YOKOGAWA Centum ANT421 Manual Download Page 2

2

All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation

<<Contents>>  <<Index>>

GS 33J60F55-01EN Aug. 6, 2021-00

Table  ANT522 Optical ESB Bus Repeater Slave Module for 4 km

Installable Unit and Slot Number

Optical ESB Bus Node Unit

Base Plate (for FIO)

Optical ESB Bus Repeater Unit

Base Plate (for FIO)

ANB11

, A2BE2D (*3)

ANT10U, A2BE2D (*3)

Single configuration (*1)

B1

IO1, 3, 5, 7, B1

Dual-redundant configuration (*2)

B1, 2

IO1 to 8, B1, 2

*1: 

A dummy cover is to be attached to the even-numbered slot of a pair of slots in which the module is installed. 

*2: 

Install the module in the slots with the following numbers: IO1-2, IO3-4, IO5-6, IO7-8, and B1-2

*3:   Base plate A2BE2D constitutes FIO node unit (ESB Bus Node Unit, Optical ESB Bus Node Unit) or Optical ESB bus 

repeater unit with each function modules. Refer to “A2BE2D Base Plate(for FIO)”

 

(GS 33J60G30-01EN) for detail.

n

 STANDARD SPECIFICATIONS

Function: ESB bus optical transport

Topology: chain and star connection

Maximum number of hops: 2 hops (for chain connection)

Maximum number of hops for each FCU (*1) (*4):

 

FCU (for FIO): 8 hops (for chain and star connection)

 

FCU (for N-IO): 16 hops (for chain and star connection) (*2)

 

FCU (for RIO System Upgrade): 8 hops (for chain and star connection)

Maximum transmission distance (*3): 4 km (one hop)

Optical connector type: LC (IEC61754-20-compliant)

Number of optical fiber cores: 2

Current consumption: 0.5 A

Weight: Approx. 0.25 kg (main body only)

*1: 

The number of paired connection between Master Module and Slave Module.

*2: 

Up to 24 hops are possible only when A2FV50

 is used for FCU and star connection is configured with ANT4

1 via 

EC402. (Supported by CENTUM VP R6.06 or later.)

*3: 

Depending on the characteristics of the optical fiber cable, the maximum transmission distance is different. Please refer to 

the section “Optical fiber cable specifications”.

*4:   For detail about each FCU, refer to “FIO System Overview” (GS 33J60A10-01EN), “N-IO System Overview” (GS 

33J62A10-01EN), and “Field Control Unit, Cabinet Utility Kit (for RIO System Upgrade)” (GS 33J64E10-01EN) 

l

 HKU Interface (ANT522)

When ESB Bus Adapter A2EE3A-

H (With HKU Interface) is connected to ANT522, the environmental information of 

the cabinet where the modules are installed can be transmitted to FCU via optical ESB bus.
The FCU monitors the connected cabinet’s environmental conditions and displays HKU’s operating status as well as 

system alarm on HIS.

Summary of Contents for Centum ANT421

Page 1: ...the temperatures and fans in the cabinet specify With HKU interface A2EE3A H The ESB Bus Adapter A2EE3A should be ordered separately l Installation Position The following table shows the units and num...

Page 2: ...connection FCU for N IO 16 hops for chain and star connection 2 FCU for RIO System Upgrade 8 hops for chain and star connection Maximum transmission distance 3 4 km one hop Optical connector type LC...

Page 3: ...iber cable specifications Maximum permissible optical loss 0 to 7 dB 1 3 m 1 Optical Fiber Type Quartz multimode fiber GI 50 125 2 GI 62 5 125 3 Transmission bandwidth Up to 2 km transmission distance...

Page 4: ...129 130 Unit mm F02E ai A2EE2A N Connector unit for ESB Bus A2EE2A T Connector unit with terminator for ESB Bus IN OUT OPT CN2 CN1 IN OUT OPT CN1 Nominal tolerances Nominal tolerance is 0 8 mm for the...

Page 5: ...side ANT522 as described below ANT421 for master side and ANT522 for slave side ANT421 for master side and A2EN501 for slave side A2EN501 for master side and ANT522 for slave side Dual redundant modu...

Page 6: ...4 km or less Optical ESB Bus Node Unit for dual redundant Optical ESB Bus A L F 1 1 1 A L F 1 1 1 A L R 1 2 1 A L R 1 2 1 A N T 5 2 2 A N T 5 2 2 Optical ESB Bus Node Unit for dual redundant Optical...

Page 7: ...tic cable 4 km Total Max length of Fiber optic cable 8 km Optical ESB Bus Node Unit Optical ESB Bus Node Unit FCU for FIO I O M I O M I O M I O M I O M I O M I O M I O M P S U P S U I O M I O M I O M...

Page 8: ...P S U E C 4 0 1 E C 4 0 1 C P 4 6 1 or C P 4 7 1 C P 4 6 1 or C P 4 7 1 1 1 Optical ESB Bus Repeater Unit P S U P S U A N T 4 1 1 A N T 4 1 1 A N T 4 0 1 A N T 4 0 1 Optical ESB Bus Node Unit I O M I...

Page 9: ...Optical ESB Bus Repeater Slave Module for Multimode Fiber Description Model ANT522 Optical ESB Bus Repeater Slave Module 4 km for Multimode Fiber Suffix Codes 5 Standard type with no explosion protec...

Page 10: ...t to be installed needs to be specified 4 Select the option code ATDOC to follow the ATEX Directive and UKEX Regulation for use in potentially explosive atmospheres Node Unit for Dual Redundant ESB Bu...

Page 11: ...ew GS 33J01A10 01EN n ORDERING INFORMATION Specify the model and suffix codes and option codes when ordering For selecting the right products for explosion protection please refer to TI 33J01J30 01EN...

Reviews: