Modbus Map SOLECTRIA XGI 1500 (Rev A)
DOCR-XXXXXX
12 of 30
Write “ 4 “ to VV Points Active
Write “ 90.0” to VV1 %Voltage Ref
Write “ +30.0 to VV1 %QMax
Write “ 95.0” to VV2 %Voltage Ref
Write “ +0.0 to VV2 %QMax
Write “ 105.0” to VV3 %Voltage Ref
Write “ +0.0 to VV3 %QMax
Write “ 110.0” to VV4 %Voltage Ref
Write “ -30.0 to VV4 %QMax
Click the little box on the top left corner of the configuration window to enable Volt-Var
Click Save button to apply the settings to local inverter
The alternative method is to use software which supports Modbus TCP/IP. The register address is shown
below.