No.
Name
Description
F6-01
Communications Error
Operation Selection
0: Ramp to stop. Decelerate to stop using
the deceleration time in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the
deceleration time in C1-09.
3: Alarm only.
4: Alarm only. Continue operation using the
frequency reference set in d1-04.
5: Alarm only. Decelerate to stop using the
deceleration time in C1-02.
Note:
1. Setting 4 available in
drive software
versions PRG: 1017
and later.
2. Setting 5 available in
drive software
versions PRG: 1018
and later.
H1-01 to
H1-07
Multi-Function Digital
Input Terminal S1 to S7
Function Selection
Selects the functions of terminals S1 to S7.
Note:
Set unused terminals to F.
H2-01
Terminal M1-M2
function selection
(relay)
Selects the functions of terminals M1-M2,
M3-M4, and M5-M6.
H2-02
Terminal M3-M4
function selection
(relay)
H2-03
Terminal M5-M6
function selection
(relay)
H3-01
Terminal A1 Signal
Level Selection
0: 0 to 10 V with zero limit
1: 0 to 10 V without zero limit
2: 4-20 mA
3: 0-20 mA
Note:
Use jumper switch S1 to
set input terminal A1 for
current or voltage.
H3-02
(0434)
Terminal A1 Function
Selection
Sets the function of terminal A1.
H3-03
Terminal A1 Gain
Setting
Sets the level of the input value selected in
H3-02 when 10 V is input at terminal A1.
H3-04
Terminal A1 Bias
Setting
Sets the level of the input value selected in
H3-02 when 0 V is input at terminal A1.
H3-09
Terminal A2 Signal
Level Selection
0: 0 to 10 V with zero limit
1: 0 to 10 V without zero limit
2: 4 to 20 mA
3: 0 to 20 mA
Note:
Use jumper switch S1 to
set input terminal A2 for
current or voltage input
signal.
H3-10
Terminal A2 Function
Selection
Sets the function of terminal A2.
H3-11
Terminal A2 Gain
Setting
Sets the level of the input value selected in
H3-10 when 10 V (20 mA) is input at
terminal A2.
H3-12
Terminal A2 Bias
Setting
Sets the level of the input value selected in
H3-10 when 0 V (0 or 4 mA) is input at
terminal A2.
H3-13
Analog Input Filter
Time Constant
Sets a primary delay filter time constant for
terminals A1 and A2. Used for noise
filtering.
H3-14
Analog Input Terminal
Enable Selection
Determines which analog input terminals
will be enabled when a digital input
programmed for “Analog input enable”
(H1-
oo
= C) is activated.
1: Terminal A1 only
2: Terminal A2 only
3: Terminals A1 and A2
No.
Name
Description
H3-16
Terminal A1 Offset
Adds an offset when the analog signal to
terminal A1 is at 0 V.
H3-17
Terminal A2 Offset
Adds an offset when the analog signal to
terminal A2 is at 0 V.
H4-01
Multi-Function Analog
Output Terminal FM
Monitor Selection
Selects the data to be output through multi-
function analog output terminal FM.
Set the desired monitor parameter to the
digits available in U
o
-
oo
.
For example, enter “103” for U1-03.
H4-02
Multi-Function Analog
Output Terminal FM
Gain
Sets the signal level at terminal FM that is
equal to 100% of the selected monitor
value.
H4-03
Multi-Function Analog
Output Terminal FM
Bias
Sets the signal level at terminal FM that is
equal to 0% of the selected monitor value.
H4-04
Multi-Function Analog
Output Terminal AM
Monitor Selection
Selects the data to be output through multi-
function analog output terminal AM.
Set the desired monitor parameter to the
digits available in U
o
-
oo
.
For example, enter “103” for U1-03.
H4-05
Multi-Function Analog
Output Terminal AM
Gain
Sets the signal level at terminal AM that is
equal to 100% of the selected monitor
value.
H4-06
Multi-Function Analog
Output Terminal AM
Bias
Sets the signal level at terminal AM that is
equal to 0% of the selected monitor value.
H4-07
Multi-Function Analog
Output Terminal FM
Signal Level Selection
0: 0 to 10 V
2: 4 to 20 mA
H4-08
Multi-Function Analog
Output Terminal AM
Signal Level Selection
0: 0 to 10 V
2: 4 to 20 mA
H5-01
Drive Slave Address
Selects drive station slave number (address)
for MEMOBUS/Modbus terminals R+, R-,
S+, S-. Cycle power for the setting to take
effect.
Note:
If this parameter is set to 0,
the drive will be unable to
respond to MEMOBUS/
Modbus commands.
H5-02
Communication Speed
Selection
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
Cycle power for the setting to take effect.
H5-03
Communication Parity
Selection
0: No parity
1: Even parity
2: Odd parity
Cycle power for the setting to take effect.
H5-04
Stopping Method after
Communication Error
(CE)
0: Ramp to stop
1: Coast to stop
2: Fast Stop
3: Alarm only
4: Run at d1-04
H5-05
Communication Fault
Detection Selection
0: Disabled
1: Enabled
If communication is lost for more than two
seconds, a CE fault will occur.
H5-06
Drive Transmit Wait
Time
Set the wait time between receiving and
sending data.
H5-07
RTS Control Selection
0: Disabled. RTS is always on.
1: Enabled. RTS turns on only when
sending.
i.8 Parameter Table
YASKAWA ELECTRIC TOEP C710616 54A YASKAWA AC Drive - Z1000 Quick Start Guide
73