n
Output Terminals
lists the output terminals on the drive. Text in parenthesis indicates the default setting for each multi-function output.
Table i.8 Control Circuit Output Terminals
Type
No.
Terminal Name (Function)
Function (Signal Level) Default Setting
Fault Relay
Output
MA
N.O.
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
MB
N.C. output
MC
Fault output common
Multi-Function
Digital Output
MD
N.O.
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
ME
N.C. Output
MF
Common (Speed agree)
M1
Multi-function digital output (During run)
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
M2
M3
Multi-function digital output (Zero speed)
M4
Monitor Output
FM
Analog monitor output 1 (Output frequency)
-10 to +10 Vdc, or 0 to +10 Vdc
AM
Analog monitor output 2 (Output current)
AC
Monitor common
0 V
External Power
Supply
24V
External Power Supply
24 V (Max. 150 mA)
life is estimated at 200,000 times (assumes 1 A, resistive load).
n
Serial Communication Terminals
Table i.9 Control Circuit Terminals: Serial Communications
Type
No.
Signal Name
Function (Signal Level)
Serial Communication
(APOGEE FLN,
BACnet, MEMOBUS/
Modbus, or Metasys
N2)
R+
Communications input (+)
APOGEE FLN, BACnet, MEMOBUS/
Modbus, or Metasys N2 communication: Use
an RS-422 or RS-485 cable to connect the
drive.
• APOGEE FLN
Comm. RS-422/
RS-485, 4.8 kbps
• BACnet Comm.
RS-485, max. 76.8
kbps
• MEMOBUS/
Modbus Comm.
RS-422/RS-485,
max. 115.2 kbps
• Metasys N2 Comm.
RS-422/RS-485, 9.6
kbps
R-
Communications input (-)
S+
Communications output (+)
S-
Communications output (-)
IG
Communications ground
0 V
FE
Option card ground
–
S2 to the ON position. Refer to TOEPC71063610 Z1000U User Manual section on
i.4 Electrical Installation
30