<7. Operation>
7-9
IM 01C25B01-01E
7.6.4 Loop Test Configuration
Loop test configuration can be changed as below. Output current value (4 mA, 12 mA or 20 mA) for Loop test
can be selected by turning the zero-adjustment screw.
[Available loop test]
4mA: 0% output
12mA: 50% output
20mA: 100% output
Select by the push
button or turning the
extemal adjustment
scerw
F0719.ai
screw
push
Select by the push button
Blinking
Blinking
Run ?/
Cancel ?
7.6.5 Tag Number Configuration
Tag Number is edited by turning the zero-adjustment screw. Up to 8 alphanumeric characters for HART or 16
alphanumeric characters for BRAIN can be set.
F0712.ai
screw
push
Change the first Character
Go to the next Character
Set all other
characters in the
same way
Blinking
Blinking
Save ?/
Cancel ?
7.6.6 Pressure Unit Configuration
Pressure unit for the below table can be changed as below. By turning the zero-adjustment screw, user can
scroll between the various available pressure units.
F0713.ai
screw
push
Select by the push button
Blinking
Blinking
Save ?/
Cancel ?
[Available pressure units]
kPa bar inH
2
O@4degC(39.2degF)
Torr mbar inH
2
O@20degC(68degF)
atm g/cm
2
inHg
MPa kg/cm
2
ftH
2
O@4degC(39.2degF)
hPa Pa ftH
2
O@20degC(68degF)
mmHg
mmH
2
O@4degC(39.2degF)
psi
mmH
2
O@20degC(68degF)
In addition to the above units,
mmAq@4degC, mmAq@20degC,
mmWG@4degC and mmWG@20degC are
available for BRAIN communication type.