VAN-V07007E
[J7
→
J1000] Replacement Instructions
13/16
J7
J1000
Drive
Function/
Parameter
Parameter
No.
Initial Value
Parameter
No.
Initial Value
Comments
DC injection braking
current
n52 50% b2-02 50%
DC injection time at
stop
n53 0.5
s b2-04 0.50
s
DC injection time at
start
n54 0.0
s b2-03 0.00
s
Stall prevention during
deceleration
n55 0 L3-04 1
J7 J1000
n55
→
0 L3-04
→
1
n55
→
1 L3-04
→
0
Stall prevention level
during acceleration
n56 170% L3-02
-
Initial value of J1000 depends on Duty
mode selection (C6-01).
Stall prevention level
during run
n57 160% L3-06
-
Initial value of J1000 depends on Duty
mode selection (C6-01)
Output frequency
detection level (DO)
n58
0.0 Hz
L4-01
0.0 Hz
Over torque detection
n59 0 L6-01 0
J7 J1000
n59
→
0 L6-01
→
0
n59
→
1 L6-01
→
1
n59
→
2 L6-01
→
3
n59
→
3 L6-01
→
2
n59
→
4 L6-01
→
4
Over torque detection
level
n60 160% L6-02 150%
Over torque detection
time
n61
0.1 s
L6-03
0.1 s
Frequency reference
hold selection
(up/down function)
n62 0 d4-01 0
J7 J1000
n62
→
0 d4-01
→
0
n62
→
1 d4-01
→
1
Torque compensation
gain
n63 1.0 C4-01 1.00
Motor rated slip
n64 E2-02 -
Default value depends on the drive rating.
Motor no-load current
n65 E2-03 -
Default value depends on the drive
capacity.
Set E2-03 = n32 * n65 / 100%
Slip compensation
gain
n66 0.0 C3-01 0.0
Slip compensation
time constant
n67 2.0
s C3-02
2000
ms
J7: Setting unit is 1.0 s
J1000: Setting unit is 1 ms
H5-04 3
H5-05 0
C1-02 10.0
Memobus
communication error
behavior selection
n68 0
C1-09 100
J1000
J7
H5-04 H5-05
n68
→
0
1
n68
→
1
0 (C1-02)
n68
→
2
2 (C1-09)
n68
→
3
3
1
n68
→
4
No effect
0
Memobus
communication error
detection
H5-05 1
Memobus frequency
reference and monitor
units
n69 0
H5-13 0
J7 J1000
n69
→
0 H5-13
→
0
n69
→
1
H5-13
→
1 and
o1-03
→
0
n69
→
2 H5-13
→
2
n69
→
3 H5-13
→
3