A2-32
IM 34M06C11-01E
(3) F3XA16-1N AC Input Module
Item
Specifications
Item
Specifications
Input type
AC voltage
Operating
voltage
/current
ON
80V AC min., 5mA min.
Number of points
16
OFF
40V AC max., 1mA min.
Common line type
8 points/common line
Response
time
OFF
→
ON
15ms max. or 30ms,
selectable
Isolation method
Transformer insulation
ON
→
OFF
25ms max. or 40ms,
selectable
Withstanding voltage
1500V AC for one
minute between the
group of terminals for
external connection
and the internal circuit
Interrupt
Can be specified for each
input point
Dissipating current
65mA (5V DC)
Rated input voltage
100 to 120V AC
50
/
60Hz
Input display
LED (lit when input is
turned on)
Operating voltage
range
85 to 132V AC
50
/
60Hz
External connection
18-point terminal block
with M3.5 screws
Rated input current
5.4-6.5mA
/
point
(100-120V AC, 60Hz)
Weight
180g
Input impedance
21.9k
Ω
50Hz
18.5k
Ω
60Hz
Maximum ratio of inputs
turned on simultaneously
100%
.
Front View
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
2
5
7
COM1
3
4
6
8
COM2
10
11
13
15
9
12
14
16
XA16-1N
AC IN
F3XA16-1N
FA020516_1.VSD
Internal Circuit Configuration
Bus
Interface
Inter
n
al
B
us
1
8
9
~
COM
FA020512.VSD
External Connection Diagram
1
3
5
7
9
11
13
15
17
1
2
3
4
5
6
7
8
COM1
2
4
6
8
10
12
14
16
18
9
10
11
12
13
14
15
16
COM 2
FA020516_2.vsd
Note: Viewed from the front side of the module.
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...