8
Pump
Motor
Unusually
noisy
Pump
High
temp
Condition
Pump Area
Possible Problem
Solution
Worn motor
Replace motor
Loose motor bolts
Tighten bolts
Coupling drive
Adjust/replace coupling
No end play on shaft
Adjust coupling
Dirt, low, improper oil
Flush and replace oil
Air leaks:
1) caps/connection
Tighten
2)
Gaskets/”O”-rings
Replace/put on oil
3) Fittings
Replace/reseal
Damaged or worn bearing
Call factory
Damaged or worn stators
Call factory
Pump out of adjustment
Call factory
Low voltage
Short extension cord
Dirty oil
Flush and replace
Low oil
Add/replace
Lint/foreign material
Open gas ballast
Parts friction
Replace oil/call factory
Too small for system
Size pump for system
Air leaks
Replace/repair
Motor
Replacement Parts
4
2
1
7, 8, 9, 16, 17, 18
4
5
11 or 12,
13, 14 and 15
19
6, 10
Models #93530 and 93533 - 8 CFM (190 L/M)
3
7
Diagnostics Chart
Poor
vacuum
Quiet pump
Exhaust
Seal
Case
Oil
Leaks
Ultimate
vacuum of
pump - does
not meet
mfg. spec
(read with
thermocouple)
Pump
won’t
start
Motor
stalled
hot/cold
Thermal
Condition
Pump Area
Possible Problem
Solution
Dirty oil
Flush 1 to 3 times
Coupling or set screw loose
Repair or replace
Bad exhaust valve
Repair or replace
Pump not oiling
Call factory
Vanes not functioning
Call factory
Stator misaligned
Call factory
Worn pump bearings
Call factory
Pump dropped
Call factory
Bad thermocouple
Clean or replace
Bad motor
Repair or replace
Dirty oil
Flush 1 to 3 times
Air leaks
Repair or replace
System leaks
Isolate/repair
Fitting sealant compound
Repair or replace
System leaks
Repair leaks
Low oil level
Add/replace
Dirty oil
Flush 1 to 3 times
Worn pump
Replace module, call factory
Air leaks at fittings or gasket seals
Replace/repair
Oil level high
Adjust oil level
System vented pressure through pump Check oil level, add or replace oil
Pump tipped over
Check oil level, add or replace oil
Pump shaft
Repair
Worn or damaged seal
Replace
Motor loose
Adjust/tighten, check seal
Gasket bolts loose
Tighten
Oil drain fitting
Repair or replace
Gasket damaged
Replace
Damaged motor
Repair or replace
Damaged pump
Replace/call factory
Closed gas ballast on pumps
Open intake fitting and gas ballast
Low voltage
Shorter extension cord
Cold weather cut-out
Open intake fitting for 1 minute
to warm up while starting
Dirty oil
Flush 1 to 3 times
Noisy
pump