SIEP C730600 84G DeviceNet Technical Manual
Drive Error Code (Hex.)
DeviceNet Error Code
(Hex.)
Name
Possible Solution
21
7500
bUS [Option Communication Error]
•
Check DeviceNet network cable connections.
•
Check 24 Vdc power supply voltage.
22
Check DeviceNet Option Card installation and connections.
23
•
Cycle drive power.
•
Replace DeviceNet Option or drive if fault continues.
24
25
8321
CF [Control Fault]
•
Check motor parameters.
•
Auto-tune
27
9000
EF0 [Option Card External Fault]
•
Examine the operation of the controller program.
•
Check MI switch setting.
•
Check DeviceNet Option Card LEDs for fault indication.
*1
Drive error code is stored in MEMOBUS/Modbus address 0080 (Hex.).
■
DeviceNet Option Fault Monitors U6-98 [First Fault] and U6-99 [Current Fault]
The DeviceNet option can declare error/warning conditions via drive monitor parameters on the drive keypad as
shown in
Table 12.3 DeviceNet Option Fault Monitor Descriptions
Fault Condition
Fault Declared
Status Value (U6-98/
U6-99)
Description
No Fault
-
0
No Fault
Option Card failure
EF0
1
Option card failure.
PLC in Idle State
EF0
2
PLC is sending polled I/O with all data set to zero.
Force Fault
EF0
3
Network sent a message to force this node to the fault state.
Network Power Loss
bUS
1000
Power on DeviceNet network is off.
Connection Time-out
bUS
1001
This nodes timer (Expect Packet Rate) timed out.
Dup MAC ID
bUS
1002
This node and at least one other node have the same MAC ID. Another node sent its
MAC ID to the network first.
Bus Off
bUS
1003
CAN transceiver senses network error.
Two drive monitor parameters,
U6-98 [First Fault]
and
U6-99 [Current Fault]
, assist the user in network
troubleshooting.
•
U6-98
displays the first declared fault since the last fault reset or power cycle.
U6-98
is only cleared upon drive
power-up.
•
U6-99
displays the present option status.
These parameters are accessible from the DeviceNet network or the drive keypad.
U6-98
and
U6-99
are cleared
upon a drive fault reset and upon power-up.
Note:
In the event of a PLC idle state, the action taken by the DeviceNet Option SI-N3 depends upon the value of parameter
F6-54 [Net Idle
Fault Detection]
.
◆
Option Compatibility
You can connect a maximum of 3 options at the same time depending on the type of option.
Note:
•
You can only connect one option to a GA500 drive. Connect the option to the CN5 connector.
•
You can connect two options to an FP605 drive. Connect the communication option to the CN5-A connector.
•
Compatible communication options are different for different models. Refer to the drive manuals for more information.
Table 12.4 Option Compatibility
Option
Connector
Number of Options Possible
PG-B3
, PG-X3
CN5-B, CN5-C
2
PG-RT3
, PG-F3
CN5-C
1