6.  DESCRIPTION OF ALARM ACTIONS 

This chapter describes examples of alarm actions under the 

following conditions. 

Item

Alarm 1

Alarm 2

Parameter

Setpoint Parameter

Setpoint

Direction of alarm 

action

E05: ALM1 ACTION High-limit 

alarm

E06: ALM2 ACTION Low-limit 

alarm

Alarm setting

E03: SET POINT1

80%

E04 : SET POINT2

15%

Hysteresis

E09: HYSTERESIS1

10%

E10 : HYSTERESIS2

5%

Alarm ON delay

E11: ON DELAY1

1 sec

E12 : ON DELAY2

3 sec

Alarm OFF delay

E13: OFF DELAY1

2 sec

E14 : OFF DELAY2

4 sec

Description of  

alarm actions

The alarm is output if the 

condition where the input value 

is 80% or more of high-limit 

alarm continues for 1 second 

or more.

After the alarm is output, when 

the condition where the input 

value is less than 70% of 

high-limit alarm continues for 

2 seconds or more, the status 

returns to normal.

The alarm is output if the 

condition where the input value 

is 15% or less of low-limit 

alarm continues for 3 seconds 

or more.

After the alarm is output, when 

the condition where the input 

value is more than 20% of 

low-limit alarm continues for 

4 seconds or more, the status 

returns to normal.

Figure 6.1

Alarm-1 action

Alarm-2 action

Normal

Normal

Normal

Normal

Alarm

Alarm

[%]

0

20

15

40

60

80

100

1 sec.

2 sec.

3 sec.

4 sec.

Alarm-2 hysteresis (5%)

Alarm-1 hysteresis (10%)

Alarm-1 setpoint (80%)

Alarm-2 setpoint (15%)

Elapsed time 1 sec.

[1]

[2]

[3]

[4]

[1]: Alarm status does not continue for more than 1 second after 

the alarm conditions are established at alarm-1.

[2]: Normal status does not continue for more than 2 seconds after 

the normal conditions are established at alarm-1.

[3]: Alarm status does not continue for more than 3 seconds after 

the alarm conditions are established at alarm-2.

[4]: Normal status does not continue for more than 4 seconds after 

the normal conditions are established at alarm-2.

Alarm-1 

ON delay

Alarm-2 

ON delay

Alarm-2 

OFF delay

Alarm-1 

OFF delay

Alarm conditions 

established

Alarm conditions

established

Normal conditions

established

Normal conditions established

High-limit alarm ON

Low-limit alarm ON

High-limit alarm OFF

Low-limit alarm OFF

7.  LIST OF PARAMETERS

Parameter Display

Item

MODEL

Model

TAG NO

Tag no.

SELF CHK

Self-check result

A

DISPLAY1

Display1

A01 INPUT1

Input value

A06 OUTPUT

Output value

A15

ALM1 STATUS

Alarm-1 status

A16

ALM2 STATUS

Alarm-2 status

A54 STATUS

Status

(*1)

A56 REV NO

Rev. no.

A58 MENU REV

MENU REV

A60

SELF CHK

Self-check result

B

DISPLAY2

Display2

B01

INPUT1

Input value

B06

OUTPUT

Output value

B15 ALM1 STATUS

Alarm-1 status

B16 ALM2 STATUS

Alarm-2 status

B60 SELF CHK

Self-check result

D

SET (I/O)

Setting (I/O)

(*2)

D01 TAG NO.1

Tag no. 1

D02 TAG NO.2

Tag no. 2

D03 COMMENT1

Comment 1

D04 COMMENT2

Comment 2

D12

INP TYPE

Input type

D13 IN RESIST

Input resistance

D20 UNIT

Output Range Unit

D24

INPUT1 L_RNG

Input1 low range

D25

INPUT1 H_RNG

Input1 high range

D30

OUT L_RNG

Output low range

D31

OUT H_RNG

Output high range

D44

LOW CUT

Output low cut point

D55

PULSE TYPE

Pulse width type

D56

PULSE WIDTH

Pulse width time

D57

S/W FILTER

Software Filter

D59 NMRR

Frequency setting

(*3)

D60

SELF CHK

Self-check result

E

SET(ALM)

Setting (alarm output)

(*2)

E03 SET POINT1

Alarm-1 setting

E04 SET POINT2

Alarm-2 setting

E05

ALM1 ACTION

Direction of alarm-1 action

E06

ALM2 ACTION

Direction of alarm-2 action

E09

HYSTERESIS1

Alarm-1 hysteresis

E10

HYSTERESIS2

Alarm-2 hysteresis

E11

ON DELAY1

Alarm-1 ON delay setting

E12

ON DELAY2

Alarm-2 ON delay setting

E13

OFF DELAY1

Alarm-1 OFF delay setting

E14

OFF DELAY2

Alarm-2 OFF delay setting

E15

RL1 ACTION

Direction of alarm-1 relay 

action

E16

RL2 ACTION

Direction of alarm-2 relay 

action

E60

SELF CHK

Self-check result

F

SET(COM)

Setting (communication)

(*2)

F01

PROTOCOL

Communication protocol

F02 ADDRESS

Address

F03

BAUD RATE

Baud rate

F04

PARITY

Parity

F05

DATA LEN

Data Length

F06

STOP BIT

Stop bit

F07 INPUT DEC PT

Decimal point position of 

input

F60

SELF CHK

Self-check result

P

ADJUST

Adjustment

P04 IN1 ZERO ADJ1

Zero adjustment of input

P04 IN1 SPAN ADJ1

Span adjustment of input

P40 RESISTOR ADJ

Adjustment of external input 

resistance

P60

SELF CHK

Self-check result

Q

TEST

Test

(*2)

Q10

ALM1 TEST

Forced output (alarm 1)

Q11

ALM2 TEST

Forced output (alarm 2)

Q30 OUT TEST

Forced output (Pulse)

Q60

SELF  CHK

Self-check result

*1

The Status is displayed for service personnel to see 

history records.

*2

There are items not displayed depending on what output-2 

is specified.

*3

The parameters are the items to be set at the factory.

5

IM 77J01Q17-01E