![YOKOGAWA FA-M3 Vitesse System Upgrade Manual Download Page 12](http://html2.mh-extra.com/html/yokogawa/fa-m3-vitesse/fa-m3-vitesse_system-upgrade-manual_3469546012.webp)
3
. System upgrade procedure
11
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation
TI 34M06Z42-01E
2018.06-00
3.3.2
Communication interfaces of sequence CPU
■
Changes
●
The replacement sequence CPU module has an Ethernet port.
●
F3SP7□-□S has no RS-232C port. If a touch panel etc. was
connected via RS-232C, it is necessary to switch to Ethernet or
go via a PC link module.
●
Dedicated ROM pack for program backup has been substituted by
a general-purpose SD card, which can also be used to store
device data.
Figure 3.2
Interface of sequence CPU
Table 3.2
Interfaces of F3SP2□/3□/5□
Item
Media
Purpose
Communication RS-232C
Programming and connection of display
Memory
Dedicated ROM pack
Program backup
Table 3.3
Interfaces of F3SP7□
Item
Media
Purpose
Communication
Ethernet
Connection of PC and display
USB
Programming
Memory
SD (SDHC)
Data storage and program backup