YOKOGAWA FX1000 Installation Manual Download Page 2

IM 04L21B01-03EN  page 2/4

•  Use two mounting brackets to support the top and bottom or the left and right sides of the 

case (remove the stickers that are covering the holes before you attach the brackets).

•  Follow the procedure below to mount the FX to the panel.

•  First, attach the two mounting brackets and temporarily tighten the mounting screws.

•  Next, fix the FX in place by tightening the mounting screws with the appropriate torque. 

When the FX is approximately perpendicular to the panel, press the mounting brackets 

so that they are in contact with the case, and fully tighten the mounting screws.

•  Tighten the mounting bracket screws until you hear clicks.

CAUTION

l

  Using more than the appropriate torque to tighten the screws 

can deform the case or damage the brackets.

l

  Be sure not to insert foreign objects or tools into the case 

through the mounting bracket holes.

l

  Do not touch the screw at the top of the mounting bracket 

(A). Loosening or tightening this screw may cause the FX to 

malfunction.

 

Front

Panel

Panel

Mounting bracket

Mounting bracket

Torque driver

(Phillips or flat blade)

Mounting screw

FX case

Attach firmly

(In the figure, the mounting brackets are used on the top and bottom of the case.)

Mounting screw

Screws temporarily fastened

Fixed

Rubber packing for dust 

and water protection

(except side-by-side 

mounting)

A

Note

To achieve sufficient dust proofing and waterproofing, mount the FX in the middle of 

the panel cut out. However, do not use the rubber packing if you are mounting two 

instruments side by side or one on top of the other.

n

 

External Dimensions and Panel Cutout Dimensions

136.5

+0.4 0

Unit: mm (approx. inch)

If not specified, the tolerance is ±3%.

However, in cases of less than 10mm, the tolerance is ±0.3 mm.

Panel thickness

(Dimensions after attaching 

the mounting bracket)

If not installing the rubber packing for dust and water protection,

*1: 20.2 (0.80), *2: 163.7 (6.44), *3: 110.0 (4.33).

(*1)

(*2)

(*3)

(Dimensions after attaching 

the mounting bracket)

136.5  (5.37)

144.0 (5.67)

161.7 (6.37)

72.0   (2.83)

72.0 (2.83)

12.6  (0.50)

12.6 (0.50)

±0.3(0.01)

(2.74)

74.5 (2.93)

161.7 (6.37)

22.2 (0.87) 161.7 (6.37)

108.0 (4.25)

144.0 (5.67)

2 to 26 

(

0.08 to 1.02

)

Mounting bracket

69.5

Panel cut dimensions

MIN 175 

     (6.89)

L

+ 2 (0.08)

0

137 (5.39)

+ 2 (0.08)

0

Side-by side mounting 

(vertically; max. 3 units)

137 

(5.39)

MIN 175 

     (6.89)

0

L

+ 2 (0.08)

0

Side-by-side mounting 

(horizontally)

137 (5.39)

+ 2 (0.08)

0

137 

(5.39)

+ 2 (0.08)

0

Single-unit mounting

L

+ 2 (0.08)

0

2

3

4

5

6

7

8

9

10

n

282 (11.10)

426 (16.77)

in mm (approx. inches)

570 (22.44)

714 (28.11)

858 (33.78)

1434 (56.46)

1290 (50.79)

1146 (45.12)

1002 (39.45)

(144 × n) – 6 [(5.67 × n) – 0.24]

Units

+ 2 (0.08)

External dimensions

3.  Wiring

n

 

Input Signal Wiring

WARNING 

To prevent electric shock while wiring, make sure that the power 

supply is turned off.

CAUTION

l

  Applying a strong tension to the input and output signal cables 

connected to the FX may damage the cables or the FX terminals. 

To avoid applying tension directly to the terminals, fix all cables 

to the rear of the mounting panel.

l

 

To prevent fire, use signal cables with a temperature rating of 80°C 

or more.

l

 Do not apply voltages that exceed the following values to the 

input terminals. Doing so may damage the FX.

•  Maximum input voltage: ±60 VDC

•  Maximum common mode voltage: ±60 VDC (under 

measurement category II conditions)

l

  The FX is an installation category II product.

Precautions to Be Taken While Wiring

Take the following precautions when wiring the input signal cables.

When using a screw terminal, we recommend that you use a crimp-on lug with an 

insulation sleeve (designed for 3 mm screws).

Take measures to prevent noise from entering the measurement circuit.

•  Move the measurement circuit away from the power cable (power circuit) and ground circuit.

•  Ideally, the object being measured should not generate noise. However, if this is 

unavoidable, isolate the measurement circuit from the object. Also, ground the ob-

ject being measured.

•  Shielded wires should be used to minimize the noise caused by electrostatic induc-

tion. Connect the shield to the ground terminal of the FX as necessary (make sure 

you are not grounding at two points).

•  To minimize noise caused by electromagnetic induction, twist the measurement 

circuit wires at short, equal intervals.

•  Make sure to earth ground the protective ground terminal through minimum resis-

tance (less than 100 Ω).

When using internal reference junction compensation on the thermocouple input, 

take measures to stabilize the temperature at the input terminal.

•  Always use the terminal cover.

•  Do not use thick wires which may cause large heat dissipation (we recommend a 

cross sectional area of 0.5 mm

2

 or less).

•  Make sure that the ambient temperature remains reasonably stable. Large tem-

perature fluctuations can occur if a nearby fan turns on or off.

Connecting the input wires in parallel with other devices can cause signal degradation, 

affecting all connected devices. If you need to make a parallel connection, then

•  Turn the burnout detection function off.

•  Ground the instruments to the same point.

•  Do not turn other instruments on or off during operation. This can have adverse ef-

fects on the other instruments.

•  RTDs cannot be wired in parallel.

Input terminal block 

of the FX1002

Input terminal block 

of the FX1004

Input terminal block 

of the FX1006

Input terminal block 

of the FX1008

Input terminal block 

of the FX1010

Input terminal block 

of the FX1012

For TC input, use shielded compensating lead wires for wiring.

For RTD input, lead wire resistance per wire of 10 Ω or less. Make the resistances of 

the three wires equal.

For DCA input, example: for 4 to 20 mA input, use a shunt resistor of 250 Ω ± 0.1%.

+/A

/b

CH1

–/B

CH2

+/A

/b

CH1

–/B

CH2

CH3

CH4

+/A

/b

CH1

–/B

CH2

CH3

CH4

CH5

CH6

+/A

/b

CH1

CH7

–/B

CH2

CH8

CH3

CH4

CH5

CH6

+/A

/b

CH1

CH7

–/B

CH2

CH8

CH9

CH10

CH3

CH4

CH5

CH6

+/A

/b

CH1

CH7

–/B

CH2

CH8

CH9

CH10

CH11

CH12

CH3

CH4

CH5

CH6

Note

RTD input terminals A and B are isolated on each channel. Terminal b is shorted 

internally across all channels. However, terminal b is also isolated on each channel 

on models with the /N2 option (3 leg isolated RTD).

Optional Terminal Wiring

WARNING 

l

  To prevent electric shock while wiring, make sure that the power 

supply is turned off.

l

  If a voltage of more than 30 VAC or 60 VDC is to be applied to the 

output terminals, use ring-tongue crimp-on lugs with insulation 

sleeves  on  all  terminals  to  prevent  the  signal  cables  from 

slipping out when the screws become loose. Furthermore, use 

double-insulated cables (dielectric strength of 3000 VAC or more) 

for the signal cables on which a voltage of 30 VAC or 60 VDC 

or more is to be applied. For all other signal cables, use basic 

insulated cables (dielectric strength of 1500 VAC). To prevent 

electric shock, attach the terminal cover after wiring and make 

sure not to touch the terminals.

CAUTION

l

  Use the following circuit voltages for the connection to the 

alarm/FAIL/status output terminal.

•  When the connection is to Mains Circuits (primary power 

supply circuits): 150 V or less

•  When the connection is to circuits derived from Mains 

Circuits (secondary power supply circuits): 250 V or less

  (Keep the Mains Circuit voltage at 300 V or less, and use 

an isolation transformer.)

l

 

To prevent fire, use signal cables with a temperature rating of 70°C or more.

l

  Applying a strong tension to the input and output signal cables 

connected to the FX may damage the cables or the FX terminals. 

To avoid applying tension directly to the terminals, fix all cables 

to the rear of the mounting panel.

l

  Do not short the transmitter power supply output terminal or apply 

external voltage to it. Doing so may damage the instrument.

l

  When using the transmitter power supply output terminal, do not 

use current that is equal to or greater than the maximum output 

current (25 mADC). Doing so may damage the instrument.

Precautions to Be Taken While Wiring

We recommend that you use crimp-on lugs (designed for 3 mm screws) with 

insulation sleeves to connect to the optional terminals.

The following figures show the terminal positions for each option when only that 

option is installed. Even if you have installed a number of options, the individual 

terminal positions of the options do not change (except for the case where you have 

installed both the /TPS2 and /A1 options; in this case, the /A1 terminal positions are 

different).

Alarm output

Alarm output

Alarm output

Alarm output

Alarm output

Alarm output

Alarm output

Memory 

end

Remote control input

Remote control input

Pulse input

Voltage input

Current 

input

Current 

input

Transmitter power supply output

Transmitter power supply output

NC

C

NO

/A1

/A2

01

NC

C

NO

02

NC

C

NO

01

NC

C

NO

NC

C

NO

01

02

NC

C

NO

NC

C

NO

NC

C

NO

02

NC

C

NO

03

NC

C

NO

04

NC

C

NO

/A3

/A4A

01

NC

C

NO

NC

C

NO

NC

C

NO

02

05

06

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

RS-422A/485

NC

C

NO

03

NC

C

NO

04

01

02

03

04

05

06

07

08

09

10

11

12

FAIL

/C3

/F1

FG SG SDB SDARDBRDA

/PM1

/R1

L H L H L H

4

2

3

1 C

5

8

7

6

4

2

3

1 C

5

/PWR1, /PWR5

3S

1L 1S

P1

P2

P3

3L

/TPS2

/TPS4

+

-

+

-

+

-

+

-

+

-

+

-

/A1 when installed in the FX with a /TPS2

  Alarm Output Terminal (/A1, /A2, and /A3), FAIL Output Terminal and Memory 

End Output Terminal (/F1)

During normal 

operation

When a failure 

occurs

When power 

is turned off

NO C NC

During normal 

operation

NO C NC

When the 

specified 

status occurs

NO C NC

NO C NC

NO C NC

NO C NC

When power 

is turned off

FAIL output

(/F1)

Other output 

(/F1)

Output format: 

Relay contact

Contact rating: 

250 VAC (50/60 Hz)/3 A, 

250 VDC/0.1 A (load resistance)

Withstand voltage: 

1600 VAC (50/60 Hz) for one 

 

minute (between output 

 

terminals and the ground 

terminal)

• 

Alarm Output Terminal (/A4A)

Output format: 

Relay contact

Contact rating: 

250 VAC (50/60 Hz)/3 A, 

 

250 VDC/0.1 A (load resistance)

Withstand voltage: 

1600 VAC (50/60 Hz) for one 

 

minute (between output terminals 

 

and the ground terminal)

During normal 

operation

When the specified 

status occurs

NO C

Alarm output

NO C

• 

Remote Control Input Terminal (/R1)

C

1 to 8

• Transistor input (open collector)

Internal circuit

• Relay contact input (voltage-free contact)

Withstand voltage: 

1000 VDC for one minute 

between input terminals 

and the ground terminal

Input format:

  Photocoupler isolation 

  Shared common (C)

Allowable input voltage: 

5 VDC

5 V

Contact open at 200 Ω or less

Contact closed at 100 kΩ or greater

On voltage: 0.5 V or less (30 mADC)

Leakage current when turned off: 0.25 mA or less

•  Pulse Input Terminal (/PM1)

H

L

Withstand voltage: 

1000 VDC for one minute 

between input terminals 

and the ground terminal

Input format:

  Photocoupler isolation 

  Shared common (L)

Allowable input voltage: 

30 VDC

5 V

Internal circuit

• Transistor input (open collector)

• Relay contact input (voltage-free contact)

Contact open at 200 Ω or less

Contact closed at 100 kΩ or greater

On voltage: 0.5 V or less (30 mADC)

Leakage current when turned off: 0.25 mA or less

•  24 VDC Transmitter Power Supply Output Terminal (/TPS2, /TPS4)

Connect the FX to the transmitter as shown below.

Transmitter

Current

FX

Transmitter 

power supply 

output terminal

Input terminal

Shunt resistor: 250 Ω

+

+

Note

To reduce noise, use a shielded 

cable for wiring. Connect the 

shield to the ground terminal of 

the FX.

•  Serial Communication Interface (/C2)

9-pin D-sub RS-232 connector

•  Serial Communication Interface (/C3)

FG (Frame Ground) 

 

Case ground of the FX

SG (Signal Ground) 

  Signal ground

SDB (Send Data B) 

 

Send data B (+)

SDA (Send Data A) 

 

Send data A (–)

RDB (Received Data B)   

Receive data B (+)

RDA (Received Data A)   

Receive data A (–)

Two-wire system

FG      SG      SDB    SDA   RDB   RDA

Electric potential of the shield

Four-wire system

Shield

FG      SG      SDB    SDA   RDB   RDA

Cable

 There are two types of cables available: the four-wire cable and the two-wire cable, which is used only 

for the Modbus protocol.

The cable must meet the following specifications.

•  Type: 

Shielded twisted pair cable. 3 pairs, 24 AWG or more (four wire); 2 pairs, 

24 AWG or more (two wires).

•  Characteristic impedance:  100Ω

•  Capacitance: 

50 pF/m

•  Total cable length: 

Up to 1.2 km

Recommended length of stripped wire: 9 mm. 

Recommended tightening torque: 0.4 to 0.5 N•m

•  Connecting to the USB Port (/USB1)

The USB port complies with USB revision 1.1. The USB port is installed on the FX’s front panel.

•  Connecting to the Ethernet Port (/C7)

CAUTION

Do not connect an Ethernet cable whose plug does not comply with 

FCC specifications. If you do, the FX may malfunction.

Ethernet port

Indicators

Summary of Contents for FX1000

Page 1: ...ment Category II CAT II Measurement category II CAT II applies to measuring circuits connected to low voltage installation and electrical instruments supplied with power from fixed equipment such as electric switchboards This instrument is an EN61326 1 EMC standard class A instrument for use in commercial industrial or business environments The influence rate judgment condition A in the immunity t...

Page 2: ...isolated RTD n Optional Terminal Wiring WARNING l To prevent electric shock while wiring make sure that the power supply is turned off l If a voltage of more than 30 VAC or 60 VDC is to be applied to the output terminals use ring tongue crimp on lugs with insulation sleeves on all terminals to prevent the signal cables from slipping out when the screws become loose Furthermore use double insulated...

Page 3: ...um battery Notice The symbol see above means they shall be sorted out and collected as ordained in ANNEX II in DIRECTIVE 2006 66 EC Installing the DAQSTANDARD To install the DAQSTANDARD an appropriate license number 117 00000 5819 needs to be entered 1 Start Windows Log onto Windows as an administrator 2 Double click the downloaded file to extract the files 3 Double click Install exe 4 The install...

Page 4: ...the measurement method Most settings can be changed when memory sampling is in progress Basic setting mode A mode for configuring basic settings such as the scan interval and the measured data save method You cannot switch to this mode when memory sampling is in progress Basic setting mode Operating environment Environment View Message Input Alarm Security Media save Batch Communication Service po...

Reviews: