<3. Parameter Setting>
3-22
IM 01C25T01-06EN
3.3.10 Software Write Protection
The transmitter configured data is saved by using a
write protection function. The write protection status
is set to “Yes” when 8 alphanumeric characters are
entered in the
New password
field and transferred
to the transmitter.
When write protection is set to ”Yes,” the transmitter
does not accept parameter changes. When the
same eight alphanumeric string entered in the
New
password
field is also entered in the
Enable wrt
10min
field and transferred to the transmitter, it
will be possible to change transmitter parameters
during a 10 minute period.
To change the transmitter from the write protection
”Yes” status back to write protection ”No” status,
use
Enable wrt 10min
to first release the write
protection function and then enter eight spaces in
the
New password
field.
• Procedure to call up the display using by DD
and DTM (excluding EJX HART 5 DTM based
on FDT1.2)
DD and DTM
(excluding EJX_
HART 5[1.2])
[Root Menu]
→ Detailed setup
→ Device information → Field
device info → Wrt protect menu
→
→ Write protect
Display current protect mode
(Yes: protected, No: not
protected)
→ Enable wrt 10
min
Release the protect function for
10 min.
→ New password
Set the new password or change
the password
• Procedure to call up the display by EJX HART 5
DTM based on FDT1.2
EJX HART 5
DTM based on
FDT1.2
Write Protect →
→ Write Protect
Display current protect mode
(Yes: protected, No: not protected)
→ Enter new
password
Enter the password here to enable
the protect function.
Enter eight spaces to disable the
protect function.
→ Enable write
Enter the password here to release
the protect function for 10 min.
3.3.11 Signal Characterizer
This function is used to compensate the output for
non-linear applications. The characterized values
are applied to the analog output. For the measured
pressure, a maximum of nine coordinates can be
specified between 0-100%. Perform the coordinate
settings while the
S.C.
at
S.C. menu
parameter is
“Disabled”.
To apply the settings to the output, set the
S.C.
parameter to “Enabled”.
Note that the transmitter rejects the activation of the
function by AL. 60 with the following transmitter’s
status:
• When the specified coordinates of x and y are
not incremental as the input increases.
• When the output mode of the output signal is
set as “Sq root”; at the same time, the low cut
mode is set to “Linear”.
F0308.ai
Y
X
100%
0%
100%
INPUT
OUTPUT
Input pressure in %
Characterized value
Follow the steps below to perform the signal
characterizer.
<1> Set the desired number of coordinates on the
line graph
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
[Root Menu]
→ Detailed setup →
Signal condition → S.C. menu →
EJX_HART 5[1.2]
DTM
Configuration → Signal
Characterizer Menu →
→ Num of points
Set the number between 0 and 9
<2> Set the coordinates
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
[Root Menu]
→ Detailed setup →
Signal condition → S.C. menu →
EJX_HART 5[1.2]
DTM
Configuration → Signal
Characterizer Menu →
→ Point setting
Set the coordinates (X-axis,
Y-axis)
<3> Apply the settings
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
[Root Menu]
→ Detailed setup →
Signal condition → S.C. menu →
EJX_HART 5[1.2]
DTM
Configuration → Signal
Characterizer Menu →
→ S.C.
Select “Enabled” or “Disabled”