2.6
Modbus Device Allocation Specifications
This section describes the associations between the Modbus device and the
devices of this module.
Modbus Device List
Modbus devices are as defined below.
Devices are as described below.
Table 2.6.1 Modbus Device List
Modbus Device
Unit/Direction
Points
Number
Coil
1-bit/Read, Write
65,536
1 to 65536
Discrete input
1-bit/Read
65,536
1 to 65536
Input register
16-bit/Read
65,536
1 to 65536
Holding register
16-bit/Read, Write
65,536
1 to 65536
File record
16-bit/Read, Write
655,360,000
File: 0 to 65535
Record: 0 to 9999