<5. Functions>
105
IM 01E21A02-03EN
5.6.4 Alarm Display Setting
(1) Alarm display
If an error occurs on this product, an alarm appears on the display. The alarm display modes
are classified into two types: one mode to display a process value and alarm name, and another
mode to display an alarm name and action.
If multiple alarms occur on this product, they will be displayed in sequence on the display.
The setting can be configured with the following parameter.
Display
Device setup ► Detailed setup ► Display set ► Optional config
F
OUNDATION
Fieldbus
Device Configuration ► LTB ► Device Configuration ► Configuration ► Display Operation
Configuration ► (see below)
Block
Name
Relative
Index
Parameter
Description
Display
F
OUNDATION
Fieldbus
LTB
30
Alarm display
Display Alarm
Specifies the alarm display.
From the table below, select the alarm display.
Selection
Description
Display
F
OUNDATION
Fieldbus
Normal
Normal
Displays the process value and alarm name.
F0425.ai
01 : 00
VEL
AO1
FLP
SET
SFT
INC
0.00000m/s
mA
4.000
018: Coil open
0.0%
Detail
Detail
Displays the alarm name and action.
F0426.ai
01 : 00
SET
SFT
INC
System Alarm
Cut the power and
check coil & EX cable.
018: Coil open
(2) Alarm display based on NAMUR NE107
A prefix can be assigned to the alarm name based on NAMUR NE107.
The setting can be configured with the following parameter.
Menu path
Display
Device setup ► Detailed setup ► Display set ► Optional config ► (see below)
F
OUNDATION
Fieldbus
Device Configuration ► LTB ► Device Configuration ► Configuration ► Display Operation
Configuration ► (see below)
Block
Name
Relative
Index
Parameter
Description
Display
F
OUNDATION
Fieldbus
LTB
29
NE107 display
Display NE107
Sets the alarm display based
on NAMUR NE107.