<5. Parameter Summary>
5-8
IM 01C25T01-06EN
Function
Label
Item
Contents
Default value Handling
*
1
Process Alerts Digital Output
EJX
Display of contact output
Off or On
Off
RA
DO Select
EJX
Contact output select
Off, Combination of Pres, SP
and Temp
Off
WA
DO Signal type
EJX
Signal type select
ON WHEN AL. DETECT, OFF
WHEN AL. DETECT
ON WHEN AL.
DETECT
WA
DO Test
EJX
Test output contact
Status High, Status Low, Exit
MA
Pres Alert Mode
Alert Mode for differential pressure Off, Hi Al Detect,Lo Al Detect,
Hi/Lo Al Detect
Off
W
Hi Alert Val
High alert value for differential
pressure
Set the threshold value for
high side alarm
W
Lo Alert Val
Low alert value for differential
pressure
Set the threshold value for
low side alarm
W
SP Alert Mode
Alert Mode for static pressure
Off, Hi Al Detect,Lo Al Detect,
Hi/Lo Al Detect
Off
WD
SP Hi Alert Val
High alert value for static pressure
Set the threshold value for
high side alarm
WD
SP Lo Alert Val
Low alert value for static pressure
Set the threshold value for
low side alarm
WD
Temp Alert Mode
Alert Mode for temperature
Off, Hi Al Detect,Lo Al Detect,
Hi/Lo Al Detect
Off
W
Process Alerts Temp Hi Alert Val
High alert value for temperature
Set the threshold value for
high side alarm
120°C (deg C)
W
Temp Lo Alert Val
Low alert value for temperature
Set the threshold value for
low side alarm
-40°C (deg C)
W
*1: Handling:
R
=Read only,
W
=Read & Write,
M
=Method,
A
=Applicable for option code AL,
G
=Applicable for option code DG6,
D
=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters.
*2:
Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)
*3:
The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.
*4:
For output signal code J, refer to the section 3.3.18.
*5: These parameters may contain adjustment values based on the customer range calibration at the factory upon shipment.
When executing “Clear P sensor trim”, P LTD and P UTD will become “0”, and P LTP and P UTP will become the value of LRV and
URV respectively.