As web admin you have access to all functions that are required for uploading and admin-

istrating of websites on the Touch Panel. Additionally you may set the access rights for

user and create user groups. More detailed information about creating and administrating

of websites on the Touch Panel are available in the online documentation of the web

servers.

The login as web admin requires the following steps:

1.

Start the web browser at your PC and enter the following into the address bar: 

IP

address/webadmin

2.

Enter the following into the authentification:

n

User name: 

wince

n

Password: 

vipatp

3.6.4  Telnet server

Telnet is a text based client-server protocol on TCP level. Using of a Telnet client like e.g.
the "MS-DOS console" in your Windows

Ò

 operating system you may execute text based

all file remote functions at your Panel PC like copy, delete and create files and directories.

You may also start applications. Terminating an application is not possible.

The establishing of a Telnet connection is password protected and has the following

approach:

1.

Start a Telnet client like for example "MS-DOS console" at your PC and enter the

following into the address bar:

 telnet IP address

.

ð

When the connection is established, the Panel PC asks for the user name and

the password.

2.

Enter the following:

Login: 

wince

Password:

 vipatp

 (entry is hidden)

ð

After entering valid user data a command line for entries appears:

By entering 

Exit

 res. closing the window you may terminate the Telnet connection at any

time.

After establishment of a Telnet connection the Panel PC provides you with commands. A

list of possible commands with a short description is available via the command help. By

beginning with "help" before a command you receive help to this command.

Web admin

Establishing a Telnet con-

nection

Commands

VIPA HMI

Deployment Touch Panel

Integrated Server > Telnet server

HB160 | TP | 62I-JID0 | en | 17-25

 

38

Summary of Contents for VIPA HMI TP 608C

Page 1: ...TP 62I JID0 Manual HB160 TP 62I JID0 en 17 25 VIPA HMI Touch Panel TP 608C www vipa com en service support manuals...

Page 2: ...62I JID0_000_TP608C 2 EN 2017 VIPA GmbH Ohmstr 4 91074 Herzogenaurach Telephone 49 9132 744 0 Fax 49 9132 744 1864 Email info vipa com Internet www vipa com...

Page 3: ...4 3 3 Connection to a PLC system 28 3 4 Operating system Windows Embedded CE 6 0 Prof 28 3 4 1 General 28 3 4 2 Structure 30 3 5 Communication via ActiveSync 34 3 6 Integrated Server 36 3 6 1 General...

Page 4: ...spective purchase contract Hereby VIPA GmbH declares that the products and systems are in compliance with the essential requirements and other relevant provisions Conformity is indicated by the CE mar...

Page 5: ...ndows CE 6 0 Prof The manual is targeted at users who have a background in automation technology The manual consists of chapters Every chapter provides a self contained description of a specific topic...

Page 6: ...ect design department n installation department n commissioning n operation CAUTION The following conditions must be met before using or commis sioning the components described in this manual Hardware...

Page 7: ...ules that have been damaged by electrostatic discharges can fail after a temperature change mechanical shock or changes in the electrical load Only the consequent implementation of protection devices...

Page 8: ...n Windows CE 6 0 Prof n 62I JID0 CB Movicon 11 CE Standard 4096 I O bytes n Processor Xscale 1 1GHz n Work memory 256Mbyte n User memory 512Mbyte n 380Mbyte memory for user data n CF Card II and MMC...

Page 9: ...USB A USB B 2xEthernet RJ45 Switch 2 3 Structure 2 3 1 Overview 1 Slot for storage medium CF SD MMC 2 Connection for interfaces and power supply 3 Display with touch sensitive area touch screen 1 Comp...

Page 10: ...ck for Ethernet communication 7 RJ45 jack for Ethernet communication 8 Slot for DC 24V voltage supply 9 Slot for CF SD MMC storage medium Please make sure that the Touch Panel always has to be supplie...

Page 11: ...115 2kBaud n Serial bus connection in 2 wire technology using half duplex mode 9 pin SubD plug n Interface is compatible to the COM interface of a PC n Logical signals as voltage levels n Point to poi...

Page 12: ...el is an accumulator with a suitable charging circuit This accu mulator is maintenance free and does not need to be exchanged within the life span of the Touch Panel 2 3 3 Memory management The follow...

Page 13: ...slot until the impact To remove the card touch it at the pulling edge and pull On this slot you can plug storage modules of the type SD or MMC The card may be plugged and removed during runtime and i...

Page 14: ...allation depth 43mm The degrees of protection are only guaranteed when the following is observed Material thickness at the mounting cut out 1 5 6mm The deviation from the plane for the panel cut out i...

Page 15: ...tion voltage to reference earth Inputs outputs AC DC 50V test voltage AC 500V Protective measures against short circuit Environmental conditions to EN 61131 2 Climatic Storage transport EN 60068 2 14...

Page 16: ...lses with Surge an appropriate external protective circuit with lightning protection elements like conductors for lightning and overvoltage is necessary 2 6 Technical data 2 6 1 62I JID0 CB Order no 6...

Page 17: ...ctor Sub D 9 pin female Serial COM1 RS232 COM1 connector Sub D 9 pin male Serial COM2 RS422 485 isolated COM2 connector Sub D 9 pin female Number of USB A interfaces 2 USB A connector USB A host Numbe...

Page 18: ...x 189 mm x 7 5 mm Rear panel 248 mm x 173 mm x 43 mm Installation cut out Width 250 mm Height 175 mm Minimum 1 5 mm Maximum front panel thickness 6 mm Net weight 2325 g Environmental conditions Operat...

Page 19: ...echargeable Lithium Battery Load time for 50 buffering period 10 h Load time for 100 buffering period 48 h Accuracy max deviation per day 10 s Operating controls Touchscreen resistive Touch function S...

Page 20: ...t 0 25 A s Power loss 9 6 W Status information alarms diagnostics Supply voltage display yes Mechanical data Housing Protection type Material die cast aluminum Mounting via integrated pivoted lever Pr...

Page 21: ...Order no 62I JID0 CX Certifications UL certification in preparation KC certification VIPA HMI Hardware description Technical data 62I JID0 CX HB160 TP 62I JID0 en 17 25 21...

Page 22: ...cabinet fronts the Touch Panel requires the following front plate cutting Touch Panel W x H in mm 62I JID0 250 x 175 The fixing technique is integrated in the casing of the Touch Panel and accessible...

Page 23: ...rs to the CageClamps like this 1 Round opening for wires 2 Locking orange for screwdriver 3 Test point for 2mm test tip The picture on the left side shows the cabling step by step from top view 1 For...

Page 24: ...Touch Panel is provided by power supply the VIPA Startup Manager will be loaded At the first startup of the VIPA Startup Manager the following start screen appears n There is a button on the initial...

Page 25: ...the firmware images is shown which are available on the panel and connected storage media These images will be listed with create data and version number Choose your new image If the selected image is...

Page 26: ...owing batch files Start VIPA Webbrowser bat Start VIPA Webserver and Browser fullscreen bat Start VIPA Webserver and Browser bat Start VIPA Webserver bat n Under Delay Time you can adjust a delay time...

Page 27: ...stry settings for the back light the local settings and the LAN settings will be saved by Backup in Flashdisk Backup The name of the backup file is backup bkv Which settings will be saved and the stor...

Page 28: ...the application courses in the PLC according to the configured processes Via dia logues configured before process values may be monitored graphically altered and eval uated 3 4 Operating system Windo...

Page 29: ...ping on an object and then dragging you can move the object on the screen If no object is selected a frame is created by the dragging that selects the touched objects Characteristics with Windows Embe...

Page 30: ...your Touch Panel like e g applications system settings file browser etc 2 Open applications For every open application a button can be found in the task bar There is no button for minimizing The switc...

Page 31: ...allows you to select one of the available software keyboards At the moment the following standard keyboards are implemented At pushed Shift key At pushed a key Please note that can exclusively be ent...

Page 32: ...re keyboard allows you to enter key entries without connecting an external keyboard As soon as an entry is required the software keyboard is automatically shown Hide Input Panel hides the keyboard aga...

Page 33: ...nment via DHCP n System properties System Here you receive information about the version of the current Windows operating system the memory load and sharing alterations here are not accepted into the...

Page 34: ...a mobile device and a PC via USB Many devel oper tools res SCADA project engineering tools use ActiveSync for the data transfer Before you can access the Touch Panel from the PC via ActiveSync you hav...

Page 35: ...ouch Panel The USB device Touch Panel is recognized and the dialog window new part nership opens 2 Choose yes for fixing a partnership and push Next 3 In the opening window de activate all synchroniza...

Page 36: ...ed in the description of the server A client is an application that uses the service of a server within a network For example a web browser is a client because at every call of a website it sends a re...

Page 37: ...on your Touch Panel 3 As soon as your Touch Panel is connected via Ethernet you may monitor the IP address data via in the taskbar 4 After you ve confirmed the pre settings start your ftp client e g W...

Page 38: ...elete and create files and directories You may also start applications Terminating an application is not possible The establishing of a Telnet connection is password protected and has the following ap...

Page 39: ...the VNC server is on delivery deactivated Due to software reasons VIPA does not support the VNC server function With Autostart you can select the automatic startup of the VNC server via the Startup M...

Page 40: ...sources in a Microsoft network like drives and printer Here you may assign existing public directories or printer in the network to local directories or printer in the Touch Panel Condition for this i...

Page 41: ...rname guest Input net use data testserver archiv user guest The connected network drive is then available via network data at the Touch Panel The configuration of a network printer happens with the fo...

Page 42: ...the network connection to the drive archive of test server To save the settings also after power on you have to store them to the registry with START Programs KuK_Tools KuK Tools Store Terminate netwo...

Page 43: ...fferent ways n Electromagnetic fields RF coupling n Magnetic fields with power frequency n Bus system n Power supply n Protected earth conductor Depending on the spreading medium lead bound or lead fr...

Page 44: ...lkie n Sparking lines sparking plugs collector of electric motors welding devices In the most times it is enough to take care of some elementary rules to guarantee the EMC Please regard the following...

Page 45: ...special EMC actions Consider to wire all inductivities with erase links Please consider luminescent lamps can influence signal lines n Create a homogeneous reference potential and ground all electrica...

Page 46: ...ltage even in case of an error Thus you have to connect the ground with the protected earth conductor To avoid ground loops local distant ground constructions cubicles construction and machine parts h...

Page 47: ...e groups Group A Group B Group C Group D Group A 1 2 3 4 Group B 2 1 3 4 Group C 3 3 1 4 Group D 4 4 4 1 1 The lines may be installed in common bundles or cable trusses 2 The lines have to be installe...

Page 48: ...the equipotential bonding conductor must not exceed 10 of the impedance of the screen where screened signal lines are connected between the dif ferent sections of the plant and the screening is connec...

Page 49: ...the cover Do not connect the screen to PIN 1 of the connector In case of stationary operations it is recommended that the remove the insulation from the screened cable without cutting the screen and t...

Page 50: ...Z diode using a varistor using RC network Every cubicle must be provided with a power outlet for the PU These outlets must be wired to the distribution system which is also used to connect the neutra...

Page 51: ...been grounded by means of grounding straps connected to the body of the cubicle Cable routing Cabling divided into groups Power cables 230 400V and signal lines installed in separate channels or bunc...