 CONNECTING OPTICAL FIBER CABLE

The figure below shows how optical fiber cables are connected. A single mode fiber side of a mode conditioning patch 

cord has to be connected to an output side of ANT421 and ANT522.

F01E.ai

Multimode optical fiber cable

Mode conditioning patch cord

ANT421

OUT

IN

IN

ANT522

OUT

Mode conditioning patch cord

l

 Optical fiber cable specifications

Maximum permissible optical loss

0 to 7 dB @ 1.3 μm (*1)

Optical Fiber

Type

Quartz multimode fiber

GI 50/125 (*2)

 GI 62.5/125 (*3)

Transmission 

bandwidth

Up to 2 km transmission distance :

200 MHz · km or over @1.3 μm (*1)

2 to 4 km · transmission distance :

400 MHz · km or over @1.3 μm (*1)

*1:   In case existing optical fiber cables are used, check that these has not deviated from the specifications by aging 

degradation.

*2:   IEC 60793-2A1a-compliant

*3:   IEC 60793-2A1b-compliant

l

 Mode conditioning patch cord specifications

Item

GI 62.5/125

GI 50/125

Maximum insertion loss (*1)

0.5 dB

0.5 dB

Coupled power ratio (CPR) (*1)

28 dB < CPR < 40 dB

12 dB < CPR < 20 dB

*1: 

IEEE 802.3z-compliant

Summary of Contents for Centum ANT421

Page 1: ...the temperatures and fans in the cabinet specify With HKU interface A2EE3A H The ESB Bus Adapter A2EE3A should be ordered separately l Installation Position The following table shows the units and num...

Page 2: ...connection FCU for N IO 16 hops for chain and star connection 2 FCU for RIO System Upgrade 8 hops for chain and star connection Maximum transmission distance 3 4 km one hop Optical connector type LC...

Page 3: ...iber cable specifications Maximum permissible optical loss 0 to 7 dB 1 3 m 1 Optical Fiber Type Quartz multimode fiber GI 50 125 2 GI 62 5 125 3 Transmission bandwidth Up to 2 km transmission distance...

Page 4: ...129 130 Unit mm F02E ai A2EE2A N Connector unit for ESB Bus A2EE2A T Connector unit with terminator for ESB Bus IN OUT OPT CN2 CN1 IN OUT OPT CN1 Nominal tolerances Nominal tolerance is 0 8 mm for the...

Page 5: ...side ANT522 as described below ANT421 for master side and ANT522 for slave side ANT421 for master side and A2EN501 for slave side A2EN501 for master side and ANT522 for slave side Dual redundant modu...

Page 6: ...4 km or less Optical ESB Bus Node Unit for dual redundant Optical ESB Bus A L F 1 1 1 A L F 1 1 1 A L R 1 2 1 A L R 1 2 1 A N T 5 2 2 A N T 5 2 2 Optical ESB Bus Node Unit for dual redundant Optical...

Page 7: ...tic cable 4 km Total Max length of Fiber optic cable 8 km Optical ESB Bus Node Unit Optical ESB Bus Node Unit FCU for FIO I O M I O M I O M I O M I O M I O M I O M I O M P S U P S U I O M I O M I O M...

Page 8: ...P S U E C 4 0 1 E C 4 0 1 C P 4 6 1 or C P 4 7 1 C P 4 6 1 or C P 4 7 1 1 1 Optical ESB Bus Repeater Unit P S U P S U A N T 4 1 1 A N T 4 1 1 A N T 4 0 1 A N T 4 0 1 Optical ESB Bus Node Unit I O M I...

Page 9: ...Optical ESB Bus Repeater Slave Module for Multimode Fiber Description Model ANT522 Optical ESB Bus Repeater Slave Module 4 km for Multimode Fiber Suffix Codes 5 Standard type with no explosion protec...

Page 10: ...t to be installed needs to be specified 4 Select the option code ATDOC to follow the ATEX Directive and UKEX Regulation for use in potentially explosive atmospheres Node Unit for Dual Redundant ESB Bu...

Page 11: ...ew GS 33J01A10 01EN n ORDERING INFORMATION Specify the model and suffix codes and option codes when ordering For selecting the right products for explosion protection please refer to TI 33J01J30 01EN...

Reviews: