background image

IM 77J04R31-01E 2nd Edition  Oct. 15, 2019-00

6

The previously adjusted value 

will be reset.

The decimal point blinks during 

data change. 

This causes parameter "AH" and the measured value to 

appear alternately. 

 

Press the UP or DOWN key.  

The decimal point blinks. 

 

Press the SET/ENT key. 

The value before adjustment (153.9) appears on the DATA 

display. 

This completes the input adjustment for the MVRK. 

Press the SET/ENT key to display parameter "RST." 

Press the UP key to display "ON" on the DATA display. 

Press the SET/ENT key.

This resets the previously adjusted value.

Setup Parameter Screen 2

Using the 6-dial variable resistor, apply resistance equivalent 
to the input 150°C to the MVRK.

If additional re-adjustment must be made, take the following steps and then perform the 

procedure above. 

Press               to display 

"RST." 

Press             to display 

"ON."

Press            .

This completes the input 

adjustment.

The decimal point blinks.

The measured value and 

parameter AH are displayed 

alternately.

Press              or             .

Press             . 

11.  SETTING ACTIVE COLOR PV DISPLAY (PV DISPLAY COLOR 

CHANGING FUNCTION)

11.1 Setting Ranges and Factory-Set Values 

Setup Parameter Screen 1

Parameter 

Symbol

Parameter Name

Setting Range

Factory-Set 

Value

High limit for PV display 

color change (PCH)

When PV display color mode (PCM) is 6 or 7: PCL+1digit 

to 9999

When PV display color mode (PCM) is 8 or 9:

-100.0 to 100.0% of the measured input range

*  The setting range depends on the setting of the decimal 

point position (SDP).

Low limit for PV display 

color change (PCL)

When PV display color mode (PCM) is 6 or 7:

-1999 to PCH-1digit

When PV display color mode (PCM) is 8 or 9:

-100.0 to 100.0% of the measured input range

*  The setting range depends on the setting of the decimal 

point position (SDP).

Setup Parameter Screen 2

Parameter 

Symbol

Parameter Name

Setting Range

Factory-Set 

Value

PV display color mode 

(PCM)

0: Fixed in green

 

1: Fixed in red

2:  Link to alarm 1 

(under normal condition: green; at alarm status: red) 

3:  Link to alarm 1 

(under normal condition: red; at alarm status: green) 

4:  Link to alarm 1 and alarm 2 

(under normal condition: green; at alarm status: red) 

5:  Link to alarm 1 and alarm 2 

(under normal condition: red; at alarm status: green) 

6:  PV limit*

 

(when more than PCL, less than PCH: green; when 

PCL or less, PCH or more: red)

7:  PV limit* 

(when more than PCL, less than PCH:red; when PCL 

or less, PCH or more: green)

8:  SP deviation* 

(when more than SP-PCL, less than SP+PCH: green; 

when SP-PCL or less, SP+PCH or more: red)

9:  SP deviation*

 

(when more than SP-PCL, less than SP+PCH: red; 

when SP-PCL or less, SP+PCH or more: green)

10:  Link to alarm 1 to alarm 4 

(under normal condition: green; at alarm status: red) 

11:  Link to alarm 1 to alarm 4 

(under normal condition: red; at alarm status: green)

1

*:    PV display color is changed linking to the setting range of high limit (PCH) and low limit (PCL) for PV display 

color change.

11.2 Setting Active Color PV Display

This section describes an example of setting the PV display color mode (PCM) to “6,” high limit for 

PV display color change (PCH) to “70.0” and low limit (PCL) to “20.0.” 

The procedure below begins with the condition in which the Setup Parameter Screen 2 is displayed.

When you press the SET/ENT key for more than 3 sec. 

with the Operation Parameter Screen displayed, the Setup 

Parameter Screen 1 appears.

Press this key for 

more than 3 sec. 

Operation Parameter Screen 

Press the SET/ENT key to display parameter "PCM."

Press the UP or DOWN key to display "6" on the DATA 

display.

The decimal point blinks during 

data change. 

This completes the process for 

setting the PV display color mode.

Press               to display 

 

    "PCM." 

Press             or               
to display  "6."

"

Press              .

Press              for more

                           than 3 sec. 

Press the SET/ENT key to accept PV display color 

mode "6." 

Press the SET/ENT key for more than 3 sec.

This causes the Operation Parameter Screen to appear.

Setting the PV display color mode

Setup Parameter Screen 2 

 

Continue to the upper right

Press the SET/ENT key to display parameter "PCH."

Press the UP or DOWN key to display "70.0" on the DATA 

display.

The decimal point blinks during 

data change. 

This completes the process for 

setting the high limit for PV display

color change.

Press               to display 

 

    "PCH." 

Press             or               
to display  "70.0."

Press              .

Press              to display

                             "PCL."     

Press the SET/ENT key to accept the high limit for PV 

display color change "70.0." 

Press the SET/ENT key to display parameter "PCL." 

Press the UP or DOWN key to display "20.0" on the DATA 

display.

The decimal point blinks during 

data change. 

This completes the process for 

setting the low limit for PV display

color change.

Press             or               
to display  "20.0."

Press              .

Press              for more

                           than 3 sec.     

Press the SET/ENT key to accept the low limit for PV 

display color change "20.0." 

Press the SET/ENT key for more than 3 sec.

This causes the Operation Parameter Screen to appear.

Setting the high and low limits for PV display color change

Setup Parameter Screen 1 

To the Operation Parameter Screen

12.  OTHER PARAMETERS 

12.1 Setting Ranges and Factory-Set Values 

Setup Parameter Screen 1

Parameter 

Symbol

Parameter Name

Setting Range

Factory-Set 

Value

Key lock  

(LOC)

0: Without lock. All parameters can be set. 

1:  Parameters other than the operation parameters 

cannot be changed.

2: All parameters cannot be changed.

-1: This moves to the Setup Parameter Screen 2.

0

Setup Parameter Screen 2

Parameter 

Symbol

Parameter Name

Setting Range

Factory-Set 

Value

Measured input bias (BS) -1999 to 9999

0

Economical mode time 

(ECO)

0 (Continuous: no display OFF function), 1 to 60 

(minutes)

10

12.2 Setting Key Lock 

This section describes an example of locking keys so that parameter settings other than the 

operation parameters cannot be changed. The procedure below begins with the condition in which 

the Setup Parameter Screen 1 is displayed. 

Press the SET/ENT key to display parameter "LOC." 

Press the UP key to display "1" on the DATA display. 

Press the SET/ENT key to accept this data.

The decimal point blinks during 

data change.

Setup Parameter Screen 1

Press               to display 

  

"LOC." 

Press             to display 

  

"1." 

Press

12.3 Setting Economical Mode Time

Setting economical mode time allows indications on the PV display to be extinguished if no keystroke 

is made within the set time. 

The MVRK’s power consumption in the OFF mode is approximately 0.5 W or 1 VA during normal 

operations (non-alarm status). This section describes an example of setting the economical mode 

time to “5 minutes” (factory-set value: 10 minutes).

The procedure below begins with the condition in which the Setup Parameter Screen 2 is displayed. 

Press the SET/ENT key to display parameter "ECO." 

Press the DOWN key to display "5" on the DATA display. 

Press the SET/ENT key to accept this data.

The decimal point blinks during 

data change.

Setup Parameter Screen 2

Press              to display 

 "ECO." 

Press              to display

                           "5."

 

Press              . 

 CAUTION

The economical mode is temporarily released at the time of PV display color change 

and the PV display lights up. After the set economical mode time elapsed from the time 

of returning to normal operation, the economical mode operation begins again .

12.4 Setting Input Bias 

This section describes an example of correcting an error by setting input bias if there is an error of “-1 

(°C)” in the MVRK displayed value with respect to the measured value. The procedure below begins 

with the condition in which the Setup Parameter Screen 2 is displayed.

Press the SET/ENT key to display parameter "BS." 

Press the UP key to display "1.0" on the DATA display. 

Press the SET/ENT key to accept this data. 

The decimal point blinks during 

data change. 

Setup Parameter Screen 2 

Press               to display 

 "BS." 

Press              to display 

 "1.0."

Press              . 

Summary of Contents for JUXTA MVRK

Page 1: ...lly to the socket face Otherwise the terminals may bend and it may cause bad contact The converter shall not tilt 5 degrees or more in either direction when installed When the converter is not connect...

Page 2: ...5 PART NAMES OF FRONT PANEL AND THEIR FUNCTIONS CAUTION The front panel of the product is constructed to prevent opening Forcing it open will result in breakage 1 PV measured value display Place for a...

Page 3: ...rm 3 hysteresis HY3 Displayed only for 4 points of alarms Sets the hysteresis of alarm 3 Alarm 4 hysteresis HY4 Displayed only for 4 points of alarms Sets the hysteresis of alarm 4 Alarm ON delay OND...

Page 4: ...ion describes how to correct wiring resistance when an error occurs due to the influence of the input wiring resistance Correct wiring resistance after completing the wiring 5 4 6 A B B Short circuit...

Page 5: ...f Adjustment Related Parameters Setup Parameter Screen 2 Parameter Symbol Parameter Name Setting Range Factory Set Value Input adjustment reset RST OFF 0 or ON 1 This parameter is used set to ON to re...

Page 6: ...ay color mode 6 Press the SET ENT key for more than 3 sec This causes the Operation Parameter Screen to appear Setting the PV display color mode Setup Parameter Screen 2 Continue to the upper right Pr...

Page 7: ...Press to display RTL Press to display 50 0 Press Press to display RTH Press to display 150 0 Press Press 13 1 4 Adjusting Monitor Output 1 Instruments for adjustment Digital multimeter DMM YOKOGAWA DM...

Page 8: ...lay 1 Press Press to display PSL Press or to display the communication protocol number to use Press Press Press the DOWN key to display 1 on the DATA display Press the SET ENT key to display the Setup...

Reviews: