YOKOGAWA JUXTA MVRK User Manual Download Page 5

IM 77J04R31-01E 2nd Edition  Oct. 15, 2019-00

5

Low-limit 

alarm 

setpoint

Power ON

PV

Time

Normal

Regarded 

as normal

Abnormal

(Alarm ON)

If an alarm type code with 
stand-by action is set, alarm 
action is turned off during the 
start-up control. 
This function is useful at power 
ON or when changing the alarm  
type.

Stand-by Action

9.2  Setting Alarm Output-Related Parameters 

This section describes an example of setting the alarm-1 action (AL1) to “12” (PV low-limit alarm, with 

stand-by action), alarm-1 setpoint (A1) to “0” (°C), alarm-1 hysteresis 1 (HY1) to “5” (°C), alarm ON 

delay (OND) to “5” (sec.) and alarm OFF delay (OFD) to “5” (sec.) with the range code No. (IN) set 

to “62” (instrument input range: -199.9 to 200.0°C). (Parameters relating to alarm 2 to alarm 4 can be 

set in the same way as the procedure below.) 

Press            or          
to display "12."

To the Setup Parameter 

Screen 1

When the SET/ENT key is pressed for more than 3 sec. 

with the Operation Parameter Screen displayed, the Setup 

Parameter Screen 1 appears with parameter "AL1" 

displayed.

When the power is turned on, the PV screen of the 

Operation Parameter Screen appears. 

Press the UP or DOWN key to display "5.0" (°C) on the 

DATA display. 

Press the SET/ENT key to accept alarm-1 hysteresis "5.0" 

(°C). 

Press the SET/ENT key to display parameter "OND." 

Press            for more 

 

        than 3 sec. 

Press            . 

This completes the process for 

setting the alarm-1 hysteresis. 

This completes the process for 

setting the alarm-1 action. 

This completes the process for 

setting the alarm-1 setpoint.  

The decimal point blinks during 

data change.

Press the UP or DOWN key to display "5" (sec.) on the 

DATA display. 

Press the SET/ENT key to accept alarm ON delay "5" 

(sec). 

Press the SET/ENT key again to display parameter 

"OFD." 

The decimal point blinks during 

data change. 

The decimal point blinks during 

data change.

The decimal point blinks during 

data change. 

Press the UP or DOWN key to display "5" (sec.) on the 

DATA display. 

Press the SET/ENT key to accept alarm OFF delay "5" 

(sec). 

Press the SET/ENT key for more than 3 sec.

This causes the Operation Parameter Screen to appear. 

This completes the process for 

setting the alarm OFF delay. 

The decimal point blinks during 

data change. 

Press the UP or DOWN key to display "12" on the DATA 

display. 

Press the SET/ENT key to accept alarm-1 action "12." 

Then to set the alarm setpoint, press the SET/ENT key for 

more than 3 sec. to display the Operation Parameter 

Screen.   (To set the hysteresis parameter and successive 

settings, press the SET/ENT key to display the next 

parameter.) 

Setup Parameter Screen 1

Setup Parameter Screen 1

Operation Parameter Screen

Press the SET/ENT key to display parameter "A1." 

Press the UP or DOWN key to display a low-limit alarm 

value "0.0" (°C) that is set to the DATA display. 

Press the SET/ENT key to accept low-limit alarm "0.0" 

(°C). 

Operation Parameter Screen 

To the Operation Parameter Screen

Power ON

Step 2

Setting the alarm action

Setting the alarm setpoint

Setting the hysteresis

Setting the alarm ON delay

Setting the alarm OFF delay

Press this key for 

more than 3 sec.

Press            to display "A1." 

Press            or            
to display "0.0." 

Press            . 

Press             to display
"OND." 

Press            . 

Press            or  
to display "5.0." 

Press            or            
to display "5." 

Press            .

Press            .

Press            or            
to display "5."

Press            .

Press            for more 

 

          than 3 sec.

This completes the process for 

setting the alarm ON delay.

10.  INPUT ADJUSTMENTS 

10.1  Setting Ranges and Factory-Set Values of Adjustment-Related Parameters

Setup Parameter Screen 2

Parameter 

Symbol

Parameter Name

Setting Range

Factory-Set Value

Input adjustment 

reset (RST)

OFF (0) or ON (1)

(This parameter is used (set to ON) to reset adjusted 

values.)

OFF

Input adjustment 

point LOW (BL)

±10% of the instrument input range span (and BL < BH)

Minimum value of the 

instrument input range

Input adjustment 

LOW (AL)

±10% of the instrument input range span (and AL < AH)

Minimum value of the 

instrument input range

Input adjustment 

point HIGH (BH)

±10% of the instrument input range span (and BL < BH)

Maximum value of the 

instrument input range

Input adjustment 

HIGH (AH)

±10% of the instrument input range span (and AL < AH)

Maximum value of the 

instrument input range

10.2 Instrument for Adjustments 

 •

6-dial decade resistance box (YOKOGAWA 279301 or equivalent): 1

10.3 Input Adjustment 

10.3.1  Connecting the Adjustment Instrument 

Connect the input and supply voltage as shown in the figure below.

 

10 11

1 2

3

9

8 7

6 5

4

7
8

N–

L+

(SUPPLY)

4

6

5

B
B

A

Input signal 

Power supply

6-dial decade 

resistance box

 

10.3.2  Adjusting Inputs 

Carry out input adjustments between two points, or the minimum value (BL: input adjustment 

point LOW) and maximum value (BH: input adjustment point HIGH) that have been set within the 

adjustment range (see Section 10.1). 

This subsection describes an example of making an input adjustment between two points within the 

range of -50.0 to 150.0°C with the MVRK range code No. set to “62” (instrument input range: -199.9 

to 200.0°C).

Press              to display 

 

            "LOC."

Press             to display 

"-1." 

The MVRK enters the operable status as soon as the power is turned on, but requires 10 to 15 minutes 

of warm-up to meet the performance requirements. 

When you press the SET/ENT key for more than 3 sec. 

with the Operation Parameter Screen displayed, the Setup 

Parameter Screen 1 appears. 

When the power is turned on, the PV screen of the 

Operation Parameter Screen appears. 

Press the SET/ENT key to display parameter "BL."

In this case, the DATA display shows "-199.9," the 

minimum value of instrument input range of the set range 

code No. 

Press the UP key to display "-50.0" on the DATA display. 

Press the SET/ENT key to accept this data. 
Press the SET/ENT key to display the next parameter. 

This causes parameter "AL" and the measured value to 

appear alternately. 

Press the UP or DOWN key. 

The decimal point blinks. 

 

Press the SET/ENT key. 

The value before adjustment (-52.2) appears on the DATA 

display. 

Press the SET/ENT key to display the next parameter "BH." 

Press this key for 

more than 3 sec.

The decimal point blinks.

The decimal point blinks during 

data change.

The decimal point blinks during 

data change.

Press the SET/ENT key to display parameter "LOC." 

Press the DOWN key to display "-1" on the DATA display. 

Press the SET/ENT key to display the Setup Parameter 

Screen 2.

Setup Parameter Screen 1 

Setup Parameter Screen 2

Operation Parameter Screen

Power ON

Using the 6-dial variable resistor, apply resistance equivalent 
to the input -50°C to the MVRK.

In this case, the DATA display shows "200.0," the 

maximum value of instrument input range of the set range 

code No.

Press the DOWN key to display "150.0" on the DATA 

display. 

Press the SET/ENT key to accept this data. 
Press the SET/ENT key to display the next parameter. 

The decimal point blinks during 

data change. 

Press            .

Press              to 

 

       display "BL." 

Press             to display 

  "-50.0."

Press             . 

 

Press             .

The measured value and 

parameter AL are 

displayed alternately. 

Press            or             . 

Press             . 

Press             . 

"-52.2" appears on the

DATA  display. 

Press             to display 

 

             "150.0."

Press             . 
Press             .

Continue to the next page

Summary of Contents for JUXTA MVRK

Page 1: ...lly to the socket face Otherwise the terminals may bend and it may cause bad contact The converter shall not tilt 5 degrees or more in either direction when installed When the converter is not connect...

Page 2: ...5 PART NAMES OF FRONT PANEL AND THEIR FUNCTIONS CAUTION The front panel of the product is constructed to prevent opening Forcing it open will result in breakage 1 PV measured value display Place for a...

Page 3: ...rm 3 hysteresis HY3 Displayed only for 4 points of alarms Sets the hysteresis of alarm 3 Alarm 4 hysteresis HY4 Displayed only for 4 points of alarms Sets the hysteresis of alarm 4 Alarm ON delay OND...

Page 4: ...ion describes how to correct wiring resistance when an error occurs due to the influence of the input wiring resistance Correct wiring resistance after completing the wiring 5 4 6 A B B Short circuit...

Page 5: ...f Adjustment Related Parameters Setup Parameter Screen 2 Parameter Symbol Parameter Name Setting Range Factory Set Value Input adjustment reset RST OFF 0 or ON 1 This parameter is used set to ON to re...

Page 6: ...ay color mode 6 Press the SET ENT key for more than 3 sec This causes the Operation Parameter Screen to appear Setting the PV display color mode Setup Parameter Screen 2 Continue to the upper right Pr...

Page 7: ...Press to display RTL Press to display 50 0 Press Press to display RTH Press to display 150 0 Press Press 13 1 4 Adjusting Monitor Output 1 Instruments for adjustment Digital multimeter DMM YOKOGAWA DM...

Page 8: ...lay 1 Press Press to display PSL Press or to display the communication protocol number to use Press Press Press the DOWN key to display 1 on the DATA display Press the SET ENT key to display the Setup...

Reviews: