Installation and Operation Guide SOLECTRIA
®
XGI 1500 DCG Series Inverters
DOCR-071081-B
18 of 74
3.3.2
Bottom Conduit Entry
All conduit connections must be made in the designated area on the bottom side of the inverter. Be sure to
remove all metal shavings from the inverter after drilling a hole in order to prevent metal chips and other debris
from damaging the inverter.
Conduit entries into the inverter often allow the introduction of moisture and
condensation to form inside the inverter enclosure. Use an appropriately rated sealant for
all conduit entries to prevent moisture entry and condensation. Condensation inside the
inverter may cause irreparable damage and is not covered under warranty.
Figure 3-9 Conduit Entry Area
17.32 in. (440mm)
5.51 in. (140mm)
1.38 in. (35mm)
1.18 in.
(30mm)
Figure 3-9 Conduit entry area on the bottom face of the inverter