5.7 H: Terminal Functions
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
171
P
a
ra
me
te
r D
eta
ils
5
Figure 5.49
Figure 5.49 Frequency Detection 2 Time Chart
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 195
detection width.
Setting 6: Drive Ready
Output closes whenever the drive is ready to operate the motor.
Refer to b1-08: Run Command Selection while in Programming Mode on page 112
for details on the setting of b1-08.
Setting 7: DC Bus Undervoltage
Output closes whenever the DC bus voltage or control circuit power supply drops below the trip level. The undervoltage
trip level is determined by L2-05. A fault in the DC bus charge circuit will also cause the DC Bus Undervoltage output to
close.
Setting 8: During Baseblock (N.O.)
Output closes to indicate that the drive is in a baseblock state. While Baseblock is executed, output transistors are not
switched and no voltage will be output.
Setting 9: Frequency Reference Source
A digital output programmed for this function shows the frequency reference source that is currently selected.
Setting A: Run Command Source
A digital output programmed for this function shows the Run command source that is currently selected.
Status
Description
Open
During power up, initialization, fault or in Programming Mode (while b1-08 = 0 or 2).
Closed
Drive is ready for operation.
Status
Description
Open
DC bus voltage is above the level set to L2-05
Closed
DC bus voltage has fallen below the trip level set to L2-05.
Status
Description
Open
Drive is not in a baseblock state.
Closed
Baseblock is being executed.
Status
Description
Open
Frequency reference is provided from External Reference 1 (b1-01) or 2 (b1-15)
Closed
Frequency reference is being sourced from the digital operator.
Status
Description
Open
Run command is provided from External Reference 1 (b1-02) or 2 (b1-16)
Closed
Run command is being sourced from the digital operator.
Output
frequency
L4-02
Frequency
Detection 2
ON
OFF
L4-02
L4-01
L4-01