Model CIMR-Z
o
o
Manufacturer: Bussmann
Model
Fuse Ampere Rating (A)
2A0396
FWH-600A
600
Three-Phase 400 V Class
4A0005
FWH-40B
40
4A0008
FWH-40B
40
4A0011
FWH-45B
45
4A0014
FWH-45B
45
4A0021
FWH-60B
60
4A0027
FWH-60B
60
4A0034
FWH-125B
125
4A0040
FWH-150B
150
4A0052
FWH-200B
200
4A0065
FWH-225A
225
4A0077
FWH-225A
225
4A0096
FWH-225A
225
4A0124
FWH-250A
250
4A0156
FWH-300A
300
4A0180
FWH-350A
350
4A0240
FWH-400A
400
4A0302
FWH-600A
600
4A0361
FWH-800A
800
4A0414
FWH-800A
800
4A0480
FWH-700A
700
4A0515
FWH-800A
800
4A0590
FWH-1000A
1000
n
n
Guarding Against Harmful Materials
When installing IP00/Open Type enclosure drives, use an enclosure that prevents foreign material from entering the drive
from above or below.
n
n
Grounding
The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of grounded
systems, contact your Yaskawa representative for instructions.
u
u
EMC Guidelines Compliance
This drive is tested according to European standards EN61800-3: 2004.
n
n
EMC Filter Installation
Note:
Drive models CIMR-Z
o
2A0011 to 2A0273 and 4A0005 to 4A0302 have a built-in EMC filter.
The following conditions must be met to ensure continued compliance with guidelines.
Refer to EMC Filters on page 347
for EMC filter selection.
Installation Method for CIMR-Z
o
o
2A0011 to 2A0273 and 4A0005 to 4A0302
Verify the following installation conditions to ensure that other devices and machinery used with this drive comply with EMC
guidelines.
1.
Move the screws to the ON position to enable the internal EMC filter.
2.
Use braided shield cable for the drive and motor wiring, or run the wiring through a metal conduit.
3.
Keep wiring as short as possible. Ground the shield on both the drive side and the motor side.
Installation Method for CIMR-Z
o
o
2A0343, 2A0396, and 4A0361 to 4A0590
Verify the following installation conditions to ensure that other devices and machinery used in combination with this drive
also comply with EMC guidelines.
1.
Install an EMC noise filter to the input side specified by Yaskawa for compliance with European standards.
D.2 European Standards
YASKAWA ELECTRIC TOEP C710616 45B YASKAWA AC Drive – Z1000 User Manual
343
D
Standards Compliance
11 Replace Table D.1 on page 328
YASKAWA TOEP YAISUP 04A YASKAWA AC Drive – Z1000 User Manual Supplement
21