Status indication X11: DO
n
2L+
–
LED (green)
Supply voltage available for DO
n
.0 ... .7
–
LEDs (green)
Q+0.0 ... Q+0.7
The according LED is on at active output
n
F
–
LED (red)
Overload or short circuit error
6.4.1 Access to the I/O area
The 312-5BE23 creates in its peripheral area an area for input respectively output data.
Without a hardware configuration the in the following specified default addresses are
used.
6.4.1.1
Address assignment
Sub module
Default address
Access
Assignment
DI10/DO6
124
Byte
Digital Input I+0.0 ... I+0.7
125
Byte
Digital Input I+1.0 ... I+1.7
Counter
768
DInt
Channel 0: Count value / Frequency value
772
DInt
Channel 1: Count value / Frequency value
776
DInt
reserved
780
DInt
reserved
Sub module
Default address
Access
Assignment
DI10/DO6
124
Byte
Digital Output Q+0.0 ... Q+0.7
Counter
768
DWort
reserved
772
DWort
reserved
776
DWort
reserved
780
DWort
reserved
Input range
Output range
VIPA System 300S
+
Deployment I/O periphery
Digital part > Access to the I/O area
HB140 | CPU-SC | 312-5BE23 | en | 18-45