5.2 b: Application
122
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
■
Using PID Control
Applications for PID control are listed in the table below.
■
PID Setpoint Input Methods
When the PID control parameter b5-01 is set to 1 or 2, the frequency reference in b1-01 (or b1-15) becomes the PID
setpoint. If b5-01 is set to 3 or 4, then the PID setpoint can be input from one of the sources in the following table.
Table 5.6 PID Setpoint Sources
Note:
A duplicate allocation of the PID setpoint input will result in an OPE alarm.
■
PID Feedback Input Methods
Either one feedback signal can be input for normal PID control or two feedback signals can be input for controlling a
differential process value.
Normal PID Feedback
The PID feedback can be input from one of the sources listed below.
Table 5.7 PID Feedback Sources
Note:
A duplicate allocation of the PID feedback input will result in an OPE alarm.
Differential Feedback
The second PID feedback signal for differential feedback can come from the sources listed below. The differential
feedback function is automatically enabled when a differential feedback input is assigned.
Table 5.8 PID Differential Feedback Sources
Note:
A duplicate allocation of the PID differential feedback input will result in an OPE alarm.
Application
Description
Sensors Used
Speed Control
Machinery speed is fed back and adjusted to meet the target value. Synchronous control
is performed using speed data from other machinery as the target value
Tachometer
Pressure
Maintains constant pressure using pressure feedback.
Pressure sensor
Fluid Control
Keeps flow at a constant level by feeding back flow data.
Flow rate sensor
Temperature
Control
Maintains a constant temperature by controlling a fan with a thermostat.
Thermocoupler,
Thermistor
PID Setpoint Source
Settings
Analog Input A1
Set H3-02 = C
Analog Input A2
Set H3-10 = C
MEMOBUS/Modbus Register 0006H
Set Bit 1 in register 000FH to 1 and input the setpoint to register 0006H
Pulse Input RP
Set H6-01 = 2
Parameter b5-19
Set parameter b5-18 = 1 and input the PID setpoint to b5-19
PID Feedback Source
Settings
Analog Input A1
Set H3-02 = B
Analog Input A2
Set H3-10 = B
Pulse Input RP
Set H6-01 = 1
PID Differential Feedback Source
Settings
Analog Input A1
Set H3-02 = 16
Analog Input A2
Set H3-10 = 16