B.7 E: Motor Parameters
u
E1: V/f Pattern for Motor 1
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
E1-03
(0302)
V/f Pattern Selection
V/F Selection
0: 50 Hz
1: 60 Hz Saturation
2: 50 Hz Saturation
3: 72 Hz
4: 50 Hz VT1
5: 50 Hz VT2
6: 60 Hz VT1
7: 60 Hz VT2
8: 50 Hz HST1
9: 50 Hz HST2
A: 60 Hz HST1
B: 60 Hz HST2
C: 90 Hz
D: 120 Hz
E: 180 Hz
F: Custom V/F
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
V/f w PG
OLV
0: 50 Hz, Constant torque 1
1: 60 Hz, Constant torque 2
2: 60 Hz, Constant torque 3 (50 Hz base)
3: 72 Hz, Constant torque 4 (60 Hz base)
4: 50 Hz, Variable torque 1
5: 50 Hz, Variable torque 2
6: 60 Hz, Variable torque 1
7: 60 Hz, Variable torque 2
8: 50 Hz, High starting torque 1
9: 50 Hz, High starting torque 2
A: 60 Hz, High starting torque 3
B: 60 Hz, High starting torque 4
C: 90 Hz (60 Hz base)
D: 120 Hz (60 Hz base)
E: 180 Hz (60 Hz base)
F: Custom V/f, E1-04 through E1-13 settings define the V/f
pattern
Default: F
Range: 0 to 9;
A to F
E1-04
(0303)
Maximum Output
Frequency
Max Frequency
All Modes
Parameters E1-04 and E1-06 to E1-13 can only be changed
when E1-03 is set to F.
To set linear V/f characteristics, set the same values for E1-07
and E1-09.
In this case, the setting for E1-08 will be disregarded. Ensure
that the five frequencies are set according to the following rules
to prevent triggering an oPE10 fault:
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
Setting E1-11 to 0 disables both E1-11 and E1-12 and the above
conditions do not apply.
Output Voltage (V)
Frequency (Hz)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09
E1-07 E1-06 E1-11 E1-04
Note:
Some parameters may not be available
depending on the control mode.
• E1-07, E1-08, and E1-10 are available only in the following
control modes: V/f Control, V/f with PG, Open Loop Vector.
• E1-11, E1-12, and E1-13 are available only in the following
control modes: V/f Control, V/f with PG, Open Loop Vector,
Closed Loop Vector.
Min.: 40.0
Max.: 400.0
E1-05
(0304)
Maximum Voltage
Max Voltage
Min.: 0.0 V
Max.: 255.0 V
E1-06
(0305)
Base Frequency
Base Frequency
Min.: 0.0
Max.: E1-04
E1-07
(0306)
Middle Output
Frequency
Mid Frequency A
Min.: 0.0
Max.: E1-04
E1-08
(0307)
Middle Output
Frequency Voltage
Mid Voltage A
Min.: 0.0 V
Max.: 255.0 V
E1-09
(0308)
Minimum Output
Frequency
Min Frequency
Min.: 0.0
Max.: E1-04
E1-10
(0309)
Minimum Output
Frequency Voltage
Min Voltage
Min.: 0.0 V
Max.: 255.0 V
E1-11
(030A)
Middle Output
Frequency 2
Mid Frequency B
Default: 0.0 Hz
Min.: 0.0
Max.: E1-04
E1-12
(030B)
Middle Output
Frequency Voltage 2
Mid Voltage B
Default: 0.0 V
Min.: 0.0
Max.: 255.0 V
E1-13
(030C) Base Voltage
Base Voltage
Min.: 0.0
Max.: 255.0 V
<1> Values shown are specific to 200 V class drives. Double the value for 400 V class drives.
<2> Parameter setting value is not reset to the default value when the drive is initialized.
B.7 E: Motor Parameters
516
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
Summary of Contents for U1000 iQpump Drive
Page 705: ......