6.2.2
Thermal Design of Control Panel
Install the
Σ
-V-SD drivers, host controllers, and other units in a control panel.
Use a control panel with an enclosed structure that provides protection against corrosive gases, water, and oil.
Also, design the system so that the temperature rise in the control panel does not cause the temperature to
exceed the ambient operating temperature.
(1) Calorific Value
Power Regeneration Converter
SERVOPACK for One Axis
SERVOPACK for Two Axes
Model
Calorific Value at Continuous Rated Operation
Total (W)
Loss of Control
Block (W)
Loss of Power Block (W)
Total
Inside
Duct
CACP-JU15A3
116.4
13.1
103.3
10.3
93.0
CACP-JU19A3
154.3
13.1
141.2
14.1
127.1
CACP-JU22A3
183.8
13.1
170.7
17.1
153.6
CACP-JU30A3
247.2
14.7
232.5
23.2
209.3
CACP-JU45A3B
394.7
14.7
380.0
38.0
342.0
CACP-JU15D3
66.8
13.1
53.7
5.4
48.4
CACP-JU19D3
90.5
13.1
77.4
7.7
69.7
CACP-JU22D3
104.8
13.1
91.7
9.1
82.6
Model
Calorific Value at Continuous Rated Operation
Total (W)
Loss of Control
Block (W)
Loss of Power Block (W)
Total
Inside
Duct
CACR-JU028ACA
151.4
16.3
135.1
27.0
108.1
CACR-JU036ACA
178.3
16.3
162.0
32.4
129.6
CACR-JU065ACA
321.5
16.2
305.3
30.5
274.8
CACR-JU084ACA
421.9
18.9
403.0
40.3
362.7
CACR-JU102ACA
476.1
18.9
457.2
45.7
411.5
CACR-JU125ACA
611.8
25.9
585.9
58.6
527.3
CACR-JU196ACA
1319.7
27.1
1292.6
129.3
1163.3
CACR-JU014DCA
139.4
16.9
122.5
24.5
98.0
CACR-JU018DCA
165.9
16.9
149.0
29.8
119.2
CACR-JU033DCA
305.7
16.3
289.4
28.9
260.5
CACR-JU042DCA
365.8
18.9
346.9
34.7
312.2
CACR-JU051DCA
422.2
18.9
403.3
40.3
363.0
Model
Calorific Value at Continuous Rated Operation
Total (W)
Loss of Control
Block (W)
Loss of Power Block (W)
Total
Inside
Duct
CACR-JUM23ACA
134.4
23.4
111.0
22.2
88.8
CACR-JUM24ACA
199.4
23.4
176.0
35.2
140.8
CACR-JUM25ACA
248.8
26.8
222.0
22.2
199.8
CACR-JUM23DCA
113.2
23.4
89.8
9.0
80.8
CACR-JUM24DCA
145.6
23.4
122.2
12.2
110.0
CACR-JUM25DCA
215.2
26.8
188.4
18.8
169.6