Modbus Map SOLECTRIA XGI 1500 (Rev A)
DOCR-XXXXXX
21 of 30
Write “ 120 ” to HV2 Volt Threshold
Write “ 110 ” to HV1 Volt Threshold
Write “ 13.0 ” to HV1 Disconnect Time
Write “ 88 ” to LV1 Volt Threshold
Write “ 21.0 ” to LV1 Disconnect Time
Write “ 70 ” to LV2 Volt Threshold
Write “ 11.0 ” to LV2 Disconnect Time
Write “ 50 ” to LV3 Volt Threshold
Write “ 1.5 ” to LV3 Disconnect Time
Click Save button to apply the settings to local inverter