6. DESCRIPTION OF ALARM ACTIONS
This chapter describes examples of alarm actions under the
following conditions.
Item
Alarm 1
Alarm 2
Parameter
Setpoint Parameter
Setpoint
Direction of alarm
action
E05: ALM1 ACTION High-limit
alarm
E06: ALM2 ACTION Low-limit
alarm
Alarm setting
E03: SET POINT1
80%
E04 : SET POINT2
15%
Hysteresis
E09: HYSTERESIS1
10%
E10 : HYSTERESIS2
5%
Alarm ON delay
E11: ON DELAY1
1 sec
E12 : ON DELAY2
3 sec
Alarm OFF delay
E13: OFF DELAY1
2 sec
E14 : OFF DELAY2
4 sec
Description of
alarm actions
The alarm is output if the
condition where the input value
is 80% or more of high-limit
alarm continues for 1 second
or more.
After the alarm is output, when
the condition where the input
value is less than 70% of
high-limit alarm continues for
2 seconds or more, the status
returns to normal.
The alarm is output if the
condition where the input value
is 15% or less of low-limit
alarm continues for 3 seconds
or more.
After the alarm is output, when
the condition where the input
value is more than 20% of
low-limit alarm continues for
4 seconds or more, the status
returns to normal.
Figure 6.1
Alarm-1 action
Alarm-2 action
Normal
Normal
Normal
Normal
Alarm
Alarm
[%]
0
20
15
40
60
80
100
1 sec.
2 sec.
3 sec.
4 sec.
Alarm-2 hysteresis (5%)
Alarm-1 hysteresis (10%)
Alarm-1 setpoint (80%)
Alarm-2 setpoint (15%)
Elapsed time 1 sec.
[1]
[2]
[3]
[4]
[1]: Alarm status does not continue for more than 1 second after
the alarm conditions are established at alarm-1.
[2]: Normal status does not continue for more than 2 seconds after
the normal conditions are established at alarm-1.
[3]: Alarm status does not continue for more than 3 seconds after
the alarm conditions are established at alarm-2.
[4]: Normal status does not continue for more than 4 seconds after
the normal conditions are established at alarm-2.
Alarm-1
ON delay
Alarm-2
ON delay
Alarm-2
OFF delay
Alarm-1
OFF delay
Alarm conditions
established
Alarm conditions
established
Normal conditions
established
Normal conditions established
High-limit alarm ON
Low-limit alarm ON
High-limit alarm OFF
Low-limit alarm OFF
7. LIST OF PARAMETERS
Parameter Display
Item
MODEL
Model
TAG NO
Tag no.
SELF CHK
Self-check result
A
DISPLAY1
Display1
A01 INPUT1
Input value
A06 OUTPUT
Output value
A15
ALM1 STATUS
Alarm-1 status
A16
ALM2 STATUS
Alarm-2 status
A54 STATUS
Status
(*1)
A56 REV NO
Rev. no.
A58 MENU REV
MENU REV
A60
SELF CHK
Self-check result
B
DISPLAY2
Display2
B01
INPUT1
Input value
B06
OUTPUT
Output value
B15 ALM1 STATUS
Alarm-1 status
B16 ALM2 STATUS
Alarm-2 status
B60 SELF CHK
Self-check result
D
SET (I/O)
Setting (I/O)
(*2)
D01 TAG NO.1
Tag no. 1
D02 TAG NO.2
Tag no. 2
D03 COMMENT1
Comment 1
D04 COMMENT2
Comment 2
D12
INP TYPE
Input type
D13 IN RESIST
Input resistance
D20 UNIT
Output Range Unit
D24
INPUT1 L_RNG
Input1 low range
D25
INPUT1 H_RNG
Input1 high range
D30
OUT L_RNG
Output low range
D31
OUT H_RNG
Output high range
D44
LOW CUT
Output low cut point
D55
PULSE TYPE
Pulse width type
D56
PULSE WIDTH
Pulse width time
D57
S/W FILTER
Software Filter
D59 NMRR
Frequency setting
(*3)
D60
SELF CHK
Self-check result
E
SET(ALM)
Setting (alarm output)
(*2)
E03 SET POINT1
Alarm-1 setting
E04 SET POINT2
Alarm-2 setting
E05
ALM1 ACTION
Direction of alarm-1 action
E06
ALM2 ACTION
Direction of alarm-2 action
E09
HYSTERESIS1
Alarm-1 hysteresis
E10
HYSTERESIS2
Alarm-2 hysteresis
E11
ON DELAY1
Alarm-1 ON delay setting
E12
ON DELAY2
Alarm-2 ON delay setting
E13
OFF DELAY1
Alarm-1 OFF delay setting
E14
OFF DELAY2
Alarm-2 OFF delay setting
E15
RL1 ACTION
Direction of alarm-1 relay
action
E16
RL2 ACTION
Direction of alarm-2 relay
action
E60
SELF CHK
Self-check result
F
SET(COM)
Setting (communication)
(*2)
F01
PROTOCOL
Communication protocol
F02 ADDRESS
Address
F03
BAUD RATE
Baud rate
F04
PARITY
Parity
F05
DATA LEN
Data Length
F06
STOP BIT
Stop bit
F07 INPUT DEC PT
Decimal point position of
input
F60
SELF CHK
Self-check result
P
ADJUST
Adjustment
P04 IN1 ZERO ADJ1
Zero adjustment of input
P04 IN1 SPAN ADJ1
Span adjustment of input
P40 RESISTOR ADJ
Adjustment of external input
resistance
P60
SELF CHK
Self-check result
Q
TEST
Test
(*2)
Q10
ALM1 TEST
Forced output (alarm 1)
Q11
ALM2 TEST
Forced output (alarm 2)
Q30 OUT TEST
Forced output (Pulse)
Q60
SELF CHK
Self-check result
*1
The Status is displayed for service personnel to see
history records.
*2
There are items not displayed depending on what output-2
is specified.
*3
The parameters are the items to be set at the factory.
5
IM 77J01Q17-01E
6th Edition