YOKOGAWA Juxta VJU7 User Manual Download Page 4

5.2  Settings Related to Communication 

Function

Set the following parameters when the communication function is 

specified for the output 2.

For more information on communication functions, see the user’s 

manual for VJ Series Communication Functions (IM 77J01J11-

01E).

5.2.1  Communication Protocol 

  Select the communication protocol from among PCLINK, 

PCLINK WITH SUM, MODBUS ASCII, MODBUS RTU and 

LADDER in 

[F01: PROTOCOL]

5.2.2  Communication Address 

  Set the address number of the converter numerically in a 

range of 1 to 99 in 

[F02: ADDRESS]

.

5.2.3  Baud Rate 

  Set the baud rate by selecting from among 1200, 2400, 4800, 

9600, 19200, and 38400 bps in 

[F03: BAUD RATE]

.

5.2.4  Parity 

  Select the parity from among NONE, EVEN and ODD in 

[F04: 

PARITY]

.

5.2.5  Data Length

  Select the data length from among 7 bits and 8 bits in 

[F05: 

DATA LEN]

.

5.2.6  Stop Bit 

  Select the stop bit from among 1 bit and 2 bits in 

[F06: STOP 

BIT]

.

5.2.7  Decimal Point Position 

  Number of decimals of input value (setting of D register 

[D0003]) can be set. Select the number of decimals from 

among 0 to 5 in 

[F07: INPUT DEC PT]

.     

5.3  Settings Related to Alarm Output 

Set the following parameters when the alarm output is specified 

for the output 2.

5.3.1  Alarm Setpoint 

  Set the alarm-1 setpoint and alarm-2 setpoint numerically 

in 

[E01: SET POINT1]

 and 

[E02: SET POINT2]

 for 

thermocouple input and RTD input or in 

[E03: SET POINT1]

 

and 

[E04: SET POINT2]

 for mV input. Set them in [°C/K] for 

temperature input or in [%] for mV input.

 •

Setting range: 0 to 100% of input range 

 •

Setting resolution: 0.1% (for mV input), 4 significant digits 

(for temperature input)

5.3.2  Direction of Alarm Action 

  Select the direction of alarm-1 action and that of alarm-2 

action from among HIGH ALM (high-limit alarm) and LOW 

ALM (low-limit alarm) in 

[E05: ALM1 ACTION]

 and 

[E06: 

ALM2 ACTION]

 •

To activate alarm status when input signal ≥ alarm setpoint, 

select HIGH ALM. 

 •

To activate alarm status when input signal ≤ alarm setpoint, 

select LOW ALM. 

5.3.3  Hysteresis 

  Set the alarm-1 hysteresis and alarm-2 hysteresis numerically 

in 

[E07: HYSTERESIS1]

 and 

[E08: HYSTERESIS2]

 for 

thermocouple input and RTD input or in 

[E09: HYSTERESIS1]

 

and 

[E10: HYSTERESIS2]

 for mV input.

  Hysteresis is a value added to the alarm setpoint in order for 

an alarm status to be released (to normal) after the alarm 

status has been activated. The alarm status will be released in 

the following conditions, depending on the direction of alarm 

action.

*  When HIGH ALM (high-limit alarm) is set: Alarm is released 

when input signal < (alarm setpoint - hysteresis). 

*  When LOW ALM (low-limit alarm) is set: Alarm is released 

when input signal > (alarm se hysteresis). 

  Set them in [°C/K] for temperature input or in [%] for mV input.

 •

Setting range: 0 to 100% of input range 

 •

Setting resolution: 0.1% (for mV input), 4 significant digits 

(for temperature input)

5.3.4  Alarm ON Delay and Alarm OFF Delay 

  Set the alarm-1 ON delay and alarm-2 ON delay numerically in 

[E11: ON DELAY1]

 and 

[E12: ON DELAY2]

. Set the alarm-1 

OFF delay and alarm-2 OFF delay numerically in 

[E13: OFF 

DELAY1]

 and 

[E14: OFF DELAY2]

  An alarm ON delay is a delay time from the establishment of 

alarm conditions to its output; an alarm OFF delay is a delay 

time from the establishment of return-to-normal conditions to 

its output. 

 •

Setting range: 0 to 999 seconds 

 • Setting resolution: 

1 second (However, about 0.2 second is 

to be added to the set time to prevent wrong operation.) 

  For example, when an alarm ON delay is set to 1 second, 

alarm output is generated if alarm status continues for 1 

second or more after the input value exceeds the alarm 

setpoint. Furthermore, when an alarm OFF delay is set 

to 2 seconds, alarm output is released if normal condition 

continues for 2 seconds or more after the input value has 

returned to normal from the alarm status.

5.3.5  Direction of Relay Action 

  Select the direction of relay energizing in alarm-1 normal 

condition and alarm-2 normal condition from among NRM DE-

ENERGIZED (de-energized under normal condition) and NRM 

ENERGIZED (energized under normal condition) in 

[E15: RL1 

ACTION]

 and 

[E16: RL2 ACTION]

6.  DESCRIPTION OF ALARM ACTIONS 

This chapter describes examples of alarm actions under the 

following conditions. 

Item

Alarm 1

Alarm 2

Parameter

Setpoint

Parameter

Setpoint

Direction of alarm 

action

E05: ALM1 ACTION High-limit 

alarm

E06: ALM2 ACTION

Low-limit 

alarm

Alarm setting

E03: SET POINT1

80%

E04 : SET POINT2

15%

Hysteresis

E09: HYSTERESIS1 10%

E10 : HYSTERESIS2 5%

Alarm ON delay

E11: ON DELAY1

1 sec

E12 : ON DELAY2

3 sec

Alarm OFF delay

E13: OFF DELAY1

2 sec

E14 : OFF DELAY2

4 sec

Description of  

alarm actions

The alarm is output if the 

condition where the input value 

is 80% or more of high-limit 

alarm continues for 1 second 

or more.

After the alarm is output, when 

the condition where the input 

value is less than 70% of 

high-limit alarm continues for 

2 seconds or more, the status 

returns to normal.

The alarm is output if the 

condition where the input value 

is 15% or less of low-limit 

alarm continues for 3 seconds 

or more.

After the alarm is output, when 

the condition where the input 

value is more than 20% of 

low-limit alarm continues for 

4 seconds or more, the status 

returns to normal.

Figure 6.1

Alarm-1 action

Alarm-2 action

Normal

Normal

Normal

Normal

Alarm

Alarm

[

]

0

20

15

40

60

80

100

1 s.

2 s.

3 s.

4 s.

Alarm-2 hysteresis (5%)

Alarm-1 hysteresis (10%)

Alarm-1 setpoint (80%)

Alarm-2 setpoint (15%)

Elapsed time s.

[1]

[2]

[3]

[4]

Alarm-1 

ON delay

Alarm-2 

ON delay

Alarm-2 

OFF delay

Alarm-1 

OFF delay

Alarm conditions established

Alarm conditions

established

Normal conditions

established

Normal conditions established

High-limit alarm ON

Low-limit alarm ON

High-limit alarm OFF

Low-limit alarm OFF

[1] Alarm status does not continue for more than 1 second after the 

alarm conditions are established at alarm 1.

[2] Normal status does not continue for more than 2 seconds after 

the normal conditions are established at alarm 1.

[3] Alarm status does not continue for more than 3 seconds after the 

alarm conditions are established at alarm 2.

[4] Normal status does not continue for more than 4 seconds after 

the normal conditions are established at alarm 2.

7.  LIST OF PARAMETERS

Parameter Display Item

MODEL

Model

TAG NO

Tag no.

SELF CHK

Self-check result

A

DISPLAY1

Display 1

*2

A01

INPUT1

Input value 1

A09

OUTPUT1

Output value 1

A10

OUTPUT2

Output value 2

A15

ALM1 STATUS

Alarm-1 status

A16

ALM2 STATUS

Alarm-2 status

A54

STATUS

Status

*1

A56

REV NO

Rev. no.

A58

MENU REV

MENU REV

A60

SELF CHK

Self-check result

4

IM 77J01U07-01E 10th Edition

Summary of Contents for Juxta VJU7

Page 1: ...TIONARY NOTES FOR SAFE USE OF THE PRODUCT This User s Manual should be carefully read before installing and operating the product Please keep this User s Manual for future reference For more information of the safety precautions please refer to the Precautions on the Use of the JUXTA Series IM 77J01A00 91Z1 The related manuals and general specifications are shown in the table below Doc Name Doc Nu...

Page 2: ...ing or damage Before turning on the power ensure the following Power supply voltage and input signal value applied to the product should meet the required specifications The external wiring to the terminals and wiring to ground are as specifications Wiring should be connected to the terminals on the socket of the product The terminals for external connections are of M3 screws Use crimp on terminal...

Page 3: ...7 select the RTD type to use in D09 RTD TYPE Furthermore for thermocouple or RTD input select the temperature unit in D21 UNIT 5 1 2 Input Range Set the 0 value of input range in D24 INPUT1 L_RNG and the 100 value of input range in D25 INPUT1 H_RNG numerically within the following specified range Input type TC Measurable range C JIS C 1602 IEC 60584 1 ITS 90 TYPE K 270 to 1372 JIS C 1602 IEC 60584...

Page 4: ... delay time from the establishment of return to normal conditions to its output Setting range 0 to 999 seconds Setting resolution 1 second However about 0 2 second is to be added to the set time to prevent wrong operation For example when an alarm ON delay is set to 1 second alarm output is generated if alarm status continues for 1 second or more after the input value exceeds the alarm setpoint Fu...

Page 5: ...n adjustment of output 2 P60 SELF CHK Self check result Q TEST Test 2 Q01 RJC ON OFF of RJC Q04 OUT1 TEST Forced output output 1 Q05 OUT2 TEST Forced output output 2 Q10 ALM1 TEST Forced output alarm 1 Q11 ALM2 TEST Forced output alarm 2 Q60 SELF CHK Self check result 1 The Status is displayed for service personnel to see history records 2 There are items not displayed depending on what input sens...

Page 6: ...llation Appliances portable equipments etc III CAT III For measurements performed in the building installation Distribution board circuit breaker etc IV CAT IV For measurements performed at the source of the low voltage installation Overhead wire cable systems etc EMC standards CE EN 61326 1 Class A Table 2 EN 61326 2 3 The instrument continues to operate at a measurement accuracy of within 20 of ...

Reviews: