numeric value 1 000000 to 1800 000000 Expire time Type Alarm R W Numeric value 1 000000 to 1800 00000...

Page 35: ...W Numeric value 0 000000 to 2 000000 S Res hi lim Measure Res only R W Numeric value 0 000000 to 10000000 000000 ohm Temp too high R W Off Warn Fail Temp too low R W Off Warn Fail Pol detected R W Off...

Page 36: ...DTM disables the setting properly Num resp preams R W Numeric value 0 to 255 The use of Built in DTM disables the setting properly Review Model R Distributor R Write protect R Manufacturer R Dev id R...

Page 37: ...2 value R mA S1 perc R S2 perc R S3 perc R S4 perc R Zoom device Serial number R Software Revision R Device Revision R Logbook Calibration Commissioning Input contact R W Disable Factor 10 mA1 Factor...

Page 38: ...0 15 NaOH 25 50 User defined 1 User defined 2 TC SC1 Method SC1 TC R W Numeric value 0 000000 to 3 5000000 Temp unit C 0 000000 to 2 000000 Temp unit F C F Note Method SC2 Measure Cond only Conc only...

Page 39: ...ly Cond Conc CONCENT1 Measure Conc Only TEMPERATURE CONCENT Measure Cond Conc CONDUCT2 Measure Cond Only CONCENT2 Measure Conc Only PID SP Type Control R W Numeric value no limit S cm S m Param CONDUC...

Page 40: ...ype Output Func Linear R W Numeric value no limit S cm S m Param CONDUCT1 2 p p b P a r a m CONCENT1 C F Param TEMPERATURE P a r a m CONCENT2 Note Lin 100 Type Output Func Linear R W Numeric value no...

Page 41: ...S m Param CONDUCT1 2 p p b P a r a m CONCENT1 C F Param TEMPERATURE P a r a m CONCENT2 Note PID Dir Type Control R W direct reverse PID MR Type Control Func P R W Numeric value 0 000000 to 100 000000...

Page 42: ...unc Type Simulate R Simulate Percentage Type Simulate R W Numeric value 0 000000 to 100 000000 S1 setup Type R W Off Control Alarm Fail Simulate HOLD Func Type Off R Off Func Type Control R W P PI PID...

Page 43: ...Measure Cond Conc CONDUCT2 Measure Cond Only CONCENT2 Measure Conc Only Alarm Sp Type Alarm R W Numeric value no limit Note Alarm dir Type Alarm R W Low High Alarm hyst Type Alarm R W Numeric value g...

Page 44: ...ter than 0 000000 S cm S m Param CONDUCT1 2 p p b P a r a m CONCENT1 C F Param TEMPERATURE P a r a m CONCENT2 Note PID Dir Type Control R W direct reverse PID MR Type Control Func P R W Numeric value...

Page 45: ...e greater than 0 000000 S cm S m Param CONDUCT1 2 ppb Param CONCENT1 C F Param TEMPERATURE Param CONCENT2 Note Alarm delay Type Alarm R W Numeric value 1 000000 to 1800 000000 s Expire time Type Alarm...

Page 46: ...ue 1 000000 to 3600 000000 s PID D time Type Control Func PID R W Numeric value 0 000000 to 60 000000 s Analog output Type Control R W PF DC Max freq Type Control Analog output PF R W Numeric value 1...

Page 47: ...ff Func Type Cntrol R W P PI PID Param Type Control R W NONE CONDUCT Measure Cond Only Cond Conc CONCENT1 Measure Conc Only TEMPERATURE CONCENT Measure Cond Conc CONDUCT2 Measure Cond Only CONCENT2 Me...

Page 48: ...hyst Type Alarm R W Numeric value greater than 0 000000 Alarm delay Type Alarm R W Numeric value 1 000000 to 1800 000000 Expire time Type Alarm R W Numeric value 1 000000 to 1800 000000 Func Type Fai...

Page 49: ...ual reset PID I time PID D time Burn Linear Damping time Expire time Multiple checkbox allows more than one option to be selected Contact logbook R W Contact setup PID setpoint PID range Manual reset...

Page 50: ...Review Model R Distributor R Write protect R Manufacturer R Dev id R Tag R Descriptor R Message R Date R Universal rev R Fld dev rev R Software rev R Poll addr R Num resp preams R Note Built in DTM ma...

Page 51: ...HART Communication Manual number TI 12A01A01 60EN Sep 2017 1st Edition Newly published n For further information visit Yokogawa website http www yokogawa com an Yokogawa Electric Corporation 2 9 32 N...