background image

Yingli Solar PV Modules, Installation and User Manual 

page 4

Figure 7: Electrical circuitry of cells and bypass diodes

In the event of a known or suspected diode failure, installers or maintenance 
providers should contact the company the PV modules were purchased from. 
Never attempt to open the junction box of a Yingli Solar PV module yourself.

PV Array Grounding

For optimal performance, Yingli Solar recommends that the negative pole of the 
PV array be connected to ground.

Equipment Grounding

The frame of the PV module, as well as any exposed non-current-carrying metal 
parts of fixed equipment that are able to become energized by the PV system, 
must be connected to the equipment grounding conductor (EGC) in order to 
prevent electrical shock. Even when applicable regulations, code requirements, 
and standards do not require safety-related grounding, Yingli Solar recommends 
grounding all PV

 

module frames in order to ensure the voltage between

 

electrically conductive equipment and earth ground is zero in all circumstances.

Proper equipment grounding is achieved by bonding all exposed non-current-
carrying metal equipment continuously to one another using an appropriately 
sized EGC or racking system that can be used for integrated grounding (see 
Option B in Grounding Methods below). 

Yingli Solar PV modules employ a coated aluminum frame for corrosion 
resistance. In order to properly ground the module frame, the coating must be 
penetrated. 

The potential for corrosion due to the electrochemical action between dissimilar 
metals in contact is minimized if the electrochemical voltage potential between 
the dissimilar metals is low. The grounding method must not result in the direct 
contact of dissimilar metals with the aluminum frame of the PV module that 
will result in galvanic corrosion. An addendum to  UL Standard 1703 “Flat Plate 
Photovoltaic Modules and Panels” recommends metal combinations not exceed 
an electrochemical potential difference of 0.5 Volts.

The frame rails have pre-drilled holes marked with a grounding sign, as 
illustrated in Figure 8. These holes should be used for grounding

 

purposes and 

must not be used for mounting the PV modules. Do not drill additional holes 
into the frame rails. 

 
 
 
 
 
 
 
 
 
 
 
 

Figure 8: Grounding hole detail

The following grounding methods are available:

Option A: Screw Assembly (see Figure 9)

1.  A grounding screw assembly must be attached at a designated grounding 

hole location using only stainless steel hardware. Insert an M5 stainless 
steel screw first through the stainless steel cup washer, and then through the 
grounding hole. 

2.  Loosely engage a stainless steel backing nut and toothed lock washer to the 

screw. 

Figure 9: Grounding screw assembly detail

3.  Bend the EGC into an omega (Ω) shape to tightly fit between the partially 

installed screw head and cup washer. The EGC shall be exclusively in contact 
with stainless steel.

4.  Tighten the screw to 2.3 N∙m torque. The toothed lock washer should be 

visibly engaged to the frame. 

5.  Route the appropriately sized EGC in such a way as to avoid contact with the 

aluminum module frame. 

Option B: Racking Manufacturer Integrated  

Grounding Methods

Yingli Solar PV modules can be grounded by bonding PV modules to a grounded 
racking system. Integrated grounding methods must be certified for grounding 
PV modules and must be installed in accordance     with the specified instructions 
of their respective manufacturers.

option c: additional Third-party grounding Devices

Yingli Solar PV modules can be grounded using third party grounding devices so 
long as they are certified for grounding PV modules and the devices are installed 
according to the manufacturer’s specified instructions. 

M E C H A N I C A L   I N S TA L L AT I O N

General

Yingli Solar PV Modules have been certified for a maximum static load on the 
back of the module of up to 2400 Pa (i.e. wind load) and a maximum static load 
on the front of the module of up to either 2400 Pa or 5400 Pa (i.e. wind and 
snow load), depending on the module type (please refer to the data sheet for 
this information).

Mounting structures and other mechanical parts must be designed and approved 
to withstand the design wind and snow loads applicable for a particular site. 
Yingli Solar PV modules must not be subjected to forces from the substructure, 
including forces caused by thermal expansion. 

The mounting method must not result in the direct contact of dissimilar 
metals with the aluminum frame of the PV module that will result in galvanic 
corrosion. An addendum to UL Standard 1703 “Flat Plate Photovoltaic Modules 
and Panels” recommends metal combinations not exceed an electrochemical 
potential difference of 0.5 Volts.

Yingli Solar PV modules can be mounted in landscape or portrait orientation, as 
illustrated in Figure 10, provided that the mounting method follows one of the 
acceptable methods listed below. 

Grounding Holes

ø0.236in (6mm)

PV Laminate

Backing Nut

Toothed Lock Washer or KEPS Nut

Cup Washer

Aluminum 

Frame

Screw

Equipment 

Grounding 

Conductor

Summary of Contents for YL250P-29b

Page 1: ...ication laboratory This Installation and User Manual is available in different languages In cases of discrepancy between versions the English language version shall control Failure to comply with the...

Page 2: ...g so may degrade performance or cause irreparable damage and will void any applicable warranties If it is necessary to store PV modules prior to installation the PV modules should remain inside the pa...

Page 3: ...Series wiring voltage additive Parallel wiring current additive Fully engage and lock Cap...

Page 4: ...at a designated grounding hole location using only stainless steel hardware Insert an M5 stainless steel screw first through the stainless steel cup washer and then through the grounding hole 2 Loosel...

Page 5: ...Landscape Orientation Portrait Orientation Screw Backing Nut Nut Washer PV Laminate Mounting Rail Aluminum Frame...

Page 6: ...al installation The PV system can generate hazardous voltage even after the system has been disconnected Follow safety regulations for working with live electrical equipment R ecycling Yingli Solar is...

Page 7: ...b YL280C 30b YL330C 36b YL235D 25b YL280D 30b YL335D 36b YL275P 29b YL325P 35b YL245C 25b YL285C 30b YL335C 36b YL240D 25b YL285D 30b YL340D 36b YL280P 29b YL330P 35b YL250C 25b YL290C 30b YL340C 36b...

Page 8: ...5 31 0 8 90 1000 15 YL270P 29b 270 37 9 9 27 30 7 8 80 1000 15 YL265P 29b 265 30 5 8 70 37 8 9 18 1000 15 YL260P 29b 260 30 3 8 59 37 7 9 09 1000 15 YL255P 29b 255 30 0 8 49 37 7 9 01 1000 15 YL250P 2...

Page 9: ...5 YL330D 36b 330 37 2 8 86 46 6 9 29 1000 15 YL325D 36b 325 36 9 8 81 46 2 9 27 1000 15 YL320D 36b 320 36 6 8 75 45 9 9 24 1000 15 YL315D 36b 315 36 2 8 69 45 5 9 21 1000 15 YLM 60 Cell 40mm Series YL...

Page 10: ...age 10 REA R AND S IDE VIE W DIMENS IONS OF MODULE SE RIES with 50mm frame UNITS mm PANDA 72 Cell NH Series Frame Cross Section 12 32 50 SECTION A A Frame P Cross Section A A Legend Legend Grounding h...

Page 11: ...Series also valid for YLM 72Cell 40mm Series REA R AND S IDE VIE W DIME NSIONS OF MODULE SER IES with 40mm frame CONT UNITS mm 1100 946 990 1960 150 55 A A 403 40 1960 577 577 Grounding holes 8 6 Moun...

Page 12: ...IDE VIEW D IME NSIONS OF M ODULE SER IES with 35mm frame UNITS mm 1000 946 990 967 1640 150 55 Drainage holes 8 3 8 Mounting holes 4 6 5 8 Grounding holes 8 6 A A 336 5 35 1640 100 100 100 100 Legend...

Reviews: