![YOKOGAWA F3SP71-4S User Manual Download Page 19](http://html1.mh-extra.com/html/yokogawa/f3sp71-4s/f3sp71-4s_user-manual_3445797019.webp)
2-3
IM 34M06P15-03E 2nd Edition: Jan. 31, 2012-00
2.4 Function
Codes
This section describes the Modbus function codes.
Support Function Codes
The functions codes supported by this module are as shown below.
Table 2.4.1 Function Code List
Function
Code
Name Description
Supported
01 ($01)
Read Coils
Consecutively reads the status of a max. of
2,000 coils.
Yes
02 ($02)
Read Discrete Inputs
Consecutively reads the status of a max. of
2,000 inputs.
Yes
03 ($03)
Read Holding Registers
Consecutively reads the status of a max. of 125
holding registers.
Yes
04 ($04)
Read Input Registers
Consecutively reads the status of a max. of 125
input registers.
Yes
05 ($05)
Write Single Coil
Writes a single coil.
Yes
06 ($06)
Write Single Register
Writes a single register.
Yes
15 ($0F)
Write Multiple Coils
Consecutively writes the status of a max. of
1,968 coils.
Yes
16 ($10)
Write Multiple Registers
Consecutively writes the status of a max. of 123
registers.
Yes
20 ($14)
Read File Record
Reads a max. of 124 file records.
Yes
21 ($15)
Write File Record
Writes a max. of 122 file records.
Yes
22 ($16)
Mask Write Register
Mask a single register with AND or OR.
Yes
23 ($17)
Read/Write Multiple Registers
Reads and writes multiple registers.
Yes
24 ($18)
Read FIFO Queue
Reads FIFO tables.
Yes
Summary of Contents for F3SP71-4S
Page 2: ...Blank Page Blank Page...
Page 12: ...Blank Page...
Page 32: ...Blank Page...
Page 48: ...Blank Page...
Page 50: ...Blank Page...