<7. Operation>
7-8
IM 01C25B01-01E
7.6.2 Activating Local Parameter Setting
Press the push button on the integral indicator to activate the Local Parameter Setting mode. The transmitter
will exit automatically from the Local Parameter Setting mode if no operation is carried out for 10 minutes.
7.6.3 Parameter Setting Review
Current setting value for the below parameters are shown sequentially by each press of the push button.
Loop test, Tag number, Unit, LRV, URV, Damping, Output mode (linear/square root), Display out 1, Re-range
by applying actual pressure (LRV/URV) and Device Information.
F0711.ai
push
push
push
push
push
push
push
push
push
Process
Measurement
Display
*
push
push
Process
Measurement
Display
1. Loop Test
2. Tag Number
3. Press Unit
4. Press LRV
5. Press URV
6. Damping Time
7. Output Mode (Transfer function)
8. Display Out1
9. LRV-Apply Press
10. URV-Apply Press
11. Device Information
*: [Software revision: 2.03] Up to 6 characters are shown in the bottom line. To review after the 7th character, turn the zero-adjustment
screw and press the push button six times or more.
[Software revision: 3.01 or later] The display automatically scrolls to show all the characters.
To configure each parameter value, turn the zero-adjustment screw on each parameter screen after activating
the Local Parameter Setting mode.
To cancel the Local Parameter Setting configuration, please refer to 7.6.13 Save or Cancel and 7.6.14 Abort
Configuration.