![YOKOGAWA FA-M3 Vitesse System Upgrade Manual Download Page 17](http://html2.mh-extra.com/html/yokogawa/fa-m3-vitesse/fa-m3-vitesse_system-upgrade-manual_3469546017.webp)
3
. System upgrade procedure
16
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation
TI 34M06Z42-01E
2018.06-00
Item
Discontinued
product
Replacement
product
Compatible
Changes
NX autonomous
distributed
F3NX01-0N
F3NX01-2N
✓
Software compatible but has no AUI port and has
different look (e.g. connector location.)
F3NX01-1N
F3NX01-2N
✓
Software compatible but has no AUI port and has
different look (e.g. connector location.)
FA link H
F3LP01-0N
F3LP02-0N
*2
(
F3LP
□□
-
□
N
*3
)
✓
(Software compatible but hardware incompatible.
New and old products cannot be mixed)
F3LP02-0N
*2
(
F3LP
□□
-
□
N
*3
)
✓
(Software compatible but hardware incompatible.
New and old products cannot be mixed)
Fiber-optic FA
link H
F3LP12-0N
*2
None
-
Replace with combination of FL-net and optical
cable converter.
μ
bus
F3LU01-0N
None
-
Need to replace with YHLS etc.
Modem
F3LM01-1N
F3LC11-1F
-
Replace with combination of F3LC11-1F and
external analog modem.
*1 F3DA04-6R/DCR with default current (4 to 20 mA) output type is available for customers using current output. Contact
Yokogawa's sales representative for details.
*2 Scheduled to be discontinued on 31 March 2019
*3 New product scheduled for sale in December 2018.
3.3.8
Application compatibility of special modules
■
As replacement models become more powerful, application
modification is needed for some special modules.
■
Even with application compatibility, processing timing may
change due to faster processing speed so you should always
verify system operation after module upgrade.