<7.
Errors and Countermeasures
>
28
IM 01C22A01-01E
7.
Errors and Countermeasures
NOTE
For F
OUNDATION
Fieldbus and PROFIBUS PA communication types, please refer to manuals in the attached CD-ROM.
The table below shows a summary of error messages for BRAIN and HART protocols.
Table 7.1
Error Message Summary
Integral
Indicator
Display
Description
Cause
Output Operation during Error
Countermeasure
None
GOOD
---
ERROR
Er. 01
CAP MODULE FAULT
Capsule problem.*
1
Outputs the signal according to
status of a burnout direction pin
or switch (the signal can be set as
“hold” for BRAIN protocol).
Replace capsule.*
2
Er. 02
AMP MODULE FAULT
Amplifier problem.
Outputs the signal (Hold, Outputs
the signal according to status of
a burnout direction pin or switch
(the signal can be set as “hold” for
BRAIN protocol).
Replace amplifier.
Er. 03
OUT OF RANGE
Input is outside
measurement range limit
of capsule.
Outputs high range limit value or
low range limit value.
Check input.
Er. 04
OUT OF SP RANGE
Static pressure exceeds
specified range.*
3
Displays present output.
Check line pressure (static
pressure).
Er. 05
OVER TEMP (CAP)
Capsule temperature
is outside range (-50 to
130°C).
Displays present output.
Use heat insulation or make
lagging to keep temperature
within range.
Er. 06
OVER TEMP (AMP)
Amplifier temperature
is outside range (-50 to
95°C).
Displays present output.
Use heat insulation or make
lagging to keep temperature
within range.
Er. 07
OVER OUTPUT
Output is outside high or
low range limit value.
Outputs high or low range limit
value.
Check input and range
setting, and change them as
needed.
Er. 08
OVER DISPLAY
Displayed value is
outside high or low range
limit value.
Displays high or low range limit
value.
Check input and display
conditions and modify them
as needed.
Er. 0
ILLEGAL LRV
LRV is outside setting
range.
Holds output immediately before
error occurrence.
Check LRV and modify as
needed.
Er. 10
ILLEGAL URV
URV is outside setting
range.
Holds output immediately before
error occurrence.
Check URV and modify as
needed.
Er. 11
ILLEGAL SPAN
SPAN is outside setting
range.
Holds output immediately before
error occurrence.
Check SPAN and change as
needed.
Er. 12
ZERO ADJ OVER
Zero adjustment is too
large.
Displays present output.
Readjust zero point.
*1: For Model EJA510A and EJA530A, this error code appears when an illegal overpressure is applied to the pressure sensor in
addition to the capsule problem. The Er. 01 will remain even if the normal input pressure is regained.
*2: For Model EJA510A and EJA530A, restart the power to the transmitter. Then if no error code appears, perform necessary
adjustments such as zero-adjustment to continue the operation.
If the error code still exists, replace the capsule assembly.
*3: For Model EJA120A, static pressure cannot be measured. The display is always 0 MPa, but this is not a measured value.