To be compatible with the Siemens SIMATIC Manager the following steps should be exe-
cuted:
1.
Start the Siemens hardware configurator with a new project.
2.
Insert a profile rail from the hardware catalog.
3.
Place at
‘Slot’
number 2 the Siemens CPU 312C (6ES7 312-5BE03-0AB0/V2.6).
5.6 Hardware configuration - I/O modules
After the hardware configuration place the System 300 modules in the plugged sequence
starting with slot 4.
For parametrization double-click during the project engineering at the slot overview on the
module you want to parameterize. In the appearing dialog window you may set the
wanted parameters. By using the SFCs 55, 56 and 57 you may alter and transfer param-
eters for wanted modules during runtime. For this you have to store the module specific
parameters in so called "record sets". More detailed information about the structure of the
record sets is to find in the according module description.
Maximally 8 modules may be addressed by the CPU 312-5BE23. The extension by
means of extension racks is not possible!
Proceeding
Hardware configuration of
the modules
Parametrization
Maximum 8 modules
addressable