HOA Keypad Display
Fault Name
FbL
PI Feedback Loss
This fault occurs when PI feedback loss detection is programmed to trigger a fault (b5-12 = 2) and
the PI feedback level is below the detection level set to b5-13 for longer than the time set to b5-14.
Cause
Possible Solution
Parameters are set inappropriately
Check b5-13 and b5-14 settings.
Incorrect PI feedback wiring
Correct the wiring.
There is a problem with the feedback sensor
• Check the sensor on the control side.
• Replace the sensor if damaged.
HOA Keypad Display
Fault Name
GF
Ground Fault
• A current short to ground exceeded 50% of rated current on the output side of the drive.
• Setting L8-09 to 1 enables ground fault detection in models 2A0075 to 2A0396, 4A0052
oo
A,
and 4A0065 to 4A0590.
Cause
Possible Solution
Motor insulation is damaged
• Check the insulation resistance of the motor.
• Replace the motor.
A damaged motor cable is creating a short circuit
• Check the motor cable.
• Remove the short circuit and reapply power to the drive
• Check the resistance between the cable and the ground terminal .
• Replace the cable.
Excessive leakage current at the drive output
• Reduce the carrier frequency.
• Reduce the amount of stray capacitance.
The drive started to run during a current offset fault
or while coasting to a stop
• The set value exceeds the allowable setting range while the drive automatically adjusts the current
offset. This only happens when attempting to restart a PM motor that is coasting to stop.
• Set b3-01 to 1 to enable Speed Search at Start.
• Perform Speed Search 1 or 2 (H1-
oo
= 61 or 62) via one of the external terminals.
Note:
Speed Searches 1 and 2 are the same when using OLV/PM.
Hardware problem
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
HOA Keypad Display
Fault Name
LF
Output Phase Loss
• Phase loss on the output side of the drive.
• Setting L8-07 to 1 or 2 enables Phase Loss Detection.
Cause
Possible Solution
The output cable is disconnected
• Check for wiring errors and properly connect the output cable.
• Correct the wiring.
The motor winding is damaged
• Check the resistance between motor lines.
• Replace the motor if the winding is damaged.
The output terminal is loose
• Apply the tightening torque specified in this manual to fasten the terminals.
and Tightening Torque on page 83
The rated current of the motor being used is less
than 5% of the drive rated current
Check the drive and motor capacities.
An output transistor is damaged
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
A single-phase motor is being used
The drive cannot operate a single phase motor.
HOA Keypad Display
Fault Name
LF2
Output Current Imbalance
One or more of the phases in the output current are lost.
Cause
Possible Solution
Phase loss has occurred on the output side of the
drive
• Check for faulty wiring or poor connections on the output side of the drive.
• Correct the wiring.
Terminal wires are loose on the output side of the
drive
Apply the tightening torque specified in this manual to fasten the terminals.
and Tightening Torque on page 83
for details.
5.4 Fault Detection
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
211
5
Troubleshooting
Summary of Contents for Z1000 CIMR-ZU*A Series
Page 399: ......