
IM 04L21B01-03EN page 2/4
• Use two mounting brackets to support the top and bottom or the left and right sides of the
case (remove the stickers that are covering the holes before you attach the brackets).
• Follow the procedure below to mount the FX to the panel.
• First, attach the two mounting brackets and temporarily tighten the mounting screws.
• Next, fix the FX in place by tightening the mounting screws with the appropriate torque.
When the FX is approximately perpendicular to the panel, press the mounting brackets
so that they are in contact with the case, and fully tighten the mounting screws.
• Tighten the mounting bracket screws until you hear clicks.
CAUTION
l
Using more than the appropriate torque to tighten the screws
can deform the case or damage the brackets.
l
Be sure not to insert foreign objects or tools into the case
through the mounting bracket holes.
l
Do not touch the screw at the top of the mounting bracket
(A). Loosening or tightening this screw may cause the FX to
malfunction.
Front
Panel
Panel
Mounting bracket
Mounting bracket
Torque driver
(Phillips or flat blade)
Mounting screw
FX case
Attach firmly
(In the figure, the mounting brackets are used on the top and bottom of the case.)
Mounting screw
Screws temporarily fastened
Fixed
Rubber packing for dust
and water protection
(except side-by-side
mounting)
A
Note
To achieve sufficient dust proofing and waterproofing, mount the FX in the middle of
the panel cut out. However, do not use the rubber packing if you are mounting two
instruments side by side or one on top of the other.
n
External Dimensions and Panel Cutout Dimensions
136.5
+0.4 0
Unit: mm (approx. inch)
If not specified, the tolerance is ±3%.
However, in cases of less than 10mm, the tolerance is ±0.3 mm.
Panel thickness
(Dimensions after attaching
the mounting bracket)
If not installing the rubber packing for dust and water protection,
*1: 20.2 (0.80), *2: 163.7 (6.44), *3: 110.0 (4.33).
(*1)
(*2)
(*3)
(Dimensions after attaching
the mounting bracket)
136.5 (5.37)
144.0 (5.67)
161.7 (6.37)
72.0 (2.83)
72.0 (2.83)
12.6 (0.50)
12.6 (0.50)
±0.3(0.01)
(2.74)
74.5 (2.93)
161.7 (6.37)
22.2 (0.87) 161.7 (6.37)
108.0 (4.25)
144.0 (5.67)
2 to 26
(
0.08 to 1.02
)
Mounting bracket
69.5
Panel cut dimensions
MIN 175
(6.89)
L
+ 2 (0.08)
0
137 (5.39)
+ 2 (0.08)
0
Side-by side mounting
(vertically; max. 3 units)
137
(5.39)
MIN 175
(6.89)
0
L
+ 2 (0.08)
0
Side-by-side mounting
(horizontally)
137 (5.39)
+ 2 (0.08)
0
137
(5.39)
+ 2 (0.08)
0
Single-unit mounting
L
+ 2 (0.08)
0
2
3
4
5
6
7
8
9
10
n
282 (11.10)
426 (16.77)
in mm (approx. inches)
570 (22.44)
714 (28.11)
858 (33.78)
1434 (56.46)
1290 (50.79)
1146 (45.12)
1002 (39.45)
(144 × n) – 6 [(5.67 × n) – 0.24]
Units
+ 2 (0.08)
External dimensions
3. Wiring
n
Input Signal Wiring
WARNING
To prevent electric shock while wiring, make sure that the power
supply is turned off.
CAUTION
l
Applying a strong tension to the input and output signal cables
connected to the FX may damage the cables or the FX terminals.
To avoid applying tension directly to the terminals, fix all cables
to the rear of the mounting panel.
l
To prevent fire, use signal cables with a temperature rating of 80°C
or more.
l
Do not apply voltages that exceed the following values to the
input terminals. Doing so may damage the FX.
• Maximum input voltage: ±60 VDC
• Maximum common mode voltage: ±60 VDC (under
measurement category II conditions)
l
The FX is an installation category II product.
Precautions to Be Taken While Wiring
Take the following precautions when wiring the input signal cables.
When using a screw terminal, we recommend that you use a crimp-on lug with an
insulation sleeve (designed for 3 mm screws).
Take measures to prevent noise from entering the measurement circuit.
• Move the measurement circuit away from the power cable (power circuit) and ground circuit.
• Ideally, the object being measured should not generate noise. However, if this is
unavoidable, isolate the measurement circuit from the object. Also, ground the ob-
ject being measured.
• Shielded wires should be used to minimize the noise caused by electrostatic induc-
tion. Connect the shield to the ground terminal of the FX as necessary (make sure
you are not grounding at two points).
• To minimize noise caused by electromagnetic induction, twist the measurement
circuit wires at short, equal intervals.
• Make sure to earth ground the protective ground terminal through minimum resis-
tance (less than 100 Ω).
When using internal reference junction compensation on the thermocouple input,
take measures to stabilize the temperature at the input terminal.
• Always use the terminal cover.
• Do not use thick wires which may cause large heat dissipation (we recommend a
cross sectional area of 0.5 mm
2
or less).
• Make sure that the ambient temperature remains reasonably stable. Large tem-
perature fluctuations can occur if a nearby fan turns on or off.
Connecting the input wires in parallel with other devices can cause signal degradation,
affecting all connected devices. If you need to make a parallel connection, then
• Turn the burnout detection function off.
• Ground the instruments to the same point.
• Do not turn other instruments on or off during operation. This can have adverse ef-
fects on the other instruments.
• RTDs cannot be wired in parallel.
Input terminal block
of the FX1002
Input terminal block
of the FX1004
Input terminal block
of the FX1006
Input terminal block
of the FX1008
Input terminal block
of the FX1010
Input terminal block
of the FX1012
For TC input, use shielded compensating lead wires for wiring.
For RTD input, lead wire resistance per wire of 10 Ω or less. Make the resistances of
the three wires equal.
For DCA input, example: for 4 to 20 mA input, use a shunt resistor of 250 Ω ± 0.1%.
+/A
/b
CH1
–/B
CH2
+/A
/b
CH1
–/B
CH2
CH3
CH4
+/A
/b
CH1
–/B
CH2
CH3
CH4
CH5
CH6
+/A
/b
CH1
CH7
–/B
CH2
CH8
CH3
CH4
CH5
CH6
+/A
/b
CH1
CH7
–/B
CH2
CH8
CH9
CH10
CH3
CH4
CH5
CH6
+/A
/b
CH1
CH7
–/B
CH2
CH8
CH9
CH10
CH11
CH12
CH3
CH4
CH5
CH6
Note
RTD input terminals A and B are isolated on each channel. Terminal b is shorted
internally across all channels. However, terminal b is also isolated on each channel
on models with the /N2 option (3 leg isolated RTD).
n
Optional Terminal Wiring
WARNING
l
To prevent electric shock while wiring, make sure that the power
supply is turned off.
l
If a voltage of more than 30 VAC or 60 VDC is to be applied to the
output terminals, use ring-tongue crimp-on lugs with insulation
sleeves on all terminals to prevent the signal cables from
slipping out when the screws become loose. Furthermore, use
double-insulated cables (dielectric strength of 3000 VAC or more)
for the signal cables on which a voltage of 30 VAC or 60 VDC
or more is to be applied. For all other signal cables, use basic
insulated cables (dielectric strength of 1500 VAC). To prevent
electric shock, attach the terminal cover after wiring and make
sure not to touch the terminals.
CAUTION
l
Use the following circuit voltages for the connection to the
alarm/FAIL/status output terminal.
• When the connection is to Mains Circuits (primary power
supply circuits): 150 V or less
• When the connection is to circuits derived from Mains
Circuits (secondary power supply circuits): 250 V or less
(Keep the Mains Circuit voltage at 300 V or less, and use
an isolation transformer.)
l
To prevent fire, use signal cables with a temperature rating of 70°C or more.
l
Applying a strong tension to the input and output signal cables
connected to the FX may damage the cables or the FX terminals.
To avoid applying tension directly to the terminals, fix all cables
to the rear of the mounting panel.
l
Do not short the transmitter power supply output terminal or apply
external voltage to it. Doing so may damage the instrument.
l
When using the transmitter power supply output terminal, do not
use current that is equal to or greater than the maximum output
current (25 mADC). Doing so may damage the instrument.
Precautions to Be Taken While Wiring
We recommend that you use crimp-on lugs (designed for 3 mm screws) with
insulation sleeves to connect to the optional terminals.
The following figures show the terminal positions for each option when only that
option is installed. Even if you have installed a number of options, the individual
terminal positions of the options do not change (except for the case where you have
installed both the /TPS2 and /A1 options; in this case, the /A1 terminal positions are
different).
Alarm output
Alarm output
Alarm output
Alarm output
Alarm output
Alarm output
Alarm output
Memory
end
Remote control input
Remote control input
Pulse input
Voltage input
Current
input
Current
input
Transmitter power supply output
Transmitter power supply output
NC
C
NO
/A1
/A2
01
NC
C
NO
02
NC
C
NO
01
NC
C
NO
NC
C
NO
01
02
NC
C
NO
NC
C
NO
NC
C
NO
02
NC
C
NO
03
NC
C
NO
04
NC
C
NO
/A3
/A4A
01
NC
C
NO
NC
C
NO
NC
C
NO
02
05
06
C
NO
C
NO
C
NO
C
NO
C
NO
C
NO
C
NO
C
NO
C
NO
C
NO
C
NO
C
NO
RS-422A/485
NC
C
NO
03
NC
C
NO
04
01
02
03
04
05
06
07
08
09
10
11
12
FAIL
/C3
/F1
FG SG SDB SDARDBRDA
/PM1
/R1
L H L H L H
4
2
3
1 C
5
8
7
6
4
2
3
1 C
5
/PWR1, /PWR5
3S
1L 1S
P1
P2
P3
3L
/TPS2
/TPS4
+
-
+
-
+
-
+
-
+
-
+
-
/A1 when installed in the FX with a /TPS2
•
Alarm Output Terminal (/A1, /A2, and /A3), FAIL Output Terminal and Memory
End Output Terminal (/F1)
During normal
operation
When a failure
occurs
When power
is turned off
NO C NC
During normal
operation
NO C NC
When the
specified
status occurs
NO C NC
NO C NC
NO C NC
NO C NC
When power
is turned off
FAIL output
(/F1)
Other output
(/F1)
Output format:
Relay contact
Contact rating:
250 VAC (50/60 Hz)/3 A,
250 VDC/0.1 A (load resistance)
Withstand voltage:
1600 VAC (50/60 Hz) for one
minute (between output
terminals and the ground
terminal)
•
Alarm Output Terminal (/A4A)
Output format:
Relay contact
Contact rating:
250 VAC (50/60 Hz)/3 A,
250 VDC/0.1 A (load resistance)
Withstand voltage:
1600 VAC (50/60 Hz) for one
minute (between output terminals
and the ground terminal)
During normal
operation
When the specified
status occurs
NO C
Alarm output
NO C
•
Remote Control Input Terminal (/R1)
C
1 to 8
• Transistor input (open collector)
Internal circuit
• Relay contact input (voltage-free contact)
Withstand voltage:
1000 VDC for one minute
between input terminals
and the ground terminal
Input format:
Photocoupler isolation
Shared common (C)
Allowable input voltage:
5 VDC
5 V
Contact open at 200 Ω or less
Contact closed at 100 kΩ or greater
On voltage: 0.5 V or less (30 mADC)
Leakage current when turned off: 0.25 mA or less
• Pulse Input Terminal (/PM1)
H
L
Withstand voltage:
1000 VDC for one minute
between input terminals
and the ground terminal
Input format:
Photocoupler isolation
Shared common (L)
Allowable input voltage:
30 VDC
5 V
Internal circuit
• Transistor input (open collector)
• Relay contact input (voltage-free contact)
Contact open at 200 Ω or less
Contact closed at 100 kΩ or greater
On voltage: 0.5 V or less (30 mADC)
Leakage current when turned off: 0.25 mA or less
• 24 VDC Transmitter Power Supply Output Terminal (/TPS2, /TPS4)
Connect the FX to the transmitter as shown below.
Transmitter
Current
FX
Transmitter
power supply
output terminal
Input terminal
Shunt resistor: 250 Ω
+
+
–
–
Note
To reduce noise, use a shielded
cable for wiring. Connect the
shield to the ground terminal of
the FX.
• Serial Communication Interface (/C2)
9-pin D-sub RS-232 connector
• Serial Communication Interface (/C3)
FG (Frame Ground)
Case ground of the FX
SG (Signal Ground)
Signal ground
SDB (Send Data B)
Send data B (+)
SDA (Send Data A)
Send data A (–)
RDB (Received Data B)
Receive data B (+)
RDA (Received Data A)
Receive data A (–)
Two-wire system
FG SG SDB SDA RDB RDA
Electric potential of the shield
Four-wire system
Shield
FG SG SDB SDA RDB RDA
Cable
There are two types of cables available: the four-wire cable and the two-wire cable, which is used only
for the Modbus protocol.
The cable must meet the following specifications.
• Type:
Shielded twisted pair cable. 3 pairs, 24 AWG or more (four wire); 2 pairs,
24 AWG or more (two wires).
• Characteristic impedance: 100Ω
• Capacitance:
50 pF/m
• Total cable length:
Up to 1.2 km
Recommended length of stripped wire: 9 mm.
Recommended tightening torque: 0.4 to 0.5 N•m
• Connecting to the USB Port (/USB1)
The USB port complies with USB revision 1.1. The USB port is installed on the FX’s front panel.
• Connecting to the Ethernet Port (/C7)
CAUTION
Do not connect an Ethernet cable whose plug does not comply with
FCC specifications. If you do, the FX may malfunction.
Ethernet port
Indicators