background image

Yingli Solar PV Modules, Installation and User Manual  /  page 5

M E C H A N I C A L   I N S TA L L AT I O N

Mounting structures and other mechanical parts must be designed and 
approved to withstand the design wind and snow loads applicable for a 
particular site. Yingli Solar PV modules must not be subjected to forces 
from the substructure, including forces caused by thermal expansion. 
The mounting method must not result in the direct contact of dissimilar 
metals with the aluminum frame of the PV module that will result  

in galvanic corrosion. An addendum to UL 1703 recommends metal 

combinations not exceed an electrochemical potential difference of  
0.5 Volts.
Yingli Solar PV modules can be mounted in landscape or portrait 
orientation, as illustrated in Figure 10, provided that the mounting method 
follows one of the acceptable methods listed below. 

Figure 10: Landscape and portrait mounting

In order to maintain the fire class rating, the distance between the PV 

module front surface (glass) and the roof surface shall be at least 4 

inches (10 cm). This spacing also allows air flow to cool the PV module. 
Install PV modules with a minimum spacing of 0.4 inches (1 cm) between 

neighboring frames to allow for thermal expansion.

 
Mounting Methods

The following mounting methods are available:

Option A: Bolts or clamps

Refer to the Module Supplement at the end of this manual to determine 

how many connection points are required for a specific module series. 

The locations of mounting holes and clamp tolerances are illustrated 
in the drawings located in the Module Supplement. Do not modify the 
existing mounting holes or drill new holes. 

•  Bolts: 

Modules must be mounted using the mounting holes located on 

the rear side of the long frame parts using ¼ inch stainless steel bolts, 

nuts, and washers. Refer to the racking manufacturer for specific torque 

requirements. This mounting method has been tested for a maximum 
static load of 50 psf (2400 Pa) in both the positive and negative 
directions. 

 
 
 
 
 
 
 
 
 

Figure 11: Detail of a bolt mounting attachment

•  Top-down Clamps: 

Third-party clamps that have been designed for 

PV mounting structures are an approved mounting attachment method 
for Yingli Solar PV modules. Modules must be fastened using clamps 
applied to the top side of the long frame parts. A clamp holds two 
modules except for the clamps at the beginning and end of a module 
row. The centerline of the clamps must be in line with the mounting 
hole positions plus or minus a distance of two (2) inches (50mm). 

Clamps must be installed according to the manufacturer’s specified 

instructions with minimum bolt size of 1/4 inches. Do not apply 
excessive pressure on the frame such that the frame deforms. Refer to 

the clamp manufacturer for specific hardware and torque requirements. 

This mounting method has been tested for a maximum static load of 
50 psf (2400 Pa) in both the positive and negative directions. 

Figure 12: Detail of a top-down clamp mounting attachment

Option B: PanelClaw™ Attachment System

Attachment with the PanelClaw system is permitted for Yingli Solar 
PV modules listed in the Module Supplement. Support structures 

manufactured by PanelClaw, Inc. employ a special clamp, or “claw” (Part 
Number: 500-0005) designed to attach to the flange of the PV module at 

each of the four corners, on the two short frame members. 

Figure 13: Detail of claw placement

For proper attachment, place a claw over the PV module frame flange at 
each of the four designated locations and tighten the stainless steel 3/8-
16 x 1.25” hex head cap screw to a torque pressure between 18 ft∙lbf 
(24.4 N∙m) and 20 ft∙lbf (27.1 N∙m). Ensure that the claws are flush with 
both the long and short lengths of the PV module flange. This mounting 

method has been tested for a maximum static load of 50 psf (2400 Pa) in 
both the positive and negative directions. 

Landscape Orientation

Portrait Orientation

Mounting with bolts diagram 
Explode assembly

PV Laminate

Backing Nut

Aluminum Frame

Nut Washer

Support Structure

Screw

Screw

Backing Nut

Nut Washer

PV Laminate

Mounting Rail

Aluminum Frame

Summary of Contents for YGE 245 Series

Page 1: ...rsion shall control Failure to comply with the requirements listed in this manual will invalidate the Limited Warranty for PV Modules as provided by Yingli Solar at the time of sale to the direct customer Additional recommendations are provided to enhance safety practices and performance results Please provide a copy of this manual to the PV system owner for their reference and inform them of all ...

Page 2: ...to any of the surfaces including the frame For your safety do not disassemble or modify Yingli Solar PV modules in any way Doing so may degrade performance or cause irreparable damage and will void any applicable warranties If it is necessary to store PV modules prior to installation the PV modules should remain inside the packaging and protected from exposure that could compromise the durability ...

Page 3: ...nector The module wiring is intended for series connections i e female to male interconnections but can also be used to connect suitable third party electrical devices that may have alternative wiring configurations so long as the manufacturer s instructions are followed Use field wiring with suitable cross sectional areas that are approved for use at the maximum short circuit current of the PV mo...

Page 4: ...Lugs Manufacturer Part Number Material Tightening Torque ILSCO GBL 4DBT Tin plated copper 20 to 25 in lbf 2 3 to 2 6 N m Burndy CL501 TN Tin plated copper 20 25 in lbf 2 3 to 2 6 N m Tyco Electronics SolKlip 1954381 4 Nickel and tin plated copper 15 4 4 1 7 in lbf 1 7 0 5 0 2 N m Table 2 Grounding lug specifications Installation of grounding lugs must be in accordance with the specified instructio...

Page 5: ... 2400 Pa in both the positive and negative directions Figure 11 Detail of a bolt mounting attachment Top down Clamps Third party clamps that have been designed for PV mounting structures are an approved mounting attachment method for Yingli Solar PV modules Modules must be fastened using clamps applied to the top side of the long frame parts A clamp holds two modules except for the clamps at the b...

Page 6: ...lectrical and thermal shock Yingli Solar recommends cleaning PV modules during early morning or late afternoon hours when solar radiation is low and the modules are cooler especially in regions with hotter temperatures Never attempt to clean a PV module with broken glass or other signs of exposed wiring as this presents a shock hazard Clean the glass surface of the PV modules with a soft brush usi...

Page 7: ...ule type Power output Voltage at Pmax Current at Pmax Open circuit voltage Short circuit current Max DC system voltage Max series fuse rating Pmax Vmpp Impp Voc Isc W V A V A V A YGE 295 SERIES YL295P 35b 295 36 3 8 12 45 4 8 63 600 15 YL290P 35b 290 35 8 8 10 45 3 8 62 600 15 YL285P 35b 285 35 5 8 02 45 0 8 50 600 15 YL280P 35b 280 35 5 7 89 45 0 8 35 600 15 YL275P 35b 275 35 5 7 75 45 0 8 30 600...

Page 8: ...3 31 1100 3 94 100 2 17 55 3 94 100 3 94 100 A A A A 38 98 990 37 24 946 1 97 50 22 72 577 16 02 408 77 56 1970 22 72 577 77 56 1970 47 24 1200 3 94 100 Grounding holes 6 ø0 236 6 Mounting holes 6 0 256x0 315 6 5x8 Drainage holes 8 0 12x0 315 3x8 2 17 55 3 94 100 27 44 697 3 94 100 0 47 12 1 26 32 1 97 50 SECTION A A Legend YGE 295 YGE 245 PANDA YGE Z Legend Grounding holes Mounting holes Drainage...

Reviews: