Yingli Solar PV Modules, Installation and User Manual  /  page 4

Equipment Grounding

The frame of the PV module, as well as any exposed non-current-carrying 

metal parts of fixed equipment that are able to become energized by the 

PV system, must be connected to the equipment grounding conductor 
in order to prevent electrical shock. Refer to section 250 of the NEC for 

specific instructions on grounding. Even when applicable regulations, 

code requirements, and standards do not require safety-related 
grounding, Yingli Solar recommends grounding all PV module frames in 
order to ensure the voltage between electrically conductive equipment 
and earth ground is zero in all circumstances.
Proper equipment grounding is achieved by bonding all exposed non-
current-carrying metal equipment continuously to one another using an 
appropriately sized equipment grounding conductor (EGC) or racking 
system that can be used for integrated grounding (see Option C in 
Grounding Methods below). 
Yingli Solar PV modules employ a coated aluminum frame for corrosion 

resistance. In order to properly ground the module frame, the coating 

must be penetrated. 
Grounding wire use copper wire with minimum 12 AWG insulated for a 

minimum 90 

ºC.

The potential for corrosion due to the electrochemical action between 
dissimilar metals in contact is minimized if the electrochemical voltage 
potential between the dissimilar metals is low. The grounding method 
must not result in the direct contact of dissimilar metals with the 
aluminum frame of the PV module that will result in galvanic corrosion. 

An addendum to UL 1703 recommends metal combinations not exceed 

an electrochemical potential difference of 0.5 Volts.
The frame rails have pre-drilled holes marked with a grounding sign, 
as illustrated in Figure 7. These holes should be used for grounding 
purposes and must not be used for mounting the PV modules. Do not 
drill additional holes into the frame rails. 

 
 
 
 
 
 
 
 
 
 
 
 

Figure 7: Grounding hole detail

The following grounding methods are available:

Option A: Grounding Lugs

Manufacturer

Part Number

Material

Tightening Torque

ILSCO

GBL-4DBT

Tin-plated copper

20 to 25 in-lbf 

(2.3 to 2.6 N∙m)

Burndy

®

CL501-TN

Tin-plated copper

20-25 in-lbf 

(2.3 to 2.6 N∙m)

Tyco Electronics

SolKlip 

1954381-4

Nickel and  
tin-plated copper

15 +4.4/-1.7 in-lbf 

(1.7+0.5/-0.2 N∙m)

Table 2: Grounding lug specifications

Installation of grounding lugs must be in accordance with the specified 

instructions of the respective manufacturers. A grounding lug must 
be attached at a designated grounding hole location using #10 
stainless steel hardware. A stainless steel toothed lock washer or KEPS 
nut is required to adequately engage the frame and penetrate the 
nonconductive coating. The screw holding the appropriately sized 

EGC in place must firmly clamp the EGC in order to establish a reliable 

electrical bond.

 

Figure 8: Grounding lug detail

Option B: Screw Assembly

1.  A grounding screw assembly must be attached at a designated 

grounding hole location using only stainless steel hardware. Insert a 
#10 stainless steel screw first through the stainless steel cup washer, 

and then through the grounding hole. 

2.  Loosely engage a stainless steel backing nut and toothed lock washer 

to the screw. 

3.  Bend the EGC into an omega (Ω) shape to tightly fit between the 

partially installed screw head and cup washer. The EGC shall be 
exclusively in contact with stainless steel. 

4.  Tighten the screw to 35 in-lbf (4 N∙m) torque. The toothed lock washer 

should be visibly engaged to the frame. 

5.  Route the appropriately sized EGC in such a way as to avoid contact 

with the aluminum module frame. 

 

 
 
 
 
 
 
 
 
Figure 9: Grounding screw assembly detail

Option C: Racking Manufacturer Integrated  
Grounding Methods

Yingli Solar PV modules can be grounded by bonding PV modules to 

a grounded racking system. Integrated grounding methods must be 
certified to UL 1703 or 2703 for grounding PV modules and must be 
installed in accordance with the specified instructions of their respective 

manufacturers. 

Grounding Holes

ø0.236in (6mm)

PV Laminate

Backing Nut

Toothed Lock Washer or KEPS Nut

Grounding Lug

Equipment 

Grounding 

Conductor

Aluminum 

Frame

Screw

PV Laminate

Backing Nut

Toothed Lock Washer or KEPS Nut

Cup Washer

Aluminum 

Frame

Screw

Equipment 

Grounding 

Conductor

Summary of Contents for YGE 245 Series

Page 1: ...rsion shall control Failure to comply with the requirements listed in this manual will invalidate the Limited Warranty for PV Modules as provided by Yingli Solar at the time of sale to the direct customer Additional recommendations are provided to enhance safety practices and performance results Please provide a copy of this manual to the PV system owner for their reference and inform them of all ...

Page 2: ...to any of the surfaces including the frame For your safety do not disassemble or modify Yingli Solar PV modules in any way Doing so may degrade performance or cause irreparable damage and will void any applicable warranties If it is necessary to store PV modules prior to installation the PV modules should remain inside the packaging and protected from exposure that could compromise the durability ...

Page 3: ...nector The module wiring is intended for series connections i e female to male interconnections but can also be used to connect suitable third party electrical devices that may have alternative wiring configurations so long as the manufacturer s instructions are followed Use field wiring with suitable cross sectional areas that are approved for use at the maximum short circuit current of the PV mo...

Page 4: ...Lugs Manufacturer Part Number Material Tightening Torque ILSCO GBL 4DBT Tin plated copper 20 to 25 in lbf 2 3 to 2 6 N m Burndy CL501 TN Tin plated copper 20 25 in lbf 2 3 to 2 6 N m Tyco Electronics SolKlip 1954381 4 Nickel and tin plated copper 15 4 4 1 7 in lbf 1 7 0 5 0 2 N m Table 2 Grounding lug specifications Installation of grounding lugs must be in accordance with the specified instructio...

Page 5: ... 2400 Pa in both the positive and negative directions Figure 11 Detail of a bolt mounting attachment Top down Clamps Third party clamps that have been designed for PV mounting structures are an approved mounting attachment method for Yingli Solar PV modules Modules must be fastened using clamps applied to the top side of the long frame parts A clamp holds two modules except for the clamps at the b...

Page 6: ...lectrical and thermal shock Yingli Solar recommends cleaning PV modules during early morning or late afternoon hours when solar radiation is low and the modules are cooler especially in regions with hotter temperatures Never attempt to clean a PV module with broken glass or other signs of exposed wiring as this presents a shock hazard Clean the glass surface of the PV modules with a soft brush usi...

Page 7: ...ule type Power output Voltage at Pmax Current at Pmax Open circuit voltage Short circuit current Max DC system voltage Max series fuse rating Pmax Vmpp Impp Voc Isc W V A V A V A YGE 295 SERIES YL295P 35b 295 36 3 8 12 45 4 8 63 600 15 YL290P 35b 290 35 8 8 10 45 3 8 62 600 15 YL285P 35b 285 35 5 8 02 45 0 8 50 600 15 YL280P 35b 280 35 5 7 89 45 0 8 35 600 15 YL275P 35b 275 35 5 7 75 45 0 8 30 600...

Page 8: ...3 31 1100 3 94 100 2 17 55 3 94 100 3 94 100 A A A A 38 98 990 37 24 946 1 97 50 22 72 577 16 02 408 77 56 1970 22 72 577 77 56 1970 47 24 1200 3 94 100 Grounding holes 6 ø0 236 6 Mounting holes 6 0 256x0 315 6 5x8 Drainage holes 8 0 12x0 315 3x8 2 17 55 3 94 100 27 44 697 3 94 100 0 47 12 1 26 32 1 97 50 SECTION A A Legend YGE 295 YGE 245 PANDA YGE Z Legend Grounding holes Mounting holes Drainage...

Reviews: