No.
Name
Description
o4-17
Set/Reset Real Time
Clock
Sets the current date and time for the Real
Time Clock.
0: — — No Setting
1: Real Time Clock Set
2: Real Time Clock Reset
Note:
Available in drive
software versions PRG:
1013 and later.
T1-01
Auto-Tuning Mode
Selection
2: Stationary Auto-Tuning for Line-to-
Line Resistance
3: Rotational Auto-Tuning for V/f Control
Energy Saving
Note:
The availability of certain
Auto-Tuning methods
depends on the control
mode selected for the
drive.
T1-02
Motor Rated Power
Sets the motor rated power as specified on
the motor nameplate.
Note:
1. Use the following
formula to convert
horsepower into
kilowatts: 1HP = 0.746
kW.
2. Default setting is
dependent on
parameter o2-04,
Drive Model
Selection.
T1-03
Motor Rated Voltage
Sets the motor rated voltage as specified on
the motor nameplate.
T1-04
Motor Rated Current
Sets the motor rated current as specified on
the motor nameplate.
T1-05
Motor Base
Frequency
Sets the rated frequency of the motor as
specified on the motor nameplate.
T1-06
(0706)
Number of Motor Poles Sets the number of motor poles as specified
on the motor nameplate.
T1-07
Motor Base Speed
Sets the rated speed of the motor as
specified on the motor nameplate.
T1-11
Motor Iron Loss
Sets the iron loss for determining the
Energy Saving coefficient.
The value is set to E2-10 (motor iron loss)
set when the power is cycled. If T1-02 is
changed, a default value appropriate for the
motor capacity that was entered will appear.
T1-12
T1 Tuning Start
The drive starts tuning.
U1-01
Frequency Reference
Monitors the frequency reference. Display
units are determined by o1-03.
U1-02
Output Frequency
Displays the output frequency. Display
units are determined by o1-03.
U1-03
Output Current
Displays the output current.
U1-06
Output Voltage
Reference
Displays the output voltage.
U1-10
Input Terminal Status
Displays the input terminal status.
U1 - 10=
00000000
Digital input 1
(terminal S1 enabled)
Digital input 2
(terminal S2 enabled)
Digital input 3
(terminal S3 enabled)
Digital input 4
(terminal S4 enabled)
Digital input 5
(terminal S5 enabled)
Digital input 6
(terminal S6 enabled)
Digital input 7
(terminal S7 enabled)
1
1
1
1
1
1
1
No.
Name
Description
U1-11
Output Terminal Status
Displays the output terminal status.
U1 - 11=
00000000
Multi-Function
Digital Output
(terminal MD-ME-MF)
Digital Output
(terminal M1-M2)
Digital Output
(terminal M3-M4)
Multi-Function
Multi-Function
Not Used
Fault Relay
(terminal MA-MC closed
MA/MB-MC open)
1
1
1
1
0
U1-12
Drive Status
Verifies the drive operation status.
U1 - 12=
00000000
During run
During zero-speed
During REV
During fault reset
signal input
During speed agree
Drive ready
During alarm
detection
During fault detection
1
1
1
1
1
1
1
1
U1-13
Terminal A1 Input
Level
Displays the signal level to analog input
terminal A1.
U1-14
Terminal A2 Input
Level
Displays the signal level to analog input
terminal A2.
U1-16
Output Frequency after
Soft Starter
Displays output frequency with ramp time
and S-curves. Units determined by o1-03.
U1-18
oPE Fault Parameter
Displays the parameter number that caused
the oPE
oo
or Err (EEPROM write error)
error.
U1-19
MEMOBUS/Modbus
Error Code
Displays the contents of a MEMOBUS/
Modbus error.
U1 - 19=
00000000
CRC Error
Data Length Error
Not Used
Parity Error
Overrun Error
Framing Error
Timed Out
Not Used
1
1
0
1
1
1
1
0
U1-25
Software Number
(Flash)
FLASH ID
U1-26
Software No. (ROM)
ROM ID
U1-27
Message ID (OPR)
OPR ID
U1-28
Message ID (INV)
INV ID
U5-01
PI Feedback
Displays the PI feedback value.
U5-02
PI Input
Displays the amount of PI input (deviation
between PI setpoint and feedback).
U5-03
PI Output
Displays PI control output.
U5-04
PI Setpoint
Displays the PI setpoint.
i.8 Parameter Table
YASKAWA ELECTRIC TOEP C710616 54A YASKAWA AC Drive - Z1000 Quick Start Guide