i.8
Parameter Table
This parameter table shows the most important parameters. Default settings are in
bold type
. Refer to the Programming Manual
for a complete list of parameters.
No.
Name
Description
A1-00 Language Selection
0: English
1: Japanese
3: French
5: Spanish
6: Portuguese
A1-01 Access Level Selection
Selects which parameters are accessible via
the HOA keypad.
0: Operation only. A1-01, A1-04, and
A1-06 can be set and monitored, and
U
o
-
oo
parameters can also be viewed.
1: User Parameters. Only parameters
A1-00, A1-01, and A1-04, and A2-01 to
A2-32 in Setup Mode can be set and
monitored.
2: Advanced Access Level. All
parameters can be set and monitored.
A1-02 Control Method
Selection
0: V/f Control
5: Open Loop Vector Control for PM
A1-03 Initialize Parameters
0: No initialization
1110: User Initialize (parameter values
must be stored using parameter o2-03)
2220: 2-Wire Initialization
3330: 3-Wire Initialization
3410: HVAC Initialization
3420: OEM Bypass Initialization
A1-04 Password
When the value set into A1-04 does not
match the value set into A1-05, parameters
A1-01 through A1-03, A1-06, and A2-01
through A2-32 cannot be changed.
A1-05 Password Setting
A1-06 Application Preset
0: Standard
1: Fan
2: Fan with PID Control
3: Return Fan with PID Control
4: Cooling Tower Fan
5: Cooling Tower Fan with PID Control
6: Pump (Secondary)
7: Pump with PID Control
A2-01
to
A2-32
User Parameters 1 to 32
Parameters selected by the user are saved
as User Parameters, including changed
parameters and parameters specifically
selected for quick access.
If parameter A2-33 is set to 1, changed
parameters will be listed between A2-17
and A2-32. Parameters A2-01 through
A2-16 must be manually selected by the
user.
If A2-33 is set to 0, recently viewed
parameters will not be saved to the group of
User Parameters. A2-
oo
parameters are
now available for manual programming.
b1-01
Frequency Reference
Selection for AUTO
Mode
0: HOA keypad
1: Terminals (Analog Input Terminals)
2: Serial communications (APOGEE FLN,
BACnet, MEMOBUS/Modbus, or Metasys
N2)
3: Option card
b1-02
Run Command
Selection for AUTO
Mode
1: Control Circuit Terminal
2: Serial communications (APOGEE
FLN, BACnet, MEMOBUS/Modbus, or
Metasys N2)
3: Option card
b1-03 Stopping Method
Selection
0: Ramp to stop
1: Coast to stop
2: DC Injection Braking to stop
3: Coast with timer
b1-04 Reverse Operation
Selection
0: Reverse enabled
1: Reverse disabled
No.
Name
Description
b1-14 Phase Order Selection
0: Standard
1: Switch phase order (reverses the
direction of the motor)
b1-17 Run Command at Power
Up
0: Disregarded
A new Run command must be issued after
power up.
1: Allowed
Motor will start immediately after power up
if a Run command is already enabled.
b2-01 DC Injection Braking
Start Frequency
Sets the frequency at which DC Injection
Braking starts when “Ramp to stop” (b1-03
= 0) is selected.
b2-02 DC Injection Braking
Current
Sets the DC Injection Braking current as a
percentage of the drive rated current.
b2-03 DC Injection Braking
Time at Start
Sets DC Injection Braking time at start.
Disabled when set to 0.00 seconds.
b2-04 DC Injection Braking
Time at Stop
Sets DC Injection Braking time at stop.
b2-09 Motor Pre-Heat Current
2
Determines the percentage of motor rated
output current used for the motor pre-heat
function.
b3-01 Speed Search Selection
at Start
0: Disabled
1: Enabled
Note:
Default setting is dependent upon
parameter A1-02, Control Method
Selection.
b3-02 Speed Search
Deactivation Current
Sets the current level at which the speed is
assumed to be detected and Speed Search is
ended. Set as a percentage of the drive rated
current.
b3-03 Speed Search
Deceleration Time
Sets output frequency reduction time
during Speed Search.
b3-04
V/f Gain during Speed
Search (Speed
Estimation Type)
Determines how much to lower the V/f ratio
during Speed Search.
Output voltage during Speed Search equals
the V/f setting multiplied by b3-04.
b3-05 Speed Search Delay
Time
When using an external contactor on the
output side, b3-05 delays executing Speed
Search after a momentary power loss to
allow time for the contactor to close.
b3-06
Output Current 1 during
Speed Search (Speed
Estimation Type)
Sets the current injected to the motor at the
beginning of Speed Estimation Speed
Search. Set as a coefficient for the motor
rated current.
b3-10
Speed Search Detection
Compensation Gain
(Speed Estimation
Type)
Sets the gain which is applied to the speed
detected by Speed Estimation Speed Search
before the motor is reaccelerated. Increase
this setting if ov occurs when performing
Speed Search after a relatively long period
of baseblock.
b3-14
Bi-Directional Speed
Search Selection (Speed
Estimation Type)
0: Disabled (uses the direction of the
frequency reference)
1: Enabled (drive detects which way the
motor is rotating)
Note:
Default setting is dependent upon
parameter A1-02, Control Method
Selection.
b3-17
Speed Search Restart
Current Level (Speed
Estimation Type)
Sets the Speed Search restart current level
as a percentage of the drive rated current.
b3-18
Speed Search Restart
Detection Time (Speed
Estimation Type)
Sets the time to detect Speed Search restart.
i.8 Parameter Table
72