3.
Attach the cables with the accordingly stripped cable screen and fix it by the shield
clamp with the shield bus.
2.5.3 Wiring 16x periphery modules
CAUTION!
Do not connect hazardous voltages!
If this is not explicitly stated in the corresponding module description,
hazardous voltages are not allowed to be connected to the corresponding
terminal block!
n
The 16x periphery module has a removable terminal block for wiring.
n
With the wiring of the terminal block a "push-in" spring-clip technique is used. This
allows a quick and easy connection of your signal and supply lines.
n
The clamping off takes place by means of a screwdriver.
n
Please use copper wire only!
U
max
30V DC
I
max
10A
Cross section solid wire
0.25 ... 0.75mm
2
Cross section with ferrule 0.14 ... 0.75mm
2
Wire type
CU
AWG
24 ... 16
Stripping length
10mm
1
Release area
2
Connection hole for wire
Terminal block connectors
Data
Wiring procedure
1
2
System SLIO
Basics and mounting
Wiring > Wiring 16x periphery modules
HB300 | IM | 053-1EC01 | en | 22-30
25