POWER ON:

 

Turn on or off by long pressing the 

ON/OFF button.  The power LED will illuminate 
green unless battery is low. 
 

WARM-UP:

  During warm-up, the unit will 

beep slowly and the signal LEDs will continu-
ously scroll from left to right until warm-up is 
complete.  Warm-up time is 45 to 90 seconds. 
 

SEARCH: 

 Detector is ready for use when 

signal LEDs stop scrolling from left to right and 
a different beep rate can be heard.
If a leak is detected, the signal LEDs will 
illuminate from left to right and the beep rate 
will increase.  The number of LEDs illuminated 
indicates the strength of the leak. 
 
The default mode is Standard mode.  In 
Standard mode, the detector automatically 
zeros to the background refrigerant.  Once it 
zeros, the alarm will stop and it will only alarm 
to a higher concentration of refrigerant.  To 
reset the zero point, hold the probe in clean 
air for a few seconds to allow the detector to 
re-zero. 
 

ADJUSTING THE SENSITIVITY LEVELS:

  Short 

press the ON/OFF button to toggle sensitivity 
from high to low.  The HIGH or LOW LED will 
illuminate to indicate the current sensitivity 
setting.  High is the default setting during 
power on. 
 

MANUAL MODE:

  Short pressing the MODE 

button toggles between Standard mode and 
Manual mode.  Manual mode is indicated by 
the 1st signal LED slow blinking and both HIGH 
and LOW LEDs being off.   
 
In manual mode, if a leak is detected, the 
detector will alarm until the MODE button is 
long pressed.  The HIGH and LOW LEDs will 
blink for 1 second to indicate the detector is 
zeroing.  At this point, the detector will only 
alarm if a high concentration of refrigerant is 
detected.  

OPERATING INSTRUCTIONS

2

You can also reset the zero point in clean air 
by holding the detector in clean air and long 
pressing the MODE button again. 
 

BATTERY AND CHARGING:  

The power LED 

will slow blink red when the battery is 10% 
or less.  If the battery is depleted completely, 
the power LED will illuminate solid red and the 
unit will not operate.   
 
To charge the unit, plug the supplied micro 
USB cable into an appropriate USB charging 
port per the input specifications (see specifi-
cations).
When charging, the power LED will slow blink 
green until fully charged, then remain solid 
green. 
 

ERRORS: 

 If the battery is above or below 

charge temperature, the unit will not charge 
and the power LED will alternate red and 
green.  In this case, let the battery cool or 
warm up.  The unit will charge once the 
battery is within the safe operating tempera-
ture. 
 
Other faults or internal errors are indicated 
when all LEDs blink.  Contact Ritchie Engineer-
ing Company, Inc. for service in this case. 
 

FILTER REPLACEMENT: 

 Accuprobe

 IR has 

an integrated filter and probe tip.  To replace 
the filter/probe tip assembly, simply unscrew 
the probe tip and screw on the new filter/
probe tip assembly.  Do not attempt to clean 
the filter. 
 

SENSOR/BATTERY REPLACEMENT: 

 The 

sensor and battery in Accuprobe

 IR are not 

field replaceable.  For instrument service, 
contact Ritchie Engineering Company, Inc. 

 