A3-16
IM 34M06C11-01E
A3.3.6
Measures against Power Failure
The power supply block of the FA-M3 incorporates a built-in power sequence circuit
which prevents the system from malfunctioning when a momentary power failure or
voltage reduction occurs. This system has two modes of detecting power failures; one
is the standard mode and the other is the immediate detection mode. There are
restrictions on the use of the immediate detection mode, as summarized in the table
given below, according to the type of power supply module or CPU module used. The
default (factory setting) mode is the standard mode.
Mode
Available Power Supply
Module
Available CPU Module
Standard
All types
All types
Immediate detection*
F3PU10-0N
F3PU10-0S
F3PU16-0N
F3PU16-0
S
F3PU20-0N
F3PU20-0S
F3PU26-0N
F3PU26-0
S
F3PU30-0N
F3PU30-0S
F3PU36-0N
F3PU36-0S
F3SP2
□
-
□□
F3SP3
□
-
□□
F3SP5
□
-
□□
F3SP6
□
-
□□
F3SP7
□
-
□□
F3FP36-3N
F3BP20-0N
F3BP30-0N
*:
Select the immediate detection mode from the “CPU Configuration” menu. For more details, refer to "FA-M3
Programming Tool WideField" (IM 34M06Q14-01E), "FA-M3 Programming Tool WideField2" (IM 34M06Q15-01E)
or
"FA-M3 Programming Tool WideField3" (IM 34M06Q16-
□□
E). For details on the modes of detecting power failures
supported by the F3BP20, F3BP30 BASIC CPU module, refer to the BASIC CPU Modules and YM-BASIC/FA
Programming Language (IM 34M06Q22-01E).
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...