Auto-Tuning for Permanent Magnet Motors
Automatically sets the V/f pattern and motor parameters E1-
oo
and E5-
oo
when a PM motor is used.
Table 4.20 Types of Auto-Tuning for Permanent Magnet Motors
Type
Setting
Application Conditions and Benefits
Control Mode
OLV/PM
PM Motor Parameter
Settings
T2-01 = 0
• Motor does not rotate during Auto-Tuning.
• Motor test report or motor data similar to
are available.
YES
lists the data that must be entered for Auto-Tuning. Make sure the data is available before starting Auto-Tuning.
The necessary information is usually listed on the motor nameplate or in the motor test report provided by the motor
manufacturer. Also refer to page
for details on the Auto-Tuning process and selection.
Table 4.21 Auto-Tuning Input Data
Input Value
Input Parameter
Unit
Tuning Type (T2-01)
0
Motor Parameter
Settings
Control Mode
A1-02
–
5
Motor Type
T2-03
–
–
Motor Rated Power
T2-04
kW
YES
Motor Rated Voltage
T2-05
Vac
YES
Motor Rated Current
T2-06
A
YES
Motor Rated Frequency
T2-07
Hz
YES
Number of Motor Poles
T2-08
–
YES
Stator Single-phase Resistance
T2-10
Ω
YES
d-Axis Inductance
T2-11
mH
YES
q-Axis Inductance
T2-12
mH
YES
Induced Voltage Constant Unit Selection
T2-13
mVs/rad (elec.)
YES
T2-14
mVmin (mech.)
YES
Tuning Pull-in Current
T2-15
A
–
T2 Tuning Start
T2-18
–
YES
<1> It is only necessary to input either T2-13 or T2-14. Select one and leave the other empty.
<2> Dependent upon T2-13 setting.
u
Before Auto-Tuning the Drive
Check the items below before Auto-Tuning the drive.
n
Basic Auto-Tuning Preparations
• Auto-Tuning requires the user to input data from the motor nameplate or motor test report. Make sure this data is available
before Auto-Tuning the drive.
• For best performance, the drive input supply voltage must be at least equal to or greater than the motor rated voltage.
Note:
Better performance is possible when using a motor with a base voltage that is lower than the input supply voltage (20 V for 200 V class
models and 40 V for 400 V class models). This is particularly important when operating the motor above 90% of base speed, where high
torque precision is required.
• To cancel Auto-Tuning, press the OFF key on the HOA keypad.
• When using a motor contactor, make sure it is closed throughout the Auto-Tuning process.
Table 4.22 Auto-Tuning Input Data
Motor Type
Auto-Tuning Type
Digital Input
Digital Output
Induction
Motor
Stationary Auto-Tuning for Line-to-Line Resistance
Digital input functions
are disabled.
Maintains the status at the start of Auto-Tuning
Rotational Auto-Tuning for V/f Control
Functions the same as during normal operation
PM Motor
PM Motor Parameter Settings
Digital output functions are disabled.
4.8 Auto-Tuning