Yingli Solar PV Modules, Installation and User Manual 

page 5

Landscape Orientation

Portrait Orientation

snow load), depending on the module type (please refer to the data sheet for 
this information).

Mounting structures and other mechanical parts must be designed and approved 
to withstand the design wind and snow loads applicable for a particular site. 
Yingli Solar PV modules must not be subjected to forces from the substructure, 
including forces caused by thermal expansion. 

The mounting method must not result in the direct contact of dissimilar 
metals with the aluminum frame of the PV module that will result in galvanic 
corrosion. An addendum to UL Standard 1703 “Flat Plate Photovoltaic Modules 
and Panels” recommends metal combinations not exceed an electrochemical 
potential difference of 0.5 Volts.

Yingli Solar PV modules can be mounted in landscape or portrait orientation, as 
illustrated in Figure 10, provided that the mounting method follows one of the 
acceptable methods listed below. 

Figure 10: Landscape and portrait mounting

In order to maintain the fire class rating, the distance between the PV module 
front surface (glass) and the roof surface shall be at least 10 cm. This spacing 
also allows air flow to cool the PV module. Install PV modules with a minimum 
spacing of 1 cm between neighboring frames to allow for thermal expansion.

Mounting Methods

The following mounting methods are available:

Bolts or Clamps

Refer to figure 12 and 13. Do not modify the existing mounting holes or drill 
new holes. Do not apply excessive pressure on the frame such that the frame 
deforms.

  

Bolts:

 Modules must be mounted using the mounting holes located on the rear 

side of the long frame parts using M8 stainless steel bolts, nuts, and washers. 
The torque of screw tightening should between 14N∙m to 20N∙m.

 
 
 
 
 
 
 
 
 
 

Figure 11: Detail of a bolt mounting attachment

Figure 12 : Mounting rails must run perpendicularly to the long frame

(120 or 144 cell modules)

The 120-cell module is mounted with four inner holes and the 144-cell module is mounted 
with four outer holes, with max mechanical loads of 5400 Pa snow (front) and 2400 Pa 
wind (back).

• 

 Top-down  Clamps:

 Third-party clamps that have been designed for PV 

mounting structures are an approved mounting attachment method for 
Yingli Solar PV modules. Modules must be fastened using clamps applied 
to the top side of the long frame parts. A clamp holds two modules except 
for the clamps at the beginning and end of a module row. The centerline of 
the clamps must be in line with the mounting hole positions plus or minus 
a distance of 50mm. The module clamps should not contact with the front 
glass and deform the frame. and avoiding shadowing effects from the module 
clamps. The module frame is not to be modified under any circumstances. 
The applied torque value should be big enough to fix the modules 
steadily,The torque of screw tightening should between 16N∙m to 24N∙m.

   

 
 
 
 
 
 
 
 
 

Figure 13-1: Detail of a top-down clamp mounting attachment

Figure 13-2:  Clamps mounting positions

Screw

Backing Nut

Nut Washer

PV Laminate

Mounting Rail

Aluminum Frame

L

L

Inner Four-hole Installation

Long Frame Side Clamp Installation -1
       (Clamp Length≥40mm)

L

L

L

Outer Four-hole Installation

Long Frame Side Clamp Installation -2
       (Clamp Length≥40mm)

Short Frame Side Clamp Installation -2

       (Clamp Length≥40mm)

L

L

Inner Four-hole Installation

Long Frame Side Clamp Installation -1
       (Clamp Length≥40mm)

L

L

L

Outer Four-hole Installation

Long Frame Side Clamp Installation -2
       (Clamp Length≥40mm)

Short Frame Side Clamp Installation -2

       (Clamp Length≥40mm)

L

L

Inner Four-hole Installation

Long Frame Side Clamp Installation -1
       (Clamp Length≥40mm)

L

L

L

Outer Four-hole Installation

Long Frame Side Clamp Installation -2
       (Clamp Length≥40mm)

Short Frame Side Clamp Installation -2

       (Clamp Length≥40mm)

 

120 cell module 

Type 

position L/mm 

Max mechanical load 

Long frame type-1 

350

470 

front 5400Pa 

back 2400Pa 

Long frame type-2 

350

470 

front 2400Pa 

back 2400Pa 

0

250 

front 1600Pa 

back 1600Pa 

short frame type-1 

0

250 

front 1600Pa 

back 1600Pa 

 

144 cell module 

Type 

position L/mm 

Max mechanical load 

Long frame type-1 

350

550 

front 5400Pa 

back 2400Pa 

Long frame type-2 

350

550 

front 2400Pa 

back 2400Pa 

0

250 

front 1000Pa 

back 1000Pa 

short frame type-1 

0

250 

front 1000Pa 

back 1000Pa 

 

 

 

 

 

 

Summary of Contents for YL365D-34d 1/2

Page 1: ...n laboratory This Installation and User Manual is available in different languages In cases of discrepancy between versions the English language version shall control Failure to comply with the requir...

Page 2: ...g so may degrade performance or cause irreparable damage and will void any applicable warranties If it is necessary to store PV modules prior to installation the PV modules should remain inside the pa...

Page 3: ...that are approved for use at the maximum short circuit current of the PV module Yingli Solar recommends installers use only sunlight resistant cables qualified for direct current DC wiring in PV syst...

Page 4: ...corrosion An addendum to UL Standard 1703 Flat Plate Photovoltaic Modules and Panels recommends metal combinations not exceed an electrochemical potential difference of 0 5 Volts The frame rails have...

Page 5: ...0 cell module is mounted with four inner holes and the 144 cell module is mounted with four outer holes with max mechanical loads of 5400 Pa snow front and 2400 Pa wind back Top down Clamps Third part...

Page 6: ...wiring as this presents a shock hazard Clean the glass surface of the PV modules with a soft brush using soft clean water PH6 9 with a recommended pressure less than 690kPa which is typical of most m...

Page 7: ...cent of the indicated values of Isc Voc and Pmax under Standard Test Conditions irradiance of 1000 W m2 AM 1 5 spectrum and a cell temperature of 25 C Refer to module datasheets for specific power out...

Page 8: ...E SERIES WITH 35MM FRAME CONT UNITS mm YLM 120 Cell half Cell also valid for YLM 120 cell half cell 1500V Frame Cross Section Legend Legend Grounding holes Mounting holes Drainage holes Mounting toler...

Reviews: