14
Replace Table D.7 on page 338
u
u
Precautionary Notes on External Heatsink (IP00/Open-Type Enclosure)
When using an external heatsink, UL compliance requires covering exposed capacitors in the main circuit to prevent injury
to surrounding personnel.
The portion of the external heatsink that projects out can be protected with the enclosure or with the appropriate capacitor
cover after completing drive installation. Use
Table D.7
to match drive models with available capacitor covers. Order capacitor
covers from a Yaskawa representative or directly from the Yaskawa sales department.
Table D.7 Capacitor Cover
Model CIMR-Z
o
o
Code Number
Model
Figure
2A0343
100-061-278
ECAT31698-11
Figure D.9
2A0396
4A0361
100-061-278
ECAT31698-11
4A0414
100-061-279
ECAT31740-11
4A0480
100-061-280
ECAT31746-11
4A0515
4A0590
A
B
C
D
E
A– Drive (outside panel)
B– Drive (inside panel)
C– Opening to capacitors
D– Installation screws
E – Capacitor cover
Figure D.9 Capacitor Cover
D.3 UL/cUL Standards
352
YASKAWA ELECTRIC TOEP C710616 45B YASKAWA AC Drive – Z1000 User Manual
14 Replace Table D.7 on page 338
24
YASKAWA TOEP YAISUP 04A YASKAWA AC Drive – Z1000 User Manual Supplement