No.
Parameter Name
Setting Range
Default
F6-30
PROFIBUS-DP Node Address
0 to 125
0
n
F6-31: PROFIBUS-DP Clear Mode Selection
Determines the operation when a Clear Mode command is received.
No.
Parameter Name
Setting Range
Default
F6-31
PROFIBUS-DP Clear Mode Selection
0, 1
0
Setting 0: Reset
Resets the drive operation (frequency reference, inputs, outputs etc.).
Setting 1: Maintain the Previous State
Returns the drive status to the state prior to receiving the command.
n
F6-32: PROFIBUS-DP Data Format Selection
Selects the data format used for PROFIBUS-DP communication.
No.
Parameter Name
Setting Range
Default
F6-32
PROFIBUS-DP Data Format Selection
0, 1
0
Setting 0: PPO-type Data Format
Setting 1: Conventional Data Format
u
CANopen Parameters
Parameters F6-35 and F6-36 set the drive to operate on a CANopen network.
n
F6-35: CANopen Node ID Selection
Selects the node ID of a CANopen option board.
No.
Parameter Name
Setting Range
Default
F6-35
CANopen Node ID Selection
0 to 126
0
n
F6-36: CANopen Communication Speed
Sets the communication speed for a CANopen option card.
No.
Parameter Name
Setting Range
Default
F6-36
CANopen Communication Speed
0 to 8
6
Setting 0: Auto detection
Setting 1: 10 kbps
Setting 2: 20 kbps
Setting 3: 50 kbps
Setting 4: 125 kbps
Setting 5: 250 kbps
Setting 6: 500 kbps
Setting 7: 800 kbps
Setting 8: 1 Mbps
u
DeviceNet Parameters
Parameters F6-50 through F6-63 set the drive to operate on a DeviceNet network.
n
F6-50: DeviceNet MAC Address
Sets the MAC address for a DeviceNet option card.
5.6 F: Option Settings
274
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual